TIMERS TIMERS GENERAL DETAILS OF TYPE S TIMERS S series are compact, low cost, precision devices designed to the most demanding specifications. The small size, epoxy filled case is highly resistant against dust, vibrations, shock or humidity. Creep and strike distance according to VDE 0110 Group C 250V. Case protection IP66. Case material - Polymid. 1.96 (50) 0.47 (12) 2.46 0.8 (62.5) 0.77 (45) 0.16 0.69 6.35 (42) (17.5) 2.76 2.36 (70) (60) 2 Function A: Delay on Make SAS SERIES Input Power S1 DELAY ON MAKE Output TIMER WITH SOLID 0 T STATE OUTPUT UL listed CSA recognized SPECIFICATIONS: Function A: When input power is applied, timing (t) begins. At the end of the preselected time, the solid state SCR output turns on. The out- Input Power 24 VAC/DC, 110 VAC/DC put turns off when the input power is removed, resetting the timer for 220 VAC/DC, 15%, 50/60 Hz the next cycle. Output Rating max.: 1.0 A at 20C min.: 10 mA Repetition accuracy . 0.5% at a constant ambient Temp rise derating 5 mA / C WIRING DIAGRAM: Reset time SAS-L & SAS-DL . 25 ms after timing 100 ms during timing SAS SAS-D SAS-P + SAS-PL . 100 ms during timing - Leakage current during timing . 5 mA max Peak surge current 20 A < 10 ms S1 S1 S1 Peak surge voltage 1400 V, 10 s Terminals 1/4 (6.35mm) quick connect 470K Opertating temperature . -22F to +140F (-30C to +60C) POTENTIOMETER Weight 1.9 oz. (55g) Peak Surge Current A1 A2 A1 A2Z1 Z2 A1 A2 100A 50A 20A Peak Surge Current vs Surge Current Duration 15A 10A 5A LOAD LOAD LOAD 2A 1A + 10ms 20ms 50ms 100ms 200ms 500ms 1s 2s 5s - Surge Current Duration ORDERING INFORMATION: (100 pcs. minimum order) S AS-D 100S 220 AD L MOUNTING SERIES TIME RANGE INPUT POWER UL S=Encapsulated requiring AS = standard relay = Fixed .1 sec - 1 min AS 24AD = 24 VAC/DC 1 AMP DIN-Rail, Panel Adapter AS-D = remote potentiometer = .1 sec - 60 min AS-D 110AD = 110 VAC/DC or use Base Mounting AS-P = internal potentiometer Ex = 10-100 sec maintain 10:1 ratio 220AD = 220 VAC/DC Holes = .1 sec - 10 sec AS-P 1-100 sec maintain 100:1 ratio Products and specifications subject to change without notice. Order/Technical Support Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com 2/43TIMERS TIMERS SDS SERIES REPEAT CYCLE TIMER UL listed CSA recognized Shock Resistant SCR Solid State Output Optional Remote Potentiometer DIN-Rail or Base Mounting When input power S1 is applied, the solid state output turns on Recycling immediately for the timer period specified. It then turns OFF for that same time period and repeats continuously while power is applied. Input Power S1 Output t TT 0 SPECIFICATIONS: WIRING DIAGRAM: Input 24 VAC, 48 VAC, 110 VAC 220 VAC, 15%, 50/60 Hz SDS SDSD SDSP Maximum power consumption 24 VAC: 0.2 VA 48 VAC: 0.3 VA S1 S1 S1 110 VAC: 0.6 VA 470 K 220 VAC: 1.2 VA Output . SCR POTENTIOMETER Output Rating . max.: 1.0 A at 20C min.: 10 mA Repetition accuracy 0.5% at a constant ambient A2 18 A1 A2 18 A1 Z1 Z2 A2 18 A1 Temp. rise derating . 5 mA / C Reset time 100 ms after timing 150 ms during timing Leakage current during timing 2 mA max. Peak surge current . 20 A < 10ms LOAD LOAD LOAD Peak surge voltage . 1400 V, 100 s Terminals . Faston 1/4 (6.35mm) Operating temperature -22F to +140F -30C to +60C Weight . 1.9 oz. (55g) DIMENSIONS See page 3-34 ORDERING INFORMATION: (100 pcs. minimum order) P.S.: Specify maximum time for D and P versions. 10 min S DS 24 L TIME RANGE MOUNTING SERIES INPUT POWER UL S = Encapsulated, requiring 1 AMP DS = Fixed time DS = Fixed .1s. - 120 min 24A = 24 VAC DIN-Rail, Panel Adapter or DS-D = remote potentiometer DS-D = .1 sec. - 120 min. use Base Mounting Holes 48A= 48 VAC DS-P = internal potentiometer Maintain 10:1 ratio 110A = 110 VAC DS-P = 1 -10 sec. or min., 10 - 100 sec. or min. 220A = 220 VAC Maintain 100:1 ratio Products and specifications subject to change without notice. Order/Technical Support Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com 2/44