Switch Amplifier KFA5-SR2-Ex1.W Features Assembly 1-channel isolated barrier 115 V AC supply Front view Dry contact or NAMUR inputs Removable terminal Relay contact output blue Line fault detection (LFD) 1 2 3 Reversible mode of operation 4 5 6 Up to SIL 2 acc. to IEC 61508/IEC 61511 LED yellow: LED green: KFA5-SR2-Ex1.W Relay output Power supply Function OUT CHK PWR LED red: Switch S1 S1 LB/SC (mode of operation) S2 This isolated barrier is used for intrinsic safety applications. It S3 I II transfers digital signals (NAMUR sensors/mechanical Switch S2 contacts) from a hazardous area to a safe area. (no functions) The proximity sensor or switch controls a form C changeover 7 8 9 10 11 12 Switch S3 13 14 15 relay contact for the safe area load. The barrier output (LB/SC-monitoring) changes state when the input signal changes state. The normal output state can be reversed using switch S1. Removable terminals Switch S3 is used to enable or disable line fault detection of green the field circuit. During an error condition, the relay reverts to its de-energized state and the LEDs indicate the fault according to NAMUR NE44. 2 Connection KFA5-SR2-Ex1.W 1+ 7 8 10 k 2+ 9 10 k 3- 400 R 2 k 14 115 V AC 15 Zone 0, 1, 2 Div. 1, 2 Refer toGeneral Notes Relating to Pepperl+Fuchs Product Informatio. Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 1 www.pepperl-fuchs.com pa-info us.pepperl-fuchs.com pa-info de.pepperl-fuchs.com pa-info sg.pepperl-fuchs.com Release date 2016-05-18 16:22 Date of issue 2016-05-18 103371 eng.xmlTechnical data KFA5-SR2-Ex1.W General specifications Signal type Digital Input Supply Connection terminals 14, 15 Rated voltage U 103.5 ... 126 V AC , 45 ... 65 Hz n Power consumption 1 W Input Connection terminals 1+, 2+, 3- Rated values acc. to EN 60947-5-6 (NAMUR) Open circuit voltage/short-circuit current approx. 8 V DC / approx. 8 mA Switching point/switching hysteresis 1.2 ... 2.1 mA / approx. 0.2 mA Line fault detection breakage I 0.1 mA , short-circuit I > 6 mA Pulse/Pause ratio 20 ms / 20 ms Output Connection terminals 7, 8, 9 Output signal, relay Contact loading 253 V AC/2 A/cos > 0.7 126.5 V AC/4 A/cos > 0.7 40 V DC/2 A resistive load Energized/De-energized delay approx. 20 ms / approx. 20 ms 7 Mechanical life 10 switching cycles Transfer characteristics Switching frequency < 10 Hz Electrical isolation Input/Output reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff Input/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff Output/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff Directive conformity Electromagnetic compatibility Directive 2014/30/EU EN 61326-1:2013 (industrial locations) Low voltage Directive 2014/35/EU EN 61010-1:2010 Conformity Electromagnetic compatibility NE 21:2006 Degree of protection IEC 60529:2001 Input EN 60947-5-6:2000 Ambient conditions Ambient temperature -20 ... 60 C (-4 ... 140 F) Mechanical specifications Degree of protection IP20 Mass approx. 150 g Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in) , housing type B2 Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001 Data for application in connection with Ex-areas EC-Type Examination Certificate PTB 00 ATEX 2081 Group, category, type of protection II (1)G Ex ia Ga IIC II (1)D Ex ia Da IIIC I (M1) Ex ia Ma I Input Ex ia Voltage U 10.6 V o Current I 19.1 mA o Power P 51 mW (linear characteristic) o Supply Maximum safe voltage U 126.5 V AC (Attention U is no rated voltage.) m m Output Contact loading 253 V AC/2 A/cos > 0.7 126.5 V AC/4 A/cos > 0.7 40 V DC/2 A resistive load Maximum safe voltage U 253 V AC (Attention The rated voltage can be lower.) m Electrical isolation Input/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V Input/power supply safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V Directive conformity Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 International approvals FM approval Control drawing 116-0035 UL approval Refer toGeneral Notes Relating to Pepperl+Fuchs Product Informatio. Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091 2 www.pepperl-fuchs.com pa-info us.pepperl-fuchs.com pa-info de.pepperl-fuchs.com pa-info sg.pepperl-fuchs.com Release date 2016-05-18 16:22 Date of issue 2016-05-18 103371 eng.xml