09/2019 Modular Power Supply MPS24 Compact 24 Vc Power Supplies range from 10 to 100 W High Efficiency, up to 90% 230 V a DIN Rail Mount and Low No-Load Power Consumption UL1310 Class 2 & CE Compliant Ideally suited for use with all Crouzet 24 Vc products 24 Vc 10 W 24 Vc 30 W 24 Vc 60 W 24 Vc 100 W Selection Guide Nominal Output Voltage Maximum Output Power Maximum Output Current Part Number 24 Vc 10 W 0.42 A 89 451 001 30 W 1.25 A 24 Vc 89 451 003 24 Vc 60 W 2.5 A 89 451 006 100 W 4.2 A 24 Vc 89 451 010 24 Vc 10 W 24 Vc 30 W 24 Vc 60 W 24 Vc 100 W General Characteristics Part Number 89 451 001 89 451 003 89 451 006 89 451 010 Product Certification CE, UL, CSA, NEC Class 2 CE, UL, CSA Safety Standards Conformity EN60950-1 EN60950-1 UL60950-1, UL508, UL1310 class2 (NEC Class2) UL60950-1, UL508 CSA22.2 No.60950-1-07 (2nd edition) CSA22.2 No.60950-1- 07 (2nd edition) EMC Standards Conformity IEC/EN 61000-6-2 (Industrial) IEC/EN 61000-6-3 (Residential, commercial and light-industrial environments) IEC/EN 61204-3 SEMI F47 (Voltage sag immunity) Line Dip (200~240 Va) Protection against Radio Interference CE: EN55022-B, CISPR22-B RE: EN55022-A, CISPR22-A Emission Harmonic current: CEI/EN 61000-3-2 Power Factor & Harmonic Correction Compliant to IEC 61000-3-2,Class A (PFHC) Power Supply Earthing None Isolation Class / Class of Protection Class II (L, N only) Pollution Degree 2, material group 3 Operating Altitude 3000 m, derating 5 C/1000 m above 2000 m You have a project Contact us on www.crouzet.com Description: Crouzet compact range of DIN Rail power supplies, from 10 to 100W at 24 Vc. With increased performance in a reduced size, they are designed for a wide range of industrial and building applications. Characterised by their wide voltage input ranges (84 to 264 Va), they allow the supply of single-phase mains electric power to DC power lines. In addition, the new terminal position, as well as double insulation and a Class II safety input, simplifies wiring and earthing is no longer necessary . In the same way, the NEC Class 2 standard, in accordance with UL1310, allows operation in cases where output currents must be limited under fault conditions. With a high efficiency of up to 90% 230V and a low of f-load power consumption, these new power supplies will fully satisfy the needs of 24 Vc applications. For more information about Crouzets Modular Power Supply range, please visit www.crouzet.com. W W W.CROUZET.COM 2 Modular Power Supply 09/2019 24 Vc 10 W 24 Vc 30 W 24 Vc 60 W 24 Vc 100 W Vibration Operating, IEC 60068-2-6, Sine Wave, 10-500Hz, 19.6 m/s (2G peak) 10 min per cycle, 60 min for all X,Y,Z directions Shock (In package) Operating, IEC 60068-2-27, Half Sine Wave, 39.2 m/s (4G) for a duration of 22 ms, 3 shocks for each 3 directions, 9 times in total Immunity EN 61000-4-2 (Level 3) EN 61000-4-3 (Level 3) EN 61000-4-4 (Level 4) EN 61000-4-5 (Level 3) EN 61000-4-6 (Level 3) EN 61000-4-8 (Level 4) EN 61000-4-11 (Class 3) Operating Temperature -20 +71 C (see derating curve) Operating Humidity 20 90 % max. (No condensing) Storage Temperature -40 C +85 C Storage Humidity 5 95 % max. (No condensing) Cooling Convection Screw Terminals Connection Capacity AWG 12-26 Case Colour Grey RAL 7035 Protection Degree IP20 Weight 65 g 120 g 200 g 280 g Dimensions (mm) 18 x 91 x 55.6 mm 36 x 91 x 55.6 mm 54 x 91 x 55.6 mm 72 x 91 x 55.6 mm Electrical Characteristics Input Voltage 100 Va 240 Va Frequency 50/60 Hz (+4 % / -6 %) from 47 to 53 Hz / 57 to 63 Hz Nominal Output Voltage 24 Vc Line Regulation 1 % max Load Regulation 1 % max Output Voltage Range N.A 24 28 Vc Input Current 0.18 A / 0.12 A (Typ)* 0.6 A / 0.4 A (Typ)* 1.2 A / 0.8 A (Typ)* 2 A / 1.1 A (Typ)* (115/230 Va) (115/230 Va) (115/230 Va) (115/230 Va) Maximum Output Current 0.42 A 1.25 A 2.5 A 4.2 A Maximum Output Power 10.08 W 30 W 60 W 100.8 W Inrush Current 40 A cold start (Typ) 50 A cold start (Typ) 60 A cold start (Typ) (115/230 Va) (115/230 Va) (115/230 Va) Ripple and Noise 1 % max * Temperature Coefficient < 0.02 %/C No Load Input Power < 0.3 W < 0.5 W Efficiency 87 % (115/230 Va) 88/90 % (115/230 Va) 89/90 % (115/230 Va) 88/90 % (115/230 Va) (Typ)* (Typ)* (Typ)* (Typ)* Power Factor 0.56/0.42 (Typ) 0.58/0.45 (Typ) 0.5/0.43 (Typ) 0.5/0.47 (Typ) (115/230 Va)* (115/230 Va)* (115/230 Va)* (115/230 Va)* Hold-Up Time 20 ms 115 Va (Typ)* 15 ms 115 Va (Typ)* Over-Voltage Protection 29.0 35.0 V Over-Current Protection > 105 %Hiccu with automatic recovery Upstream Protection of Power Supply SeeInstruction Manual: IS 19004 VO Withstand Voltage 3 kVAC (20 mA) Isolation Resistance > 100 M (500 Vc) 25 C, 70 % RH Status Indication DC OK LED (green) Series Operation Possible, seeInstruction Manual: IS 19004 VO Transient Response Deviation <1.2 V (25~75 % load change) Transient Response Recovery Time 1 ms, to within 2 % of settled value, 25~75 % load change * at Maximum Output Power, Ta = 25 C