POWER SUPPLY INDICATOR LKM-02 INSTRUCTION MANUAL Zakad Mechaniki i Elektroniki ZAMEL sp.j. J.W. Dzida, K. odziska ul. Zielona 27, 43-200 Pszczyna, Poland Tel. +48 (32) 210 46 65, Fax +48 (32) 210 80 04 www.zamelcet.com, e-mail: marketing zamel.pl DESCRIPTION TECHNICAL DATA The device is used to signal the pre- LKM-02 sence of voltage in a three-phase supply Power terminals: L1, L2, L3, N system. It is realized by means of three Rated voltage: 230/400 V AC LEDs (L1, L2, L3). There are four colours of the LED diode available (red, green, Rated voltage tolerance: -15 +10 % yellow and mixed). LKM-02 power supply Rated frequency: 50 / 60 Hz indicator can be used in the TN-C supply Rated current (type 10, 20, 30, 40): 3,6 / 9 / 4,8 / 6 mA system (with point zero), IT (without zero Power supply indicator: 3x LED point). Number of terminal clamps: 4 2 Section of connecting cables: 0,2 2,5 mm o Ambient temperature range: -20 +45 C FEATURES Operating position: freely Mounting: rail TH 35 (PN-EN 60715) Optical voltage presence signalling, Protection degree: IP20 (PN-EN 60529) LED diodes with increased light emis- Protection level: II sion, Overvoltage category: II long durability of lighting elements, Pollution degree: 2 operating mode without neutral ca- Rated impulse withstand voltage: 1 kV (PN-EN 61000-4-5) ble, Dimensions: monomodular (17,5 mm) 90x17,5x66 mm easy adaptation for special use, Weight: 0,050 kg monomodular casing, Reference standards: PN-EN 62094-1 PN-EN 61000-4-2,3,4,5,6,11 TH-35 DIN rail installation. The device is desi- APPERANCE gned for three-pha- se installation and must be installed in accordance with standards valid in a CAUTION Power terminal (L1) Power terminal (N) particular country. The device should be connected according to the details included in this operating manual. In- stallation, connection and control sho- Power terminal (L2) Power terminal (L3) uld be carried out by a qualified elec - trician staff, who act in accordance with the service manual and the device functions. Disassembling of the de- vice is equal with a loss of guarantee Voltage indicators and can cause electric shock. Before installation make sure the connection cables are not under voltage. The cru- ciform head screwdriver 3,5 mm should be used to instal the device. Improper transport, storage, and use of the device influence its wrong functioning. It is not advisable to instal the device in the follo- wing cases: if any device part is missing or the device is damaged or deformed. In case of improper functioning of the device contact the producer. The symbol means selective collecting of electrical and electronical equipment. It is forbidden to put the used equipment together with other waste VER. 001 18.09.2009MOUNTING, FUNCTIONING CONNECTING wARNING 1. Disconnect the power supply from the TNC connection IT connection If there is no neutral mains by the phase fuse, the circuit- cable connected the breaker or the switch-disconnector system can show wrong that are joined to the proper circuit, indications in case of asymmetrical phase 2. Check if there is no voltage on con- load. nection cables by means of a spe- cial measure equipment, 3. Install LKM-02 device in the switchbo- ard on TH-35 DIN rail, INNER DIAGRAM 4. Connect the cables with the terminals according to installing diagram, 5. Switch on the power supply from the mains. The appropriate LED diode is on if there is power supply on a particular phase wire. The LED diode is off if the- re is no power supply. For proper device functioning the presence of two different potentials is necessary (L1L2, L3N). Neutral connection (N) No neutral connection (N) DIMENSIONS EXAMPLE OF INSTALLATION PRODUCT FAMILY LKM-02 power supply indicator belongs to LKM voltage indicators family. Colour version: 10 - red LED (not applied to LKM-04, LKM-05) 20 - green LED (not applied to LKM-04, LKM-05) 30 - yellow LED (not applied to LKM-04, LKM-05) 40 - LED yellow, green, red (not applied to LKM-03) Device version: 01 - three-phase power supply with neutral Typical use: wire N 02 - three-phase power supply without neutral wire N LKM-02 power supply indicator signals the voltage presence or it absence on every 03 - single-phase power supply with neutral phase of a three -phase supply system: wire N, high brightness LED 04 - three-phase power supply with neutral L1, L3 diodes in ON position signal voltage presence, wire N, high brightness LEDs 05 - three-phase power supply with neutral L2 diode in OFF position signals voltage absence on L2 phase (fuse is switched wire N, high brightness LEDs off). Device symbol wARRANTY CARD There is 24 months guarantee on the product 1. ZMIE ZAMEL SP. J. assures 24 months guarantee for the product. 2. The manufacturers guarantee does not cover any of the following actions: a) mechanical damage during transport, loading / unloading or under other circumstances, b) damage caused by incorrect product mounting or misuse, c) damage caused by unauthorised modifications made by the PURCHASER or any third parties to the product or any other devices needed for the product functioning, d) damage caused by Act of God or any other incidents independent of the manufacturer. 3. The PURCHASER shall lay any claims in writing to the dealer or ZMIE ZAMEL SP. J. 4. ZMIE ZAMEL SP. J. is liable for processing any claim according to current Polish legislation. 5. ZMIE ZAMEL SP. J. shall process the claim at its own discretion: product repair, replacement or money return. 6. The manufacturers guarantee is valid in the Republic of Poland. 7. The PURCHASERs statutory rights in any applicable legislation whether against the retailer arising from the purchase contract or otherwise are not affected by this warranty. Salesman stamp and signature, date of sale VER. 001 18.09.2009