Data sheet Weidmller Interface GmbH & Co. KG WAS6 TTA Klingenbergstrae 26 D-32758 Detmold Germany www.weidmueller.com Circuit symbol General ordering data WAS/WAZ6 TTA is a universal signal converter and trip amplifier that can be configured on the PC. Combines the Version Input : universal U, I, R,, Output : I/U universal, 2 functions of isolation, transmission, linearisation and trip x relays amplification in a single module. Order No. 8939670000 Type WAS6 TTA These exceptional characteristics and outstanding GTIN (EAN) 4032248721078 configurability combine to make the TTA truly unique. Qty. 1 pc(s). The TTA functions with stability and precision under a wide range of voltages and ambient temperatures. It is compatible with all standard sensor types. Universal input signals: temperature signals such as resistance thermometer, thermocouple, potentiometer, frequency transmitter, DC voltage signals and current signals Loop-powered or passive input Wide-range power supply: 18 264 V AC/DC User-defined linearization Inputs and outputs can be configured on PC Combined analogue and relay output Ambient temperature range: -40 C 70 C The CBX200 USB interface is used to connect to the PC. The WAS/WAZ6 TTA is also offered as an option with ATEX Zone 2 and UL C1D2 approvals. Creation date September 28, 2021 9:39:36 AM CEST Catalogue status 27.09.2021 / We reserve the right to make technical changes. 1Data sheet Weidmller Interface GmbH & Co. KG WAS6 TTA Klingenbergstrae 26 D-32758 Detmold Germany www.weidmueller.com Technical data Dimensions and weights Depth 112.4 mm Depth (inches) 4.425 inch Width 45 mm Width (inches) 1.772 inch Length 100 mm Length (inches) 3.937 inch Weight 215 g Net weight 256.1 g Temperatures Storage temperature -40 C...85 C Operating temperature -40 C...70 C Humidity 5...95 %, no condensation Probability of failure MTTF 138 Jahre Environmental Product Compliance REACH SVHC Lead 7439-92-1 Input Input current -20...+50 mA (min. interval Input frequency 0.4 mA) adjustable, 2 Hz100 kHz Input voltage -200...500 mV (min. 4 mV Number of inputs span), -20...50 V DC (min. 0.5 V span) 1 Potentiometer 1050 , 50100 , Resistance 100200 , 200400 , 400800 , 800 2 k, 26.5 k, 6.5100 10 5 k Sensor Thermocouples: B, E, J, K, Sensor supply L, N, R, S, T (IEC 60584), PT100, PT1000, (EN 60571) Ni100, Ni1000, (JIS1604), Cu10, Cu25, Cu50, Cu100 (DIN 43760) 2-/3-/4-wire 24 V DC / 22 mA Temperature input range Configurable, B: +100 +1820 C, E: -270+1000 C, J: -270+1200 C, K: -150+1372 C, L: +100 +900 C, N: -180+1300 C, R: -50+1768 C, S: -50+1768 C, T: -270 +400 C, U: -200+600 C, User defined Creation date September 28, 2021 9:39:36 AM CEST Catalogue status 27.09.2021 / We reserve the right to make technical changes. 2