120W Single Output Industrial DIN RAIL NDR-120 series Bauar t gep r u f t S i c h e r h e i t e g e l m a ge o d o s b e w a c g w w w .t u v.c o m ID 2000000000 TPTC004 BS EN/EN62368-1 IEC62368-1 File Name:NDR-120-SPEC 2021-06-21120W Single Output Industrial DIN RAIL NDR-120 series SPECIFICATION MODEL NDR-120-12 NDR-120-24 NDR-120-48 DC VOLTAGE 12V 24V 48V RATED CURRENT 10A 5A 2.5A CURRENT RANGE 0 ~ 10A 0 ~ 5A 0 ~ 2.5A RATED POWER 120W 120W 120W RIPPLE & NOISE (max.) Note.2 100mVp-p 120mVp-p 150mVp-p OUTPUT VOLTAGE ADJ. RANGE 12 ~ 14V 24 ~ 28V 48 ~ 55V VOLTAGE TOLERANCE Note.3 2.0% 1.0% 1.0% LINE REGULATION 0.5% 0.5% 0.5% LOAD REGULATION 1.0% 1.0% 1.0% SETUP, RISE TIME 1200ms, 60ms/230VAC 2500ms, 60ms/115VAC at full load HOLD UP TIME (Typ.) 16ms/230VAC 10ms/115VAC at full load VOLTAGE RANGE Note.6 90 ~ 264VAC 127 ~ 370VDC DC input operation possible by connecting AC/L(+), AC/N(-) FREQUENCY RANGE 47 ~ 63Hz EFFICIENCY (Typ.) 85.5% 88% 89% INPUT 2.25A/115VAC 1.3A/230VAC AC CURRENT (Typ.) 20A/115VAC 35A/230VAC INRUSH CURRENT (Typ.) LEAKAGE CURRENT <1mA / 240VAC 105 ~ 130% rated output power OVERLOAD Protection type : Constant current limiting, recovers automatically after fault condition is removed 14 ~ 17V 29 ~ 33V 56 ~ 65V PROTECTION OVER VOLTAGE Protection type : Shut down o/p voltage, re-power on to recover OVER TEMPERATURE Shut down o/p voltage, re-power on to recover -20 ~ +70 (Refer toDerating Curv) WORKING TEMP. 20 ~ 95% RH non-condensing WORKING HUMIDITY -40 ~ +85, 10 ~ 95% RH ENVIRONMENT STORAGE TEMP., HUMIDITY TEMP. COEFFICIENT 0.03%/ (0 ~ 50) VIBRATION Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes Mounting: Compliance to IEC60068-2-6 SAFETY STANDARDS UL508, TUV BS EN/EN62368-1, EAC TP TC 004 approved (meet BS EN/EN60204-1) WITHSTAND VOLTAGE I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC SAFETY & ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25/ 70% RH EMC (Note 4) EMC EMISSION Compliance to BS EN/EN55032 (CISPR32), BS EN/EN61204-3 Class B, BS EN/EN61000-3-2,-3, EAC TP TC 020 Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55024, BS EN/EN61000-6-2 (BS EN/EN50082-2), EMC IMMUNITY BS EN/EN61204-3, heavy industry level, criteria A, EAC TP TC 020 MTBF 456.3K hrs min. MIL-HDBK-217F (25) OTHERS DIMENSION 40*125.2*113.5mm (W*H*D) 0.6Kg 20pcs/13Kg/1.16CUFT PACKING NOTE