Motor Protection Control 2-6500-... Description Bimetal operated single pole motor protection control with automatic reset actuation, small physical size, reliable snap-action mechanism. Caution: In specifying this product, care should be taken to ensure that automatic motor re-start does not represent a safety hazard. Typical applications Motors, transformers, extra low voltage wiring. 1 Ordering information 2-6500-... Type No. 2-6500 surface type with flange Terminal design Technical data P10 blade terminals 6.3-0.8 (QC .250) Shunt terminal (optional) Voltage rating AC 250 V (50/60 Hz) DC 28 V A3 blade terminals or solder terminals max. load 5 A Current ratings 0.1...10 A (up to 15 A upon request) Current ratings 0.1...10 A Typical life 100,000 operations at 2 x I N Protection is ensured for 18 days of 2-6500 - P10 - ... - 6 A ordering example continuous locked rotor condition with I 6 x I , max. 30 A k N Please be informed that we have minimum ordering quantities to be observed. (unsupervised duty) Ambient temperature -10...+60 C (-10...+140 F) Insulation co-ordination rated impulse pollution Standard current ratings and typical internal resistance values (IEC 60664 and 60664 A) withstand voltage degree 2.5 kV 3 Current Internal Current Internal Dielectric strength rating (A) resistance () rating (A) resistance () (IEC 60664 and 60664A) test voltage AC 2,000 V Insulation resistance > 100 M (DC 500 V) 0.1 140 2 0.47 Interrupting capacity 8 x I (co-co-co) N 0.2 47.5 2.5 0.33 Reset time at 23 C 30 sec 0.3 20.5 3 0.212 70 sec 0.4 11.4 3.5 0.155 Degree of protection housing IP30 (IEC 60529/DIN 40050) terminal area IP00 0.5 7.25 4 0.107 Vibration 5 g (57-500 Hz) 0.38 mm (10-57 Hz) 0.6 5.35 4.5 0.095 to IEC 60068-2-6, test Fc 10 frequency cycles/axis 0.7 3.8 5 0.072 Shock 15 g (11 ms) 0.8 2.95 6 0.054 test to IEC 60068-2-27, test Ea Corrosion 48 hours at 5 % salt mist 1 1.92 7 0.032 to IEC 60068-2-11, test Ka 1.2 1.32 8 0.02 Humidity 240 hours at 95 % RH to IEC 60068-2-78, test Cab 1.5 0.85 9 < 0.02 Mass approx. 20 g 1.8 0.59 10 < 0.02 Approvals Authority Standard Rated voltage Current ratings UL UL 244A AC 250 V 0.1 A15 A DC 28 V 0.1 A15 A CSA C22.2 No 235 AC 250 V 0.1 A15 A DC 28 V 0.1 A15 A 1908 www.e-t-a.de 112 Motor Protection Control 2-6500-... Dimensions Typical time/current characteristics at +23 C/+73.4 F 10000 4 .157 P 3 2 1000 8.25 8.25 .325 .325 44.5 1.75 100 52 2.05 1 10 3.5 6.3 .138 .248 8 .315 1 Internal connection diagram 0.1 12 46 8102040 times rated current P The time/current characteristic curve depends on the ambient temperature (3) prevailing. In order to eliminate nuisance tripping, please multiply the circuit breaker current ratings by the derating factor shown below. See also section Technical information. +14 +32 +50 +73.4 +86 +104 +122 +140 Ambient temp. F -10 0 +10 +23 +30 +40 +50 +60 C 2 0.84 0.92 1 1 1 1.08 1.16 1.24 Derating factor mm This is a metric design and millimeter dimensions take precedence ( ) inch All dimensions without tolerances are for reference only. In the interest of improved design, performance and cost effectiveness the right to make changes in these specifications without notice is reserved.Product markings may not be exactly as the ordering codes. Errors and omissions excepted. 2 www.e-t-a.de 1908 22 .866 11.5 12 .472 .453 4 8.5 .335 .157 4 4 .157 .157 0.8 .031 8 0.5 6 .236 .315 .020 10.5 10.7 .421 .413 15.7 .618 Trip time in seconds