Additional Resources: Product Page 3D Model date 04/27/2021 page 1 of 6 SERIES: PDRC-36 DESCRIPTION: AC-DC DIN RAIL POWER SUPPLY FEATURES low profile for building automation universal input (90~264 Vac) integrated fuse and surge protection 3,000 Vac input/output isolation voltage DC On/Low LED indicators over-voltage/current protection UL/cUL, TUV, CE certified 2 output output output ripple efficiency MODEL 1 voltage current power and noise max max max typ (Vdc) (A) (W) (mVp-p) (%) PDRC-36-5 5 4.5 22.5 50 75 PDRC-36-12 12 2.75 33 50 83 PDRC-36-15 15 2.4 36 50 84 PDRC-36-24 24 1.5 36 50 84 Notes: 1. At full load, nominal input, 20 MHz bandwidth oscilloscope. 2. At nominal input. 3. All specifications are measured at Ta=25C, nominal input voltage, and rated output load unless otherwise specified. PART NUMBER KEY PDRC-36 - XX Base Number Output Voltage cui.comAdditional Resources: Product Page 3D Model CUI Inc SERIES: PDRC-36 DESCRIPTION: AC-DC DIN RAIL POWER SUPPLY date 04/27/2021 page 2 of 6 INPUT parameter conditions/description min typ max units 90 264 Vac voltage 120 375 Vdc frequency 47 63 Hz at 90 Vac, full load current 5 Vdc output model 600 mA 12, 15, 24 Vdc output models 900 mA at 115 Vac, full load 25 A inrush current at 230 Vac, full load 50 A leakage current input to output 0.25 mA OUTPUT parameter conditions/description min typ max units capacitive load at Vi nom, full load 3,500 F initial set point accuracy 1 % line regulation at full load, V in min to V in max 1 % load regulation at Vi nom, 0~100% load 1 % via built in trim pot, 0.8 A load 5 Vdc output model 5 5.5 Vdc adjustability 12 Vdc output model 12 14 Vdc 15 Vdc output model 13.5 16.5 Vdc 24 Vdc output model 24 28 Vdc 5 Vdc output model (5.5 Vdc) 4.0 A rated continuous loading at 12 Vdc output model (14.0 Vdc) 2.3 A max trim voltage 15 Vdc output model (16.5 Vdc) 2.1 A 24 Vdc output model (28.0 Vdc) 1.25 A at Vi nom, full load 1.0 s start-up time at Vi nom, full load with max capacitive load 1.5 s at Vi nom, full load 150 ms rise time at Vi nom, full load with max capacitive load 500 ms at 115 Vac, full load 20 ms hold-up time at 230 Vac, full load 100 ms fall time at Vi nom, full load 150 ms transient recovery time at Vi nom, 100~50% load 2 ms switching frequency at Vi nom, full load 45 65 kHz temperature coefficient 0.03 %/C at Vi nom, full load, for 1 second 5 Vdc output model 7.5 Vdc power back immunity 12 Vdc output model 18 Vdc 15 Vdc output model 22 Vdc 24 Vdc output model 35 Vdc 5 Vdc output model 3.5 4.5 Vdc DC ON indicator threshold at 12 Vdc output model 9.0 10.8 Vdc start-up (GREEN) 15 Vdc output model 11.0 13.5 Vdc 24 Vdc output model 19.2 21.6 Vdc 5 Vdc output model 3.5 4.5 Vdc DC LOW indicator threshold 12 Vdc output model 9.0 10.8 Vdc after start-up (RED) 15 Vdc output model 11.0 13.5 Vdc 24 Vdc output model 19.2 21.6 Vdc cui.com