date 07/22/2015
page 1 of 19
SERIES: PSE-3000 DESCRIPTION: AC-DC HOT-SWAP POWER SUPPLY
FEATURES
redundant (N+1) operation
up to 3000 W continuous power
blind mate connections for hot-swap
80 PLUS Platinum Efficiency
constant power (CP) mode
PoE output isolation; (1500 Vrms to ground)
3
harmonic correction to EN61000-3-2, Class A
high power density - 33.48 W/in
TM
DROOP current sharing
PMBus communication for monitoring &
single I/O connector for AC input, DC output
control
& signals
dual fan forced cooling with speed control
remote on/off control
front to back (-F) and back to front (-B)
power good signal
airflow versions
optional 19 four slot power shelf
power factor correction
3.3 Vdc (2A) standby voltage
C US
4
output output output ripple efficiency
MODEL
2,3 1
voltage current power and noise
max max max typ
(Vdc) (A) (W) (mVp-p) (%)
PSE-3000-48-F 48 62.5 3000 480 94
PSE-3000-48-B 48 62.5 3000 480 94
PSE-3000-54-F 54 55.5 3000 540 94
PSE-3000-54-B 54 55.5 3000 540 94
Notes: 1. Measured at 20 MHz bandwidth at an oscilloscope jack on the output with 0.1 F ceramic and 10 F aluminum electrolyitc capacitors.
2. At 90~180 Vac input, maximum of 1500 W.
3. At 180~264 Vac input, maximum of 3000 W.
4. At 230 Vac input, 3000 W. Meets 80 PLUS platinum efficiency requirements.
5. All specifications measured at: Ta=25C and 220 Vac input voltage unless otherwise specified.
PART NUMBER KEY
PSE-3000 - XX - X - CXX
Base Number
Reserved for Custom
Configurations
Output Voltage
Airflow Direction:
F = AC input connector to DC output connector
B = DC output connector to AC input connector
cui.com
m
h
e
R
r
i
V
c
a
U
,
T
I
n
c
.For more information, please visit the product page.
CUI Inc SERIES: PSE-3000 DESCRIPTION: AC-DC HOT-SWAP POWER SUPPLY date 07/22/2015 page 2 of 19
INPUT
parameter conditions/description min typ max units
voltage 90 264 Vac
frequency 47 63 Hz
at 90 Vac, 1500 W 20.2 Arms
current
at 180 Vac, full load 18.5 Arms
at 115 Vac, cold start 20 A
inrush current
at 230 Vac, cold start 40 A
leakage current 1.5 mArms
power factor correction at 230 Vac, full load 0.99
( )
OUTPUT - V1 MAIN OUTPUT
parameter conditions/description min typ max units
line regulation 3 %
load regulation 3 %
load capacitance 30,000 F
50% step load, 1A/s slew rate, recovery to 1%
transient response 3 %
within 1 ms
start-up time 5 s
hold-up time at 230 Vac, full load 12 ms
remote sense between both output terminals 0.5 V
current share accuracy (Droop) over 25% to 100% load 10 %
AC OK: green to indicate AC above the lower
limit that is required to sustain normal operation
LED indicator
DC OK: green to indicate module in normal
operating condition
( )
OUTPUT - V2 STANDBY OUTPUT
parameter conditions/description min typ max units
output voltage 3.3 Vdc
output current 0 2 A
1
ripple and noise 33 mVp-p
line regulation 5 %
load regulation 5 %
load capacitance 1000 F
50% step load, 1A/s slew rate, recovery to 1%
transient response 3 %
within 1 ms
start-up time 5 s
Notes: 1. Measured at 20 MHz bandwidth at an oscilloscope jack on the output with 0.1 F ceramic and 10 F aluminum electrolyitc capacitors.
PROTECTIONS
parameter conditions/description min typ max units
V1: latch off 60 Vdc
over voltage protection
V2: latch off 110 120 %
V1: constant current inception 62.5 A
over current protection
V2: hiccup 2.6 A
over temperature protection at full load, auto recovery 55 C
cui.com