KILOVAC High Voltage DC Contactors KILOVAC High Voltage DC Contactors KILOVAC EV200P Series Latching Contactor With 1 Form X (SPST Latch) Contacts Rated 500+ Amps, 12-900 Vdc Pick Up/Latch (Max) 25C Product Facts 9 Vdc n Latching version of popular Hold (Min) N/A EV200 Series Reset (Max)/Dropout (Min) n Designed to be the 9 Vdc smallest, lowest cost, 7 Duty Cycle, Max 20% lightest weight sealed Coil Resistance 25C 2.5 contactor in the industry at Operate Specs 25C its current rating Operate Time (Typ) 15 ms Operate Bounce (Max) 7 ms n Optional auxiliary contacts Release Time (Max) 15 ms for monitoring position of power contacts Notes: 1 Product can be configured alter- n Hermetically sealed nately with form B or C auxiliary operates in explosive/ switches if required . This changes the product part number, depend- harsh environments with no ing on specific auxiliary configura- oxidation or contamination tion . Consult TE for availability and of coil or contacts part number 2 during long periods of Ambient conditions and conductor design affect rating . Terminal non-operation temperature rise should be 75C n Not position sensitive, max above ambient . Keep relay terminals below 150C max con- can be mounted in any tinuous, 175C max for two hours, orientation Dielectric Withstand Voltage Physical Data and 200C for 1 minute . 3 Terminal to Terminal/ Terminals to Coil Stabilized reading . Contact resis- n RoHS versions available Contact Arrangements tance may exceed spec in the first Main Contacts SPST, Latching 10 minutes of current carry . 1mA max 2,200 Vrms 1 Auxiliary Contacts Up to 2 Form A 4 Units are polarity sensitive . Insulation Resistance Dimensions See drawing Approximately 50% de-rating Terminal to Terminal/ Terminals to Coil for reverse polarity switching . Weight, Nominal .95 lb. (.43 kg) Consult factory for review of 100M min 500Vdc new specific requirements . Environmental Data 5 Over temperature range unless 50M min 500Vdc end of life Shock, 11ms 1/2 Sine noted . Suggested coil pulse = (Operating) 30 G peak 5 Coil Data 50-100 ms . 6 Sine Vibration, 20 G 24V and 48V coils available on peak 6 Nominal Coil Voltage 12 Vdc request consult factory . 55-2000 Hz 7 Intermittent Duty Coil . Coil over- Random Vibration, 14.06 Grms heating can occur if duty cycle 2 2 15 Hz (.002 G /Hz), 100 Hz (.002 G /Hz), 2 2 450 Hz (.12 G /Hz), 900 Hz (.12 G /Hz), Ordering Information 2 2000 Hz (.083 G /Hz) Operating Temperature Range Typical Part Number EV200 P 4 A N A -40C to +85C Series: Electrical Data EV200 = 500+ Amp, 12-900VDC Contactor Voltage Rating Main Contacts (Max) 750 Vdc Contact Form: Current Rating, Continuous P = Latching 2 Main Contacts 500A F = Latching with 1 SPDT Aux . 7 Contact Resistance Coil Voltage: 3 Main Contacts 4 = 12 Vdc 0.2 m max above 300A 5 = 24 Vdc 0.3 m max between 50 and 300A 6 = 48 Vdc Hot Switching Performance 4 (Positive Polarity) Coil Terminations: 200A make/ break 270Vdc A = 15 . 3 in . (300 mm) 10,000 cycles Coil Termination Connector: 600A make/ break 360Vdc N = None 100 cycles 800A break only 360Vdc Mounting & Power Terminals: 15 cycles A = Bottom Mount & Male 10mm x 2000A break only 360Vdc 1 cycle M8 Threaded Terminals Mechanical Life (Min) 75,000 cycles For factory-direct application assistance, dial 800-253-4560, ext. 2055, or 805-220-2055. PAGE 39KILOVAC High Voltage DC Contactors KILOVAC EV200P Series Latching Contactor (Continued) Outline Dimensions For factory-direct application assistance, dial 800-253-4560, ext. 2055, or 805-220-2055. AEROSPACE, DEFENSE & MARINE /// HIGH PERFORMANCE RELAYS