AC-DC Power Supplies XPPower VES150 Series 150 Watts Energy Efficiency Level VI European CoC Tier 2 High Power Density Single Outputs from 12 V to 48 V <0.15 W Standby Power China Compulsory Certification (CCC) Qualified -10 C to 60 C Operation BRAND Low Cost Dimensions: VES150: 6.66 x 2.79 x 1.56 (169.2 x 70.8 x 39.5 mm) Models & Ratings (1) Output Power Output Voltage Output Current Total Regulation Efficiency Model Number 12.0 V 12.50 A 89% VES150PS12 15.0 V 10.0 A 89% VES150PS15 150 W 19.0 V 7.80 A 5% 89% VES150PS19 24.0 V 6.25 A 89% VES150PS24 48.0 V 3.12 A 89% VES150PS48 Notes 1. Typical average of efficiencies measured at 25%, 50%, 75% and 100% load and 230 VAC input. Mechanical Details 47.240.79 (120020) 6.66 (169.2) 2.760.20 (705) 2.79 (70.8) Pin Function UL 2464, 2C+S Black 1 Output + 2 Output + 3 Return 4 Return 4 PINS DC POWER CONNECTOR 1 3 Connected to output Shell return and input ground 2 4 2.360.79 5.510.79 (6020) (14020) 1.56 (39.5) CORE: 14.2*2*7.0*L28.5 Notes 1. All dimensions shown in inches (mm). Tolerance is 0.02 (0.5) maximum, except 3. Weight: 1.87 lbs (850 g) approx. output cable length. 4. Output lead guage is 12 AWG for 12 V model, 14 AWG for 15 V and 19 V models, 2. Output connector: Power Mini DIN, mates with Kycon KPJX-4S or equivalent. 16 AWG for 24 V models and 18 AWG for 48 V model. www.xppower.com 1AC-DC Power Supplies XPPower VES150 Series Input Characteristic Minimum Typical Maximum Units Notes & Conditions Input Voltage 90 264 VAC Input Frequency 47 63 Hz Input Current 1.5/0.8 A Measured at 115/230 VAC Inrush Current 120 A 230 VAC, cold start at 25 C Power Factor EN61000-3-2 Class A Earth Leakage Current 230 A 264 VAC, 60 Hz No Load Input Power 0.15 W Input Protection T3.15A/250 VAC internal fuse in line Output Characteristic Min. Typ. Max. Units Notes & Conditions Output Voltage 12 48 VDC See Models and Ratings table Initial Set Accuracy 2 % At 50% load Minimum Load No minimum load required Start Up Delay 3 s Start Up Rise Time 50 ms Hold Up Time 10 ms Full load and 115 VAC Line Regulation 0.5 % Total Regulation 5 % Maximum deviation, recovering to less than 1% within Transient Response 5 % 500 s for 50% to 100% step load change 12-24V / 48V. Measured with 20 MHz Bandwidth and 10 F Ripple and Noise 240/480 mV pk-pk electrolytic in parallel with 0.1 F ceramic capacitor. Overshoot 5 % At turn on / turn off Overload Protection 120 200 % Overvoltage Protection 180 % Recycle mains to reset Short Circuit Protection Trip and restart (hiccup), auto resetting Temperature Coefficient 0.04 %/C Environmental Characteristic Minimum Typical Maximum Units Notes & Conditions Operating Temperature -10 +60 C Derate from 100% load at 40 C to 50% load at 60 C Cooling Natural convection Operating Humidity 10 90 %RH Non-condensing Storage Temperature -20 +95 C Operating Altitude 5000 m Shock IEC68-2-27, 30 g, 30 ms half sine, 3 times in each of 6 axes Vibration IEC68-2-6, 10-300 Hz, 2 g 15 mins/sweep, 60 mins for each of 3 axes, non operating Derating Curve 100% 80% 60% 40% 20% -10 20 40 60 Ambient Temperature (C) www.xppower.com 2 Output Power (%)