www.crouzet.com ETM / ETM2 / ETM22 motor thermal protection ETM2 Part number 84874024 Controls temperature of machines using built-in PTC probes Line break or probe short-circuit detection Fault latching function Pushbutton for local reset Remote reset via external contact Pushbutton test facility 2 LEDs to indicate relay and power supply status Output Supply voltage Type ETM 1 N/O contact 24 V ACDC 84 874 015 84 874 013 ETM 1 N/O contact 120 V AC 84 874 014 ETM 1 N/O contact 230 V AC 84 874 025 ETM2 1 changeover 24 V ACDC 84 874 023 ETM2 1 changeover 120 V AC 84 874 024 ETM2 1 changeover 230 V AC 84 874 035 ETM22 2 changeovers 24 V AC/DC 84 874 033 ETM22 2 changeovers 120 V AC ETM22 2 changeovers 230 V AC 84 874 034 Supply voltage Un Operating range 0.85 to 1.10 Un Nominal power 3 VA Maximal power 5 VA Immunity from micro power cuts 10 ms Delay on pick-up 500 ms Insulation coordination Category III, degree of pollution 2 conforming to IEC 664.1 / VDE 0110: 4 KV/2 Max. resistance of cold probes Trip threshold 3100 10% Reset threshold 1650 10% Short-circuit detection 0 - 10 Measurement voltage as per IEC 34-11 2,5V Repetition accuracy with constant parameters 0.5% o Temperature drift 0.05% / C Voltage-dependent drift -2% Output Breaking capacity 2000 VA / 80 W Max. breaking current 8 A AC Max. breaking voltage 440 V AC Min. breaking current 100 mA Maximum rate 360 operations / hour at full load 6 Mechanical life (operations) 5 x 10 5 Electrical life AC12: 2000 VA - 10 operations AC15: Cos = 0,3 - 6000 operations DC13: L/R = 300 ms - 6000 operations Reset time Response time 500ms Display on ETM2/ETM22 - power supply green LED Display on ETM2/ETM22 - Relay yellow LED Class of protection (529) - Term. block IP 20 Protection class (IEC 60529) - Casing IP 50 Housing material Self-extinguishing Weight (g) 145 2 Terminal capacity 2 x 1.5 mm with ferrule 2 2 x 2.5 mm without ferrule Temperature limit operation (IEC 68.1.14) (C) -20+60C Temperature limits stored (IEC 68.1.1/2) (C) -30+70C Relative humidity (no condensation) 95% (+2% -3%) Dimension Diagram : ETM / ETM2 / ETM22 06/04/2011www.crouzet.com : Reset WITHOUT fault latching (Y1 and Y2 not connected for ETM2/ETM22) Control relay is used in combination with PTC thermistor probes (not supplied) for thermal protection of machines (motors, alternators, transformers, etc). The probes are placed at critical points on the equipment to be protected (normally inserted into the stator windings of motors). The resistance of the PTC probe has a positive temperature coefficient. As soon as the nominal trip temperature of the probe is exceeded, the resistance of the probe increases rapidly. Protection relay detects this and opens the power supply circuit of the protected equipment (eg motor) and the yellow fault indicator LED lights up (version ETM2/ETM22). The ETM2/ETM22 has a TEST button which can be used to simulate a thermal overload in order to test the service condition of the relay. The relay drops out as soon as the protected equipment is subjected to a thermal overload, short-circuit or break in the probe measuring circuit. If the equipment being protected has another PTC proble with a lower nominal trip temperature, a second ETM/ETM2/ETM22 relay can be used to give early warning of tripping and thus prevent breaks in operation. Control relay ETM/ETM2/ETM22 is automatically reset as soon as the temperature drops below the trip threshod (the yellow fault indicator LED goes out). o Legend N 1 Unit power-up 2 Resistance between terminals T1 and T2 3 Output relay : Reset WITH fault latching (only for ETM2/ETM22) (Y1 and Y2 connected) The relay is reset either using the RESET pushbutton on the front face or by opening the external contact S2 (remote reset), or by cutting the auxiliary power supply (terminals A1 - A2). If the auxiliary power is cut for a period of time greater than the reset time (500 ms), the relay is reactivated if the proble detects a normal temperature when the power supply voltage is restored. o N Legend 1 Unit power-up 2 Latching contact 3 Resistance between terminals T1 and T2 4 Output relay : PTC probe specificationAccording to standard DIN 44081 (or IEC 34-11) 06/04/2011