Additional Resources: Product Page 3D Model date 04/27/2021 page 1 of 6 SERIES: PDRC-10 DESCRIPTION: AC-DC DIN RAIL POWER SUPPLY FEATURES low profile for building automation universal input (90~264 Vac) integrated fuse and surge protection 3,000 Vac input/output isolation voltage DC On/Low LED indicators over-voltage/current protection UL/cUL, TUV, CE certified 2 output output output ripple efficiency MODEL 1 voltage current power and noise max max max typ (Vdc) (A) (W) (mVp-p) (%) PDRC-10-5 5 1.5 7.5 50 75 PDRC-10-12 12 0.83 10 50 79 PDRC-10-15 15 0.67 10 50 80 PDRC-10-24 24 0.42 10 50 80 Notes: 1. At full load, nominal input, 20 MHz bandwidth oscilloscope. 2. At nominal input. 3. All specifications are measured at Ta=25C, nominal input voltage, and rated output load unless otherwise specified. PART NUMBER KEY PDRC-10 - XX Base Number Output Voltage cui.comAdditional Resources: Product Page 3D Model CUI Inc SERIES: PDRC-10 DESCRIPTION: AC-DC DIN RAIL POWER SUPPLY date 04/27/2021 page 2 of 6 INPUT parameter conditions/description min typ max units 90 264 Vac voltage 120 375 Vdc frequency 47 63 Hz current at 90 Vac, full load 300 mA at 115 Vac, full load 16 A inrush current at 230 Vac, full load 32 A leakage current input to output 0.25 mA OUTPUT parameter conditions/description min typ max units 5 Vdc output model 3,500 F 12 Vdc output model 1,800 F capacitive load 15 Vdc output model 1,500 F 24 Vdc output model 560 F initial set point accuracy 1 % line regulation at full load, V in min to V in max 1 % load regulation at Vi nom, 0~100% load 1 % at Vi nom, full load 1.0 s start-up time at Vi nom, full load with max capacitive load 1.5 s at Vi nom, full load 150 ms rise time at Vi nom, full load with max capacitive load 500 ms at 115 Vac, full load 10 ms hold-up time at 230 Vac, full load 30 ms fall time at Vi nom, full load 150 ms transient recovery time at Vi nom, 100~50% load 2 ms switching frequency at Vi nom, full load 132 kHz temperature coefficient 0.03 %/C at Vi nom, full load, for 1 second 5 Vdc output model 7.5 Vdc power back immunity 12 Vdc output model 18 Vdc 15 Vdc output model 22 Vdc 24 Vdc output model 35 Vdc 5 Vdc output model 3.5 4.5 Vdc DC ON indicator threshold at 12 Vdc output model 9.0 10.8 Vdc start-up (GREEN) 15 Vdc output model 11.0 13.5 Vdc 24 Vdc output model 19.2 21.6 Vdc 5 Vdc output model 3.5 4.5 Vdc DC LOW indicator threshold 12 Vdc output model 9.0 10.8 Vdc after start-up (RED) 15 Vdc output model 11.0 13.5 Vdc 24 Vdc output model 19.2 21.6 Vdc PROTECTIONS parameter conditions/description min typ max units at Vi nom, full load, auto recovery 5 Vdc output model 5.75 6.5 Vdc over voltage protection 12 Vdc output model 15 16.5 Vdc 15 Vdc output model 18 20 Vdc 24 Vdc output model 30 33 Vdc over current protection hiccup, auto recovery (see curve) 125 185 % short circuit protection hiccup, auto recovery cui.com