02/11/2015 www.crouzet.com
SmartCompac range with display CD12 Smart Part number 88974046
Highly visible blue LCD with 4 lines of 18 characters and configurable backlighting
Allow the use of the entire library of specific functions blocs of the software workshop
Extended temperature range (-20C+70C)
Analogue inputs 0-10 VDC, Potentiometer, NTC, LDR (0-20mA/Pt100 with converters)
Selective parameter setting: you can choose the parameters that can be adjusted on the front panel
Part numbers
Type Inputs Outputs Supply
88974046 CD12 Smart 8 digital (including 4 analogue) 4 solid state 0.5 A (including 1 PWM) 12 V DC
Specifications
General environment characteristics for CB, CD, XD, XB, XR and XE product types
Certifications CE, UL, CSA, GL
Conformity to standards (with the low voltage directive IEC/EN 61131-2 (Open equipment)
and EMC directive) IEC/EN 61131-2 (Zone B)
IEC/EN 61000-6-2,
IEC/EN 61000-6-3 (*)
IEC/EN 61000-6-4
(*) Except configuration (889701.1 or 889701.2) + (88970250 or 88970270) + 88970241 class A (class B in a metal enclosure)
Earthing Not included
Protection rating In accordance with IEC/EN 60529:
IP40 on front panel
IP20 on terminal block
Overvoltage category 3 in accordance with IEC/EN 60664-1
Pollution Degree: 2 in accordance with IEC/EN 61131-2
Max operating Altitude Operation: 2000 m
Transport: 3048 m
Mechanical resistance Immunity to vibrations IEC/EN 60068-2-6, test Fc
Immunity to shock IEC/EN 60068-2-27, test Ea
Resistance to electrostatic discharge Immunity to ESD
IEC/EN 61000-4-2, level 3
Resistance to HF interference Immunity to radiated electrostatic fields
IEC/EN 61000-4-3
Immunity to fast transients (burst immunity)
IEC/EN 61000-4-4, level 3
Immunity to shock waves
IEC/EN 61000-4-5
Radio frequency in common mode
IEC/EN 61000-4-6, level 3
Voltage dips and breaks (AC)
IEC/EN 61000-4-11
Immunity to damped oscillatory waves
IEC/EN 61000-4-12
Conducted and radiated emissions Class B (*) in accordance with EN 55022, EN 55011 (CISPR22, CISPR11) group 1
(*) Except configuration (889701.1 or 889701.2) +
(88970250 or 88970270) + 88970241 class A (class B in a metal enclosure)
Operating temperature -20+70C
except CB and XB versions in VDC: -30+70C(+40Cinanon-ventilated enclosure)
in accordance with IEC/EN 60068-2-1 and IEC/EN 60068-22
Storage temperature -40+80CinaccordancewithIEC/EN60068-2-1 and
IEC/EN 60068-2-2
Relative humidity 95% max. (no condensation or dripping water) in accordance with
IEC/EN 60068-2-30
Mounting On symmetrical DIN rail, 35 x 7.5 mm and 35 x 15 mm, or on panel (2 x 4 mm)
Screw terminals connection capacity Flexible wire with ferrule =
2
1 conductor: 0.25 to 2.5 mm (AWG 24...AWG 14)
2
2 conductors 0.25 to 0.75 mm (AWG 24...AWG 18)
Semi-rigid wire =
2
1 conductor: 0.2 to 2.5 mm (AWG 25...AWG 14)
Rigid wire =
2
1 conductor: 0.2 to 2.5 mm (AWG 25...AWG 14)
2
2 conductors 0.2 to 1.5 mm (AWG 25...AWG 16)
Tightening torque =
0.5 N.m (4.5 lb-in) (tighten using screwdriver diam. 3.5 mm)
Also valid for spring cage connectors (ref 88970313 and 88970317 for the RBT range)
General characteristics
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected02/11/2015 www.crouzet.com
Operating temperature -20+70C
Operating factor 100% (6 A relays)
66% (8 A relays)
Storage temperature -40+80C
LCD display Display with 4 lines of 18 characters, white characters on a blue background
Processing characteristics of CB, CD, XD & XB product types
LCD display CD, XD: Display with 4 lines of 18 characters
Programming method Function blocks / SCF (Grafcet) or Ladder
Program size 8 Kb: 350 typical blocks, 64 macros maximum, 256 blocks maximum per macro
or
120 lines in Ladder
Program memory Flash EEPROM
Removable memory EEPROM
Data memory 368 bit/200 words
Back-up time in the event of power failure Program and settings in the controller: 10 years
Program and settings in the plug-in memory: 10 years
Data memory: 10 years
Cycle time FBD:690ms(typically20ms)
Ladder: typically 20 ms
Response time Input acquisition time: 1 to 2 cycle times
Clock data retention 10 years (lithium battery) at 25C
Clock drift Drift < 12 min/year (at 25C)
6 s/month (at 25C with user-definable correction of drift)
Timer block accuracy 1% 2 cycle times
Start up time on power up < 1,2 s
Characteristics of products with AC power supplied
Supply
Nominal voltage 24 V AC 100240VAC
Operating limits -15% / +20% -15% / +10%
or20.4VAC28.8VAC or85VAC264VAC
Supply frequency range 50/60Hz (+4% / -6%)
50/60Hz (+ 4% / -6%)or4753Hz/5763Hz
or4753Hz/5763Hz
Immunity from micro power cuts 10 ms (repetition 20 times) 10 ms (repetition 20 times)
Max. absorbed power CB12-CD12-XD10-XB10: 4 VA CB12-CD12-XD10-XB10: 7 VA
CB20-CD20: 6 VA CB20-CD20: 11 VA
XD10-XB10 with extension: 7.5 VA XD10-XB10 with extension: 12 VA
XD26-XB26: 7.5 VA XD26-XB26: 12 VA
XD26-XB26 with extension: 10 VA XD26-XB26 with extension: 17 VA
Isolation voltage 1780 V AC 1780 V AC
Inputs
Input voltage 24 V AC (-15% / +20%) 100240VAC(-15% / +10%)
Input current 4.4mA @ 20.4 V AC
0.24mA @ 85 V AC
5.2mA @ 24.0 V AC
0.75mA @ 264 V AC
6.3mA @ 28.8 V AC
Input impedance 4.6 k 350 k
Logic 1 voltage threshold 14VAC 79VAC
Making current at logic state 1 > 2mA > 0.17mA
Logic 0 voltage threshold 5VAC 20VAC(28VAC:XE10,XR06,XR10,XR14)
Release current at logic state 0 < 0.5mA < 0.5mA
Response time with LADDER programming 50 ms 50 ms
State01(50/60Hz) State01(50/60Hz)
Response time with function blocks programming Configurable in increments of 10 ms Configurable in increments of 10 ms
50 ms min. up to 255 ms 50 ms min. up to 255 ms
State01(50/60Hz) State01(50/60Hz)
Maximum counting frequency In accordance with cycle time (Tc) and input response time (Tr) : In accordance with cycle time (Tc) and input response time (Tr) :
1/ ( (2 x Tc) + Tr) 1/ ( (2 x Tc) + Tr)
Sensor type Contact or 3-wire PNP Contact or 3-wire PNP
Input type Resistive Resistive
Isolation between power supply and inputs None None
Isolation between inputs None None
Protection against polarity inversions Yes Yes
Status indicator On LCD screen for CD and XD On LCD screen for CD and XD
Characteristics of relay outputs common to the entire range
Max. breaking voltage 530VDC
24250VAC
Breaking current CB-CD-XD10-XB10-XR06-XR10: 8 A
XD26-XB26: 8 x 8 A relays, 2 x 5 A relays
XE10: 4 x 5 A relays
XR14: 4 x 8 A relays, 2 x 5 A relays
RBT (Removable Terminal Blocks) versions: verify the maximum current according to the type of connection used
Electrical durability for 500000 operating cycles Utilization category DC-12: 24 V, 1.5 A
Utilization category DC-13: 24 V (L/R = 10 ms), 0.6 A
Utilization category AC-12: 230 V, 1.5 A
Utilization category AC-15: 230 V, 0.9 A
Max. Output Common Current 12 A for O8, O9, OA
Minimum switching capacity 10mA (at minimum voltage of 12 V)
Minimum load 12 V, 10mA
Maximum rate Off load: 10Hz
At operating current: 0.1Hz
Mechanical life 10,000,000 (operations)
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected