02/11/2015 www.crouzet.com Plug-in Mount 39 mm LN Part number 84870309 Relay for controlling level of conductive liquids Output relay status display LED Sensitivity adjustable from 5 kto 100 k LN Relay for controlling level of conductive liquids Regulation of two levels: minimum, maximum Empty function Plug in (8 or 11 pins) Sensitivity adjustable from 5 kto 100 k LN2 Combined fill and empty functions Combined regulation of pumping out a well and filling a tank Plug in (11 pins) Part numbers Supply voltage Base Type 84 870 309 LN 230 V AC 11-pin Specifications Supply voltage Un 230 V, 110 V, 48 V, 24 V AC, 50/60Hz Operating range 0,851,15xUn Max. absorbed power 3 VA Adjustable sensitivity 5 k100k Measurement accuracy (at maximum sensitivity) 0+30% Electrode voltage (max) 24 V AC (50/60Hz) Electrode current (maximum) 1mA (50/60Hz) Maximum cable capacity 10 nF Response time high level 300 ms Response time low level 500 ms Output relay (according to AC1 resistive load) 1 AgCdO switch 8 A AC max. Galvanic isolation via transformer (4 kV, 8 mm creepage Class II distance) Isolation of contacts and electrodes from power supply 2,5 kV AC Temperature limits use (C) -20+60 Temperature limits stored (C) -30+70 Weight (g) 140 Principles Operating principle Control of maximum and/or minimum levels of conductive liquids (tap water, sea water, waste water, chemical solutions, coffee etc). The principle is based on measurement of the apparent resistance of the liquid between two submerged probes. When this value is lower than the preset threshold on the unit front face, the output relay changes state. To avoid electrolytic phenomena, an AC current funs across the probes. Applications found in environmental, chemical industries and food technology etc. Regulation of two levels: Minimum / Maximum The output relay changes state when the level of liquid reaches the maximum electrode, with the minimum electrode submerged. It returns to its initial state when the minimum probe is no longer in contact with the liquid. Note The probe wire (max length 100 metres) does not have to be screened, but avoid mounting it in parallel with the power supply wires. A screened wire can be used, with the screening connected to the common. Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected02/11/2015 www.crouzet.com o Legend N Max. level Min. level Output relay Down Unit power-up Controlled level Empty function Dimensions (mm) LN connector sockets 8-pin: 25622129 11-pin: 25622078 TRADOSEmptyField Dimensions (mm) LN TRADOSEmptyField Connections LN Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected