D1U54P-W-1500-12-HxxTC Series
54mm 1U Front End AC-DC Power Supply Converter
PRODUCT OVERVIEW
The D1U54P-W-1500-12-HxxTC product series offers very high efciency in a compact form factor. These variants offers
1500 watt, and is a power factor corrected front end supply with a 12Vdc main output and either a 3.3V, 5V or 12V
auxiliary/standby output. Active (digital) current sharing is provided and up to eight supplies may be operated in parallel.
The supply may be hot plugged, and auto recovers from overtemperature faults, that are reported by a status LEDS on the
front panel in addition to logic and PMBus status signals. The low prole 1U package and excellent 35W/cubic inch
power density it ideal for delivering reliable, efcient power to servers, workstations, storage systems and other 12V
distributed power architectures.
ORDERING GUIDE
Power Output Power Output Power Output
Input Voltage Input Voltage Input Voltage Main Standby
Part Number Airow
(200-240 Vac) (110-120 Vac) (100 Vac) Output Output
45C 45C 40C
D1U54P-W-1500-12-HC4TC 3.3Vdc
Back to
D1U54P-W-1500-12-HA4TC 5Vdc
Front
D1U54P-W-1500-12-HB4TC 1500W 1400W 1260W 12Vdc 12Vdc
D1U54P-W-1500-12-HC3TC 3.3Vdc Front to
D1U54P-W-1500-12-HA3TC 5Vdc Back
FEATURES
1
The HAxTC variants are certified for compliance to 80 PLUS Platinum efficiency requirements.
+1500W continuous output power
IEC60320-C16 connector for maximized
INPUT CHARACTERISTICS
low line operation
Parameter Conditions Min. Nom. Max. Units
94% efciency at 50% Load
Input Voltage Operating Range 90 115/230 264 Vac
12V main output
Input Frequency 47 50/60 63 Hz
3.3V; 5V and 12V standby output Options
Turn-on Input Voltage Ramp up 74 84
Vac
1U height: 2.15" x 12.65" x 1.57"
Turn-off Input Voltage Ramp down 70 80
> 35 watts per cubic inch density
Maximum current Vin = 100 Vac/60Hz; 1260W 15 Arms
N+1 redundancy, hotpluggble, Ishare
Cold start between 0 to
Inrush Current 50 Apk
compatible with DC input series
200msec, 264Vac
active (digital) current sharing on 12V
Power Factor At 230Vac, full load 0.99
main output; integral ORing /isolation
20% load 90
device MOSFET
Efciency (230Vac) excluding fan load 50% load 94 %
internal cooling fan (variable speed)
100% load 91
overvoltage, overcurrent,
OUTPUT VOLTAGE CHARACTERISTICS
overtemperature protection
Output
Parameter Conditions Min. Typ. Max. Units
PMBus/IC interface with LED status
Nominal Output Voltage 12 Vdc
indicators
Output Set Point Accuracy 50% load; Tamb =25C -0.5 +0.5
RoHS compliant
2
%
Line and Load Regulation Measured at remote sense -1.0 +1.5
two year warranty
1,2
Ripple Voltage & Noise 20MHz Bandwidth 120 mV p-p
12V
Output Current 1500W; (115-264Vac) 0 125
A
Output Current 1260W; (90-264Vac) 0 105
Load Capacitance 30,000 F
Nominal Output Voltage 3.3 Vdc
Line and Load Regulation 3.14 3.46
1,3
3.3VSB Ripple Voltage & Noise 20MHz Bandwidth 75 mV p-p
Output Current 0 4 A
Load Capacitance 0 3000 F
Nominal Output Voltage 5.0
Available now at: www.murata-ps.com/en/3d/acdc.html Vdc
Line and Load Regulation 4.76 5.24
1,3
5VSB
Ripple Voltage & Noise 20MHz Bandwidth 75 mV p-p
Output Current 0 4 A
Load Capacitance 0 3000 F
Nominal Output Voltage 12
Vdc
Line and Load Regulation 11.7 12.3
1,3
12VSB Ripple Voltage & Noise 120 mV p-p
A
Output Current 0 2.5
Load Capacitance F
1000
1
Ripple and noise are measured with 0.1 F of ceramic capacitance and 10 F of tantalum capacitance on each of the power supply
outputs. A short coaxial cable to the scope termination is used.
2
Minimum Load of 5A.
3
Minimum Load of 0.25A.
CB
For full details go to
www.murata-ps.com/rohs
D1U54P-W-1500-12-HxxTC Series
54mm 1U Front End AC-DC Power Supply Converter
OUTPUT CHARACTERISTICS
Parameter Conditions Min. Typ. Max. Units
Startup Time AC ramp up
3 s
12V Main 10% to 60% load step; 1A/s slew rate -5
+5 % nom
Recovery Time to within 1% Vnom
2 Ms
3.3V & 5VSB, 10% to 60% load step; 1A/s slew rate -5
+5 % nom
Transient Response
Recovery Time to within 1% Vnom
2 ms
12VSB, 10% to 60% load step; 1A/s slew rate. -5
+5 % nom
Recovery Time to within 1% Vnom
2 ms
Current sharing accuracy At 100% load -5 +5 %
Hot Swap Transients All outputs remain in regulation -5 +5 %
110/230Vac in voltage ranges, 100% load (1500W) 12 ms
Holdup Time
110/230Vac in voltage ranges, 900W load 20 ms
ENVIRONMENTAL CHARACTERISTICS
Parameter Conditions Min. Typ. Max. Units
Storage Temperature Range -40 70
Operating Temperature Range 1500W (180-264Vac) See Derating Curves -5 45
C
Operating Temperature Range 1260W (90-264Vac) -5
Continuous 45
Operating Temperature Range (85-264Vac)
See Derating Curves -5 40
Operating Humidity Noncondensing 5 90
%
Storage Humidity 5 95
Altitude (without derating at 40C) 3000 m
Shock 30G non-operating
Sine sweep; 5-150Hz, 2G;
Operational Vibration
random vibration, 5-500Hz, 1.11G
MTBF Per Telcordia SR-332 M1C1 @40C 540K hrs.
CAN/CSA C22.2 No 60950-1-07, Am.1:2011; Am 2_2014
nd nd
UL 60950-1-2011, 2 Ed. UL 60950-1, 2 Ed.
TUV EN60950
nd
Safety Approval Standards (Planned Submissions) IEC60950-1:2005 (2 Ed.)_A1
EN 60950-1:2006+A11+A1+A12+A2
BSMI (099/09/30); CNS13438 ((095/06/01)
CQC GB4943.1-2011; GB9254-1-2008; GB17625, 1-2012
Input Fuse Power Supply has single internal 20A/250V fast blow fuse on the AC line input
Weight 3.15 lbs. (1.43 kg)
PROTECTION CHARACTERISTICS
Output
Parameter Conditions Min. Typ. Max. Units
Voltage
Overtemperature (intake) Autorestart
60 65 70 C
Overvoltage Latching
13.0 14.5 V
Shortciruit 4 Hiccup then latch
145 -
12V
A
Overcurrent At 90-264VVac 4 Hiccup, >500msec each, then latch
132 150
Overvoltage Latching
3.6 4.0 V
3.3VSB
Overcurrent Hiccup 5.1
6.7 A
Overvoltage Latching 5.4 6.0 V
5VSB
Overcurrent Hiccup 5.1 6.7 A
Overvoltage Latching 13.0 14.5 V
12VSB
Overcurrent Hiccup 3.5 4.5 A