Data sheet Weidmller Interface GmbH & Co. KG RCI484AC4 Klingenbergstrae 26 D-32758 Detmold Germany www.weidmueller.com Product image Individual relays within the RIDERSERIES RCI 2 CO contacts DC coils With integrated status LED, free-wheeling diode and test button General ordering data Version RIDERSERIES RCI, Relay, Number of contacts: 2, CO contact AgNi, Rated control voltage: 24 V DC, Continuous current: 8 A, Plug-in connection, Test button available: Yes Order No. 8870320000 Type RCI484AC4 GTIN (EAN) 4032248613700 Qty. 10 pc(s). Creation date March 26, 2022 8:05:12 AM CET Catalogue status 11.03.2022 / We reserve the right to make technical changes. 1Data sheet Weidmller Interface GmbH & Co. KG RCI484AC4 Klingenbergstrae 26 D-32758 Detmold Germany www.weidmueller.com Technical data Dimensions and weights Depth 26.7 mm Depth (inches) 1.051 inch Height 29 mm Height (inches) 1.142 inch Width 13 mm Width (inches) 0.512 inch Net weight 17 g Temperatures Storage temperature -40 C...85 C Operating temperature -40 C...70 C Humidity 40 C / 93 % rel. humidity, no condensation Probability of failure B10 80.000 AC15: 250Vac/2.5A Rated data UL Certificate No. (cURus) E224238 Control side Rated control voltage 24 V DC Rated current DC 17.5 mA Power rating 419 mW Pull-in/drop-out voltage, typ. 16.8 V / 2.4 V DC Coil resistance 1440 10 % Status indicator Green LED Protective circuit Free-wheeling diode Load side Rated switching voltage 250 V AC Continuous current 8 A Max. switching frequency at rated load Min. switching power 1 mA 24 V, 10 mA 12 0.1 Hz V, 100 mA 5 V Inrush current 15 A / 4 s AC switching capacity (resistive), max. 2000 VA DC switching capacity (resistive), max. 192 W 24 V Switch-on delay 10 ms Switch-off delay 6 ms Contact type 2 CO contact (AgNi) 6 Mechanical service life AC coil 5 x 10 switching 6 cycles, DC coil 10 x 10 switching cycles General data Test button available Version of test button lockable, just when Yes removing the detend lock Mechanical switch position indicator Yes Colour Transparent UL 94 flammability rating V-2 Insulation coordination Rated voltage 250 V Pollution severity 2 Surge voltage category III Insulating material group IIIa Clearance and creepage distances for Dielectric strength for control side - load 5 kV / 1min control side - load side 8 mm side eff Dielectric strength of neighbouring Dielectric strength of open contact 2.5 kV / 1 Min. 1 kV / 1 min contacts eff eff Impulse withstand voltage 5 kV (1.2/50 s) Creation date March 26, 2022 8:05:12 AM CET Catalogue status 11.03.2022 / We reserve the right to make technical changes. 2