02/11/2015 www.crouzet.comExpandabl range with display XD26 Part number 88970814
Green LCD with 4 lines of 18 characters and configurable backlighting
More cost effective solution
Industrial temperature range (-20C+55C)
Analogue inputs 0-10 VDC or 0-20mA/Pt100 with converters
Open to XN network communication extensions and digital I/O or analogue extensions
Part numbers
Inputs Outputs Supply
Type
88970814 XD26 16 digital (including 6 analogue) 10 solid state 0.5 A (including 4 PWM) 12 V DC
Specifications
General environment characteristics for CB, CD, XD, XB, XR and XE product types
Certifications CE, UL, CSA, GL
Conformity to standards (with the low voltage directive IEC/EN 61131-2 (Open equipment)
and EMC directive) IEC/EN 61131-2 (Zone B)
IEC/EN 61000-6-2,
IEC/EN 61000-6-3 (*)
IEC/EN 61000-6-4
(*) Except configuration (889701.1 or 889701.2) + (88970250 or 88970270) + 88970241 class A (class B in a metal enclosure)
Earthing None
Protection rating In accordance with IEC/EN 60529:
IP40 on front panel
IP20 on terminal block
Overvoltage category 3 in accordance with IEC/EN 60664-1
Pollution Degree: 2 in accordance with IEC/EN 61131-2
Max operating Altitude Operation: 2000 m
Transport: 3,048 m
Mechanical resistance Immunity to vibrations IEC/EN 60068-2-6, Fc test
Immunity to shock IEC/EN 60068-2-27, Fa test
Resistance to electrostatic discharge Immunity to ESD IEC/EN 61000-4-2, level 3
Resistance to HF interference Immunity to radiated electrostatic fields
IEC/EN 61000-4-3,
Immunity to fast transients (burst immunity)
IEC/EN 61000-4-4, level 3
Immunity to shock waves
IEC/EN 61000-4-5
Radio frequency in common mode
IEC/EN 61000-4-6, level 3
Voltage dips and breaks (AC)
IEC/EN 61000-4-11
Immunity to damped oscillatory waves
IEC/EN 61000-4-12
Conducted and radiated emissions Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1
(*) Except configuration (889701.1 or 889701.2) + (88970250 or 88970270) + 88970241 class A (class B in metallic cabinet)
Operating temperature -20+55C(+40Cinanon-ventilated enclosure) in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-2-2
Storage temperature -40+70CinaccordancewithIEC/EN60068-2-1 and IEC/EN 60068-2-2
Relative humidity 95% max. (no condensation or dripping water) in accordance with IEC/EN 60068-2-30
Mounting On symmetrical DIN profile, 35 x 7.5 mm and 35 mm x 15 or panel (2 x 4 mm )
Screw terminals connection capacity Flexible wire with ferrule =
2
1 conductor: 0.25 to 2.5 mm (AWG 24...AWG 14)
2
2 conductors 0.25 to 0.75 mm (AWG 24...AWG 18)
Semi-rigid wire =
2
1 conductor: 0.2 to 2.5 mm (AWG 25...AWG 14)
Rigid wire =
2
1 conductor: 0.2 to 2.5 mm (AWG 25...AWG 14)
2
2 conductors 0.2 to 1.5 mm (AWG 25...AWG 16)
Tightening torque =
0.5 N.m (4.5 lb-in) (tighten using screwdriver diam. 3.5 mm)
Processing characteristics of CB, CD, XD & XB product
types
LCD display CD, XD: Display with 4 lines of 18 characters
Programming method Function blocks / SCF (Grafcet) or Ladder
Program size For CB, CD:
4 Ko: 64 macros max.
256 blocks max. per macro
180 typical blocks
For XB, XD:
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected02/11/2015 www.crouzet.com
8 Ko: 64 macro max.
256 blocks max. per macro
350 typical blocks
Or for CB, CD, XB, XD: 120 lines in Ladder
Program memory Flash EEPROM
Removable memory EEPROM
Data memory 368 bit/200 words
Back-up time in the event of power failure Program and settings in the controller: 10 years
Program and settings in the plug-in memory: 10 years
Data memory: 10 years
Cycle time Functionblocks:690ms(typically20ms)
Ladder: typically 20 ms
Response time Input acquisition time: 1 to 2 cycle times
Clock data retention 10 years (lithium battery) at 25C
Clock drift Drift < 12 min/year (at 25C)
6 s/month (at 25C with user-definable correction of drift)
Timer block accuracy 1% 2 cycle times
Start up time on power up < 1,2 s
Characteristics of products with AC power supplied
Supply 24 V AC 100240VAC
(88970..4) (88970..3)
Nominal voltage 24 V AC 100240VAC
Operating limits -15% / +20% -15% / +10%
or20.4VAC28.8VAC or85VAC264VAC
Supply frequency range 50/60Hz (+4% / -6%)
50/60Hz (+4% / -6%)or4753Hz/57<63Hz
or4753Hz/57<63Hz
Immunity from micro power cuts 10 ms (repetition 20 times) 10 ms (repetition 20 times)
Max. absorbed power CB12-CD12-XD10-XB10: 4 VA CB12-CD12-XD10-XB10: 7 VA
CB20-CD20: 6 VA CB20-CD20: 11 VA
XD10-XB10 with extension: 7,5 VA XD10-XB10 with extension: 12 VA
XD26-XB26: 7.5 VA XD26-XB26: 12 VA
XD26-XB26 with extension: 10 VA XD26-XB26 with extension: 17 VA
Isolation voltage 1780 V AC 1780 V AC
Inputs 24 V AC 100240VAC
(88970..4) (88970..3)
Input voltage 24 V AC (-15% / +20%) 100240VAC(-15% / +10%)
Input current 4,4mA @ 20,4 V AC
0,24mA @ 85 V AC
5,2mA @ 24,0 V AC
0,75mA @ 264 V AC
6,3mA @ 28,8 V AC
Input impedance 4.6 k 350 k
Logic 1 voltage threshold 14VAC 79VAC
Making current at logic state 1 >2mA >0.17mA
Logic 0 voltage threshold 5VAC 20VAC(28VAC:XE10,XR06,XR10,XR14)
Release current at logic state 0 <0.5mA <0.5mA
Response time with LADDER programming 50 ms 50 ms
State01(50/60Hz) State 0 < 1 (50/60Hz)
Response time with function blocks programming Configurable in increments of 10 ms Configurable in increments of 10 ms
50 ms min. up to 255 ms 50 ms min. up to 255 ms
State01(50/60Hz) State01(50/60Hz)
Maximum counting frequency In accordance with cycle time (Tc) and input response time (Tr) : In accordance with cycle time (Tc) and input response time (Tr) :
1/ ( (2 x Tc) + Tr) 1/ ( (2 x Tc) + Tr)
Sensor type Contact or 3-wire PNP Contact or 3-wire PNP
Input type Resistive Resistive
Isolation between power supply and inputs None None
Isolation between inputs None None
Protection against polarity inversions Yes Yes
Status indicator On LCD screen for CD and XD On LCD screen for CD and XD
Characteristics of relay outputs common to the entire range
Max. breaking voltage 530VDC
24250VAC
Breaking current CB-CD-XB10-XD10-XR06-XR10: 8 A
XD26-XB26: 8 x 8 A relays, 2 x 5 A relays
XE10: 4 x 5 A relays
XR14: 4 x 8 A relays, 2 x 5 A relays
Electrical durability for 500000 operating cycles Usage category DC-12: 24 V, 1.5 A
Usage category DC-13: 24 V (L/R = 10 ms), 0.6 A
Usage category AC-12: 230 V, 1.5 A
Usage category AC-15: 230 V, 0.9 A
Max. Output Common Current 12A for O8,O9,OA
Minimum switching capacity 10mA (at minimum voltage of 12 V)
Minimum load 12 V, 10mA
Maximum rate Off load: 10Hz
At operating current: 0.1Hz
Mechanical life 10,000,000 operations (cycles)
Voltage for withstanding shocks In accordance with IEC/EN 60947-1 and IEC/EN 60664-1: 4 kV
Off-cycle response time Make 10 ms
Release 5 ms
Built-in protections Against short-circuits: None
Against overvoltages and overloads: None
Status indicator On LCD screen for CD and XD
Characteristics of product with DC power supplied
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected