DATASHEET Single-Stage Filters FN 2030
General Purpose EMI Filter with High Attenuation Performance
Rated currents from 1 to 30 A Approvals
High performance filter attenuation
High differential-mode attenuation
Optional medical versions (B type)
Optional safety versions (A type)
Optional overvoltage protection (Z type)
Features and benefits
FN 2030 filters are designed for easy and fast chassis
mounting
The FN 2030 filters are also available as B versions
with no Y-capacitors for medical applications as well
as A versions with low capacitance for safety critical
applications with a requirement for low leakage
currents
All filters provide an exceptional conducted
attenuation performance, based on chokes with
high permeable core material and excellent thermal
behavior
The higher inductivity versus amperage offers
increased attenuation performance with same form
factor compared to FN 2010 and FN 2020 filter series
All FN 2030 filters can be delivered with optional
surge pulse protection. FN 2030 filters are also
available as two- stage filters (FN 2090 series) for very
noisy environment
Various terminal options allow you to select the
Technical specifications
desired connection style
Operating voltage 110/250 VAC, 50/60 Hz
Typical application
Operating frequency dc to 400 Hz
Rated currents 1 to 30 A @ 40 C max. Electrical and electronic equipment
High potential test voltage P > PE 2000 VAC for 2 sec (standard types)
Consumer goods
P > N 1100 VDC for 2 sec
Household equipment
P > PE 2500 VAC for 2 sec (B types)
Medical equipment
Temperature range (operation and storage) -25 C to +100 C (25/100/21)
Electronic data processing equipment
Design corresponding to UL 1283, CSA 22.2 No. 8 1986, IEC/EN 60939
Office automation and datacom equipment
Flammability corresponding to UL 94 V-2 or better
Various noisy applications requiring high filter
Surge pulse protection (optional) 2kV, IEC 61000-4-5
performance
MTBF @ 40C/230V (Mil-HB-217F) 2,200,000 hours (1 to 10 A types)
1,200,000 hours (12 to 30 A types)
Typical electrical schematic
2 EMC/EMI Products Schaffner Group Datasheets 2015
Filter selection table
Filter* Rated current Leakage current** Inductance Capacitance Resistance Input/Output Weight
@ 40 C (25 C) @ 230 VAC/50 Hz L Cx Cy R connections
[A] [mA] [mH] [F] [nF] [k] [g]
FN 2030-1-.. (1.1) 0.34 20 0.22 2.2 1000 -06 -07 58
FN 2030-3-.. 3 (3.4) 0.52 14 0.33 3.3 1000 -06 -07 87
FN 2030-4-.. 4 (4.5) 0.52 14 0.33 3.3 1000 -06 -07 92
FN 2030-6-.. 6 (6.7) 0.73 8 0.47 4.7 680 -06 -07 100
FN 2030-8-.. 8 (8.9) 0.73 8 0.47 4.7 680 -06 -07 170
FN 2030-10-.. 10 (11.2) 0.73 8 0.47 4.7 680 -06 -07 196
FN 2030-12-.. 12 (13.4) 0.87 4 1.0 10 330 -06 -07 185
FN 2030-16-.. 16 (17.9) 0.87 4 1.0 10 330 -06 -07 225
FN 2030-20-.. 20 (22.4) 0.87 4 1.0 10 330 -06 -08 285
FN 2030-30-08 30 (33.5) 0.87 2 1.0 10 330 -08 326
FN 2030A-1-.. 1 (1.1) 0.074 20 0.22 0.47 1000 -06 -07 58
FN 2030A-3-.. 3 (3.4) 0.074 14 0.33 0.47 1000 -06 -07 87
FN 2030A-4-.. 4 (4.5) 0.074 14 0.33 0.47 1000 -06 -07 92
FN 2030A-6-.. 6 (6.7) 0.074 8 0.47 0.47 680 -06 -07 100
FN 2030A-8-.. 8 (8.9) 0.074 8 0.47 0.47 680 -06 -07 170
FN 2030A-10-.. 10 (11.2) 0.074 8 0.47 0.47 680 -06 -07 196
FN 2030A-12-.. 12 (13.4) 0.074 4 1.0 0.47 330 -06 -07 185
FN 2030A-16-.. 16 (17.9) 0.074 4 1.0 0.47 330 -06 -07 225
FN 2030A-20-.. 20 (22.4) 0.074 4 1.0 0.47 330 -06 -08 285
FN 2030A-30-08 30 (33.5) 0.074 2 1.0 0.47 330 -08 326
FN 2030B-1-.. 1 (1.1) 0.002 20 0.22 1000 -06 -07 58
FN 2030B-3-.. 3 (3.4) 0.002 14 0.33 1000 -06 -07 87
FN 2030B-4-.. 4 (4.5) 0.002 14 0.33 1000 -06 -07 92
FN 2030B-6-.. 6 (6.7) 0.002 8 0.47 680 -06 -07 100
FN 2030B-8-.. 8 (8.9) 0.002 8 0.47 680 -06 -07 170
FN 2030B-10-.. 10 (11.2) 0.002 8.45 0.47 680 -06 -07 196
FN 2030B-12-.. 12 (13.4) 0.002 4 1.0 330 -06 -07 185
FN 2030B-16-.. 16 (17.9) 0.002 4 1.0 330 -06 -07 225
FN 2030B-20-.. 20 (22.4) 0.002 4 1.0 330 -06 -08 285
FN 2030B-30-08 30 (33.5) 0.002 2 1.0 330 -08 326
* To compile a complete part number, please replace the -.. with the required I/O connection style. For surge pulse protection, please add Z (e.g. FN 2030Z-10-06, FN 2030BZ-20-
08).
** Maximum leakage under normal operating conditions. Note: if the neutral line is interrupted, worst case leakage could reach twice this level.
Typical filter attenuation
Per CISPR 17; A = 50 /50 sym; B = 50 /50 asym; C = 0.1 /100 sym; D = 100 /0.1 sym
1 to 4 A types 6 to 10 A types 12 to 20 A types 30 A types