02/11/2015 www.crouzet.com DIN Rail Mount 22.5 mm EUL Part number 84872021 Voltage monitoring 2 relays to cover 6 ranges of measurement: 0.2V to 600V Automatic recognition AC/DC Frequency up to 500Hz Part numbers Measurement range Supply voltage Type EUL 0,260V 24 V AC 84 872 021 Specifications Supply Voltage supply tolerance -15% / +15% limited to -15% / +10% if products are mounted without space between them Operating range 0,851,15Un Immunity from micro power cuts 10 ms Inputs and measuring circuit Frequency of measured signal 40500Hz Threshold adjustment 10100%ofthemeasurementrange Hysteresis 550%ofdisplayedthreshold Display precision 10% of full scale Repetition accuracy with constant parameters 0,1% Measuring error with voltage drift < 0,5% Measuring error with temperature drift 0,05% /C Timing Delay on thresold crossing Tt 0,13s10% Output Type of output 1 changeover AgNi, 8 AAC max Type of contacts No cadmium Maximum breaking voltage 250 VAC/DC Max. breaking current 8 AAC max. Min. breaking current 100mA AC/DC 5 Electrical life (number of operations) AC 12: 2000 VA - 10 AC 15: Cos = 0,3 - 6000 DC 13: L/R = 300 ms - 6000 Breaking capacity (resistive) 2000 VAAC Maximum rate 360 operations/hour at full load Operating categories acc. to IEC/EN 60947-5-1 AC12, AC15, DC13 6 Mechanical life (operations) 5 x 10 Insulation Insulation coordination (IEC/EN 60664-1) Overvoltage category III: degree of pollution 2 Rated impulse withstand voltage (IEC/EN 60664-1) 4 kV (1,2 / 50 s) Dielectric strength (IEC/EN 60664-1) 2.5 kV AC 50Hz 1 min. Insulation resistance (IEC/EN 60664-1) > 100 M/ 500 VDC General characteristics Display power supply Green LED Display relay Yellow LED Casing 22,5 mm Mounting On 35 mm symmetrical DIN rail, IEC/EN 60715 Mounting position All positions Material: enclosure plastic type VO to UL94 standard Protection (IEC/EN 60529) Terminal block: IP20 Casing: IP50 Weight 160 g 2 2 2 Connecting capacity IEC/EN 60947-1 Rigid: 1 x 4 - 2 x 2.5 mm 1 x 11 AWG - 2 x 14 AWG 2 2 2 Flexible with ferrules: 1 x 2.5 - 2 x 1.5 mm 1 x 14 AWG - 2 x 16 AWG Max. tightening torques IEC/EN 60947-1 0,6 mN / 5,3 Lbf.In Operating temperature IEC/EN 60068-2 -20+60 Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected02/11/2015 www.crouzet.com Storage temperature IEC/EN 60068-2 -30+70 Humidity IEC/EN 60068-2-30 93% RH max. without condensation Vibrations according to IEC/EN60068-2-6 1055Hz,A=0.35mm Standards Product standard IEC/EN 60255-1 Electromagnetic compatibility (EMC) IEC/EN 61000-6-1, IEC/EN 61000-6-2, IEC/EN 61000-6-3, IEC/EN 61000-6-4 Certifications UL, CSA Marking CE (DBT) 2006/95/EC - EMC 2004/108/EC Conformity with environmental directives RoHS Supply Supply voltage Un 24 VDC, 120 VAC, 230 VAC Polarity with DC voltage DC: yes Galvanic isolation of power supply/measurement DC: no galvanic isolation. In this case, the product power supply and measuring circuit power supply must be electrically isolated AC: galvanic isolation by transformer Power consumption at Un DC: 1 W AC: 3 VA Inputs and measuring circuit Measurement range 0,260V E1-M:0,22V E2-M:110V E3-M:660V Input resistance E1-M: 2k E2-M: 10k E3-M: 60k Permanent overload at 20C E1-M: 4 V E2-M: 20 V E3-M: 120 V o E1-M: 50 V Peak overload < 1ms at 20 C E2-M: 100 V E3-M: 300 V Principles When the value of the controlled voltage, AC or DC, reaches the treshold Ue displayed on the front face, the output relay changes state at the end of a time delay T1, which can be set on the front face at between 0.1 and 3s. Once the voltage drops below 5 to 50% of the treshold (hysteresis), the output relay changes state again instantly. Changing the hysteresis onthe front face does not therefore modify the value of the preset treshold. o Legend N Treshold Ue Hysteresis UPPER function UNDER function Unit power-up Controlled voltage Principles Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected