SCD 400R1111 SPECIFICATION CONTROL DRAWING Title Date Revision ONE CONDUCTOR CABLE, SHIELDED, JACKETED, LIMITED FIRE HAZARD, 600 VOLT 3-8-16 B This specification sheet forms a part of the latest issue of Raychem Specification WCD 3114. SHIELD - TIN COATED COPPER COMPONENT WIRE - 400R0111 JACKET - RADIATION-CROSSLINKED, FLUOROPOLYMER TABLE I. CABLE CONSTRUCTION DETAILS MAXIMUM JACKET THICKNESS OUTSIDE DIAMETER CONDUCTOR SHIELD PART NUMBER WEIGHT (inch) (mm) (inch) (mm) SIZE SIZE 1/ (lbs/1000 ft.) (AWG) (AWG) (kg/km) MINIMUM NOMINAL NOMINAL MAXIMUM 400R1111-26-* 26 40 .006 (.152) .008 (.203) .063 (1.60) .068 (1.73) 4.3 (6.40) 400R1111-24-* 24 40 .006 (.152) .008 (.203) .069 (1.75) .075 (1.91) 5.3 (7.89) 400R1111-22-* 22 38 .006 (.152) .008 (.203) .080 (2.03) .086 (2.18) 7.5 (11.2) 400R1111-20-* 20 38 .006 (.152) .008 (.203) .088 (2.24) .095 (2.41) 9.6 (14.3) 400R1111-18-* 18 36 .006 (.152) .008 (.203) .102 (2.59) .109 (2.77) 13.9 (20.7) 400R1111-16-* 16 36 .006 (.152) .008 (.203) .109 (2.77) .118 (3.00) 16.3 (24.3) 400R1111-14-* 14 36 .006 (.152) .008 (.203) .126 (3.20) .137 (3.48) 22.4 (33.3) 400R1111-12-* 12 36 .006 (.152) .008 (.203) .145 (3.68) .156 (3.96) 31.0 (46.1) 400R1111-10-* 10 36 .006 (.152) .008 (.203) .166 (4.22) .179 (4.55) 43.8 (65.2) NOTE: Nominal values are for information only. Nominal values are not requirements. Users should evaluate the suitability of this product for their application. Specifications are subject to change without notice. Tyco Electronics Corporation also reserves the right to make changes in materials or processing, which do not affect compliance with any specification, without notification to Buyer. 1/ COLORS AND COLOR CODE DESIGNATORS SHALL BE IN ACCORDANCE WITH MIL-STD-681. HOWEVER, DUE TO LENGTH LIMITATIONS OF THE RAYCHEM PART NUMBER, AN ALTERNATIVE COLOR CODE MAY REPLACE MIL-STD-681 COLOR CODE DESIGNATORS. (EXAMPLE: 901/902.. MAY BE REPLACED BYAxx.) OTHER CODES AND SUFFIXES MAY BE ADDED TO THE PART NUMBER, AS NECESSARY, TO CAPTURE ANY ADDITIONAL REQUIREMENTS IMPOSED BY THE PURCHASE ORDER. Raychem, TE Connectivity, TE connectivity (logo), and TE (logo) are trademarks. Raychem Wire & Cable 501 Oakside Avenue DIMENSIONS ARE IN INCHES AND, UNLESS OTHERWISE DESIGNATED, ARE NOMINAL. Redwood City, CA 94063-3800 Page 1 of 2 Phone: 1-800-227-8816 THIS SPECIFICATION SHEET TAKES PRECEDENCE OVER DOCUMENTS REFERENCED HEREIN. Fax: 1-650-361-6297 REFERENCED DOCUMENTS SHALL BE OF THE ISSUE IN EFFECT ON DATE OF INVITATION FOR BID. 2015-2016 Tyco Electronics Corporation. All rights reserved. Page Revision SCD SPECIFICATION CONTROL DRAWING 2 of 2 B 400R1111 TABLE II. CABLE PERFORMANCE DETAILS BEND TESTING MANDREL DIAMETER WEIGHT PART NUMBER (inch) (mm) ( 3%) (lb) (kg) ( 3%) 1/ ACCELERATED COLD ACCELERATED COLD AGING BEND AGING BEND 400R1111-26-* 3.00 (76.2) 3.00 (76.2) .125 (.057) .750 (.340) 400R1111-24-* 3.00 (76.2) 3.00 (76.2) .188 (.085) .750 (.340) 400R1111-22-* 3.00 (76.2) 3.00 (76.2) .188 (.085) 1.50 (.680) 400R1111-20-* 3.00 (76.2) 3.00 (76.2) .188 (.085) 1.50 (.680) 400R1111-18-* 3.00 (76.2) 3.00 (76.2) .250 (.113) 1.50 (.680) 400R1111-16-* 3.00 (76.2) 3.00 (76.2) .250 (.113) 1.50 (.680) 400R1111-14-* 6.00 (152.) 6.00 (152.) .500 (.227) 4.50 (2.04) 400R1111-12-* 6.00 (152.) 6.00 (152.) .500 (.227) 4.50 (2.04) 400R1111-10-* 6.00 (152.) 6.00 (152.) .500 (.227) 4.50 (2.04) CABLE RATINGS AND ADDITIONAL REQUIREMENTS TEMPERATURE RATING: 125C SMOKE TEST: D4, 50 (maximum) Dm, 300 (maximum) Maximum continuous conductor temperature TOXICITY: HCN: 100 ppm (maximum) SO2: 100 ppm (maximum) VOLTAGE RATING: 600 volts (rms) at sea level CO: 3500 ppm (maximum) HF: 100 ppm (maximum) ACCELERATED AGING: 300 3C for 6 hours NO: 100 ppm (maximum) HCI: 500 ppm (maximum) BLOCKING: 150 3C for 6 hours VOLTAGE WITHSTAND (Post Environmental): 1000 volts (rms), 60 Hz, 1 minute DIELECTRIC WITHSTAND: 2500 volts (rms), 60 Hz, 1 minute FLAMMABILITY: Char Length, 5 ft. (1.5 m) (maximum) 1/ PART NUMBER: JACKET COLOR: White preferred The in the part numbers in Tables I and II shall be replaced by color code JACKET CONCENTRICITY: 70% (minimum) designators with a dash separating the component wire color from the jacket JACKET ELONGATION AND TENSILE STRENGTH: color. Elongation, 200% (minimum) Example: AWG 20, white component wire white jacket: 2 Tensile Strength, 4000 lbf/in (27.6 MPa) (minimum) 400R1111-20-9-9 JACKET FLAWS: Spark Test, 1.5 kV (rms) CABLE IDENTIFICATION: Impulse Dielectric Test, 6.0 kV (peak) Jacket shall be marked in contrasting color as follows: LOW TEMPERATURE-COLD BEND: -65 2C for 4 hoursRAYCHEM 400R1111-xx - 600V Yr of Mf (xx = applicable AWG size) SHIELD COVERAGE: 85% (minimum) SMOKE RELEASE: 2 Peak Smoke Release Rate, 0.40 m /s (maximum) 2 Total Smoke Release, 150 m (maximum) 1/ See footer section on page 1