Catalog 1308242 Issued 3-03 (PDF Rev. 03-10) W6/W9 series Magnetic Hydraulic P&B Circuit Breakers Features Typical Resistance and Impedance Designed for the international market. UL Recognized (UL1077 and DC 50/60 Hz. Current Resistance Impedance UL1500), CSA Accepted and VDE approved. (Amps) (Ohms) (Ohms) Ratings to 50 amps. Heavy duty 10-32 stud connections. (W9) 0.2 90 90 Quick-connect or screw terminals. (W6) 1.0 1.2 1.2 Optional 10 amp auxiliary switch. 2.0 0.28 0.28 Several delay curve options. 5.0 0.04 0.04 10.0 0.013 0.013 Choice of toggle or rocker actuator per pole or per unit (W6). 20.0 0.004 0.005 Optional relay/remote trip pole available. 30.0 0.0027 0.004 Trip-free operation. 40.0 0.002 0.002 50.0 0.0015 0.0015 Agency Approvals Tolerance: 0.1 - 4.99 15% 5 - 9.99 20% 10 - 15 25% 16 - 30 50%. UL: Recognized as Supplementary Protector under UL 1077. Available models meet Ignition Protection requirements in accordance with UL1500. File E69543. Mechanical/Environmental Data CSA: Accepted as a Supplementary Protector. File LR15734. Operating Temperature: -40C to +85C. VDE: Approved to VDE 0642/EN 60 934 (Circuit Breakers for Equipment) Humidity: Meets requirements of Mil-STD-202 method 103. License No. 73782. Shock: Tested per Mil-STD-202, method 213, test condition C (100g 6 ms). Users should thoroughly review the technical data before selecting a product part Vibration:Tested per Mil-STD-202, method 201, 10-55 Hz., 0.06 number. It is recommended that users also seek out the pertinent approvals files of the agencies/laboratories and review them to confirm the product meets the (1.52mm) total excursion in 2 planes. requirements for a given application. Fungus And Moisture Resistance: Special moisture resistant finish applied to all ferrous parts. Electrical Data Plastic parts are made of inherently fungus resistant material. Auxiliary Switch: See Auxiliary Switch Ratings Table 2 for details. Marking: International 1 and 0 symbols are marked on the toggle for Calibration: Breakers will hold 100% of rated current. both W6 and W9. W9 units have ON and OFF molded into Breakers may trip between 101% and 124% of rated load the area at the base of the toggle. On a special order basis, (134% for AC/DC units). graphics can be imprinted on the rockers of rocker actuated W6 Breakers must trip at 125% of rated load and above (135% units. VDE approved versions of rocker actuated W6 breakers for AC/DC units). have their rockers imprinted with 1 and 0. Dielectric Strength: 50/60 Hz., 1500V: DC, 1100V. Mounting: Units are mounted with two 6-32 screws from the front of Insulation Resistance: 100 Megohms at 500VDC. the panel. Metric models for use with M3 x 0.5 screws are Endurance: 10,000 on/off cycles - 6000 at rated load, 4000 at no load. available. To maintain published performance specifications, Units tested at six cycles per minute, 1 second on and 9 units should not be mounted more than 90 from their normal seconds off at 25C ambient. upright position. Relay Trip Coil: (Ratings applicable to all W6 models with this option) Weight: Approximately 2.5 ounces per pole. 24 to 277VAC, 150mA minimum available current 6 to 48VDC, 300mA minimum available current. Approvals and Ratings Table 1 W6 Series UL1077/CSA (All Circuit Functions) W6 or W9 Series VDE (Circuit Function X) Current Interrupting Current Interrupting Maximum Frequency Phase Rating Capacity Maximum Frequency Phase Rating Capacity Voltage (Hz) (Amps) (Amps) Voltage (Hz) (Amps) (Amps) 65 DC - 0.2 - 50 2,000 65 DC - 0.2-50 2,000 277 50/60 1 0.2 - 20 5,000 250 50/60 1 0.2-30 5,000 277 50/60 1 21 - 50 2,500 250 50/60 1 31-50 2,000 277/480 50/60 3-Wye 0.2 - 20 5,000 415/240 50/60 3 0.2-30 5,000 W9 Series UL1077/CSA (All Circuit Functions) W6 or W9 Series UL1500 (Circuit Function X) Current Interrupting Current Interrupting Maximum Frequency Phase Rating Capacity Maximum Frequency Phase Rating Capacity Voltage (Hz) (Amps) (Amps) Voltage (Hz) (Amps) (Amps) 65 DC - 0.2 - 50 2,000 48 DC - 0.2 - 50 3,000 277 50/60 1 0.2 - 50 5,000 125/250 50/60 1 0.2 - 50 1,000 277/480 50/60 3-Wye 0.2 - 20 5,000 250 50/60 3-Wye 0.2 - 50 1,000 Auxiliary Switch Ratings Table 2 UL/CSA Switch Voltage Current Terminals Number 50/60 Hz. (Amps) WxTxL A 125 10 .093 x .020 x .250 (2.36 x .51 x 6.40) Revised 03-10 Dimensions are in inches over Dimensions are shown for reference USA: 1-800-522-6752 South America: 55-11-2103-6000 www.tycoelectronics.com (millimeters) unless otherwise purposes only. Specifications and Canada: 1-905-470-4425 Hong Kong: 852-2735-1628 1 specified. availability subject to change. Mexico: 01-800-733-8926 Japan: 81-44-844-8013 C. America: 52-55-1106-0803 UK: 44-8706-080208Catalog 1308242 Issued 3-03 (PDF Rev. 03-10) Time vs. Current Trip Curves For W6 Series and W9 Series AC 50/60 Hz. DC & 50/60 Hz. 400 Hz. CURVE 0 INSTANTANEOUS CURVE 2 STAND ARD DELAY 50/60 Hz. CURVE 3 SHORT DELAY 50/60 Hz. 10,000 10,000 10,000 TRIP TIMES OVERLOAD TRIP TIMES OVERLOAD TRIP TIMES OVERLOAD 50/60 Hz. & DC 400 Hz. (SEC.) (SEC.) 1000 1000 1000 125% 100 ms max. May Trip 125% 10 - 150 125% 1 - 15 150% 55 ms max. 100 ms max. 200% 2.2 - 20 200% .15 - 1.5 100 100 100 200% 30 ms max. 30 ms max. 400% .2 - 2 400% .03 - .25 400% 15 ms max. 15 ms max. 600% .03 - .75 600% .007 - .15 10 10 10 600% 12 ms max. 12 ms max. 800% .007 - .15 800% .003 - .08 800% 12 ms max. 12 ms max. 1000% .005 - .04 1000% .003 - .04 1 1 1 .1 .1 .1 .01 .01 .01 .001 .001 .001 100 200 300 400 500 600 700 800 900 1000 1100 1200 100 200 300 400 500 600 700 800 900 1000 1100 1200 100 200 300 400 500 600 700 800 900 1000 1100 1200 0 0 0 125 150 125 150 125 150 LOAD CURRENT AS A PERCENT LOAD CURRENT AS A PERCENT LOAD CURRENT AS A PERCENT OF BREAKER RATING OF BREAKER RATING OF BREAKER RATING MOTOR START / LONG DELAY CURVE 12 HIGH INRUSH 50/60 Hz. CURVE 13 HIGH INRUSH 50/60 Hz. CURVE 10 HIGH INRUSH 50/60 Hz. AC 10,000 10,000 10,000 OVERLOAD TRIP TIMES OVERLOAD TRIP TIMES OVERLOAD TRIP TIMES (SEC.) (SEC.) (SEC.) 1000 1000 1000 125% 40 - 500 200% 9 - 100 125% 10 - 150 125% .8 - 30 400% 2 - 20 200% 3 - 25 200% .15 - 2.5 100 100 100 600% .8 - 10 400% .5 - 2.5 400% .03 - .3 800% .1 - 4.5 600% .15 - 1 1000% .009 - 2 600% .02 - .15 10 10 10 800% .015 - .7 800% .009 - .12 1000% .009 - .35 1000% .009 - .09 1 1 1 .1 .1 .1 .01 .01 .01 .001 .001 .001 100 200 300 400 500 600 700 800 900 1000 1100 1200 100 200 300 400 500 600 700 800 900 1000 1100 1200 100 200 300 400 500 600 700 800 900 1000 1100 1200 0 0 0 125 150 125 150 125 150 LOAD CURRENT AS A PERCENT LOAD CURRENT AS A PERCENT LOAD CURRENT AS A PERCENT OF BREAKER RATING OF BREAKER RATING OF BREAKER RATING DC CURVE 2 STANDARD DELAY DC CURVE 3 SHORT DELAY DC CURVE 53 DC HIGH INRUSH 10,000 10,000 10,000 OVERLOAD TRIP TIMES OVERLOAD TRIP TIMES OVERLOAD TRIP TIMES (SEC.) (SEC.) (SEC.) 1000 1000 1000 125% 80 - 700 125% 2 - 55 125% .6 - 7 200% 15 - 150 200% .60 - 8 200% .16 - 1.5 400% 2 - 20 100 100 100 600% .70 - 10 400% .1 - 1.5 400% .03 - .25 800% .10 - 3 600% .02 - .5 600% .01 - .13 1000% .01 - .1 10 10 10 800% .004 - .05 800% .004 - .05 1000% .004 - .025 1000% .003 - .015 1 1 1 .1 .1 .1 .01 .01 .01 .001 .001 .001 100 200 300 400 500 600 700 800 900 1000 1100 1200 100 200 300 400 500 600 700 800 900 1000 1100 1200 100 200 300 400 500 600 700 800 900 1000 1100 1200 0 0 0 125 150 125 150 125 150 LOAD CURRENT AS A PERCENT LOAD CURRENT AS A PERCENT LOAD CURRENT AS A PERCENT OF BREAKER RATING OF BREAKER RATING OF BREAKER RATING AC/DC CURVE 34 DC, 50/60 Hz. STANDARD DELAY 10,000 OVERLOAD TRIP TIMES (SEC.) 1000 135% 1 - 90 200% .60 - 20 100 400% .095 - 2 600% .02 - .95 10 800% .002 - .45 1000% .002 - .09 1 .1 .01 .001 100 200 300 400 500 600 700 800 900 1000 1100 1200 0 125 150 LOAD CURRENT AS A PERCENT 135 OF BREAKER RATING Note: For instantaneous curves for all voltages refer to Curve 0 Instantaneous under the AC 50/60 Hz. heading. Pulse Tolerance Specifications Pulse tolerance is defined as a single pulse of a half sine Pulse Tolerance Value Time wave (1/2 cycle or 8 milliseconds) that will not trip the Delay Inertia breaker. An inertia wheel for increased pulse tolerance is Voltage Curve Standard Delay available by specifying P after the time delay curve number in the ordering information. The table at right lists 2 7.5 18 AC 36 18 pulse tolerance values of standard and inertia delay models. 50/60 Hz. 10 18 30 12 18 30 13 18 30 To determine pulse tolerance multiply breaker rating by value in table. For example, a 2A breaker with time delay curve 3 has a standard pulse tolerance of 12A (2A x 6). The same breaker with an inertia delay has a pulse tolerance of 36A (2A x 18). Revised 03-10 Dimensions are in inches over Dimensions are shown for reference USA: 1-800-522-6752 South America: 55-11-2103-6000 www.tycoelectronics.com (millimeters) unless otherwise purposes only. Specifications and Canada: 1-905-470-4425 Hong Kong: 852-2735-1628 2 specified. availability subject to change. Mexico: 01-800-733-8926 Japan: 81-44-844-8013 C. America: 52-55-1106-0803 UK: 44-8706-080208 TIME IN SECONDS TIME IN SECONDS TIME IN SECONDS TIME IN SECONDS TIME IN SECONDS TIME IN SECONDS TIME IN SECONDS TIME IN SECONDS TIME IN SECONDS TIME IN SECONDS