2000~6000W 1U Distributed Power System RKP-1U Rack System < = Bauart gepruft Sicherheit :+, ) ,6 + :: & egelma ge od os be wac g www.tuv.com ID 2000000000 * >,& , + ( 5% 4 3 8 * ( 4 1 ( & 9 ( 0 /0 % 6 % & ( ( * , - . ( /0 12 133 4 ( % %/ % & %/ 7 %/ 1 ( 7 %/ %/ 7 %/ 87 5% 8 &89%, % : 7 %/ -7 - 87 5% 8 &89%, % : -7 - 7 ) 7 / . File Name:RKP-1U RACK SYSTEM-SPEC 2016-07-262000~6000W 1U Distributed Power System RKP-1U Rack System SPECIFICATION - Power Supply System MODEL RKP-6K1U-12 RKP-6K1U-24 RKP-6K1U-48 RECTIFIER RCP-2000-12 RCP-2000-24 RCP-2000-48 RACK SHELF RKP-1UI or RKP-1UT OUTPUT VOLTAGE 12V 24V 48V OUTPUT MAX. OUTPUT CURRENT 300A 240A 126A MAX. OUTPUT POWER Note.7 3600W 5760W 6048W VOLTAGE RANGE Note.6 90 ~ 264VAC 127 ~ 370VDC FREQUENCY RANGE 47 ~ 63Hz INPUT 13A/115VAC 7A/230VAC 16A/115VAC 11A/230VAC 16A/115VAC 11A/230VAC AC CURRENT (Typ.)PER MODULE LEAKAGE CURRENT <3.5mA / 230VAC 5V 0.3A, 12V 0.8A AUXILIARY POWER REMOTE ON-OFF CONTROL By electrical signal or dry contact ON:short OFF:open Compensate voltage drop on the load wiring up to 0.5V. REMOTE SENSE Adjustment of output voltage is allowable to 90 ~ 110% of nominal output voltage. Please refer to the Function Manual. OUTPUT VOLTAGE PROGRAMMABLE FUNCTION The isolated TTL signal out, Please refer to the Installation Manual DC OK SIGNAL AC OK SIGNAL The isolated TTL signal out, Please refer to the Installation Manual OVER TEMP WARNING Logic Hig for over temperature warning, Please refer to the Installation Manual, isolated signal The isolated TTL signal out, Please refer to the Installation Manual FAN FAIL SIGNAL -40 ~ +70 (Refer toDerating Curv) WORKING TEMP. 20 ~ 90% RH non-condensing WORKING HUMIDITY STORAGE TEMP., HUMIDITY -40 ~ +85, 10 ~ 95% RH ENVIRONMENT TEMP. COEFFICIENT 0.03%/ (0 ~ 50) VIBRATION 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes SAFETY STANDARDS UL60950-1, TUV EN60950-1 approved WITHSTAND VOLTAGE I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.7KVDC ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25/ 70% RH Parameter Standard Test Level / Note Conducted EN55022 (CISPR22) / EN55011 (CISPR11) Class A Radiated EN55022 (CISPR22) / EN55011 (CISPR11) Class A EMC EMISSION Harmonic Current EN61000-3-2 ----- Voltage Flicker EN61000-3-3 ----- EN55024 , EN61204-3, EN61000-6-2 SAFETY & Parameter Standard Test Level / Note EMC (Note 5) ESD EN61000-4-2 Level 3, 8KV air Level 2, 4KV contact Radiated EN61000-4-3 Level 3 EFT / Burst EN61000-4-4 Level 3 EMC IMMUNITY Surge EN61000-4-5 Level 4, 4KV/Line-Earth Level 3, 2KV/Line-Line Conducted EN61000-4-6 Level 3 Magnetic Field EN61000-4-8 Level 4 >95% dip 0.5 periods, 30% dip 25 periods, Voltage Dips and Interruptions EN61000-4-11 >95% interruptions 250 periods DIMENSION Rack 483.6*350.8*44(L*W*H) OTHERS 14.1Kg 1pcs/14.1Kg/2.67CUFT PACKING 5 21- 5% 6 NOTE A /= B A :> , ( 9% 8 ( C : - 7 6 - D 5 9/% . > , - D 9/% ( 3 9/% E9/8 F & ( 744 ) ( > 1 % + 0 ( ( 8 ( C File Name:RKP-1U RACK SYSTEM-SPEC 2016-07-26