Product data sheet 6EP1332-1SH43 LOGO POWER 24 V STABILIZED POWER SUPPLY INPUT: 100-240 V AC (110-300 V DC) OUTPUT: 24 V/2.5 A DC Technical specifications Product LOGO Power Power supply, type 24 V/2.5 A Input Input 1-phase AC or DC Rated voltage value Vin rated 100 240V Voltage range 85 264V Input voltage / at DC 110 300V Wide-range input Yes Overvoltage resistance 2.3 Vin rated, 1.3 ms Mains buffering at Iout rated, min. 40ms Mains buffering at Vin = 187 V Rated line frequency 50 / 60Hz Rated line range 47 ... 63Hz Input current / at nominal level of the input voltage 120 V 1.22A Input current / at nominal level of the input voltage 230 V 0.66A Switch-on current limiting (+25 C), max. 46A It, max. 3As Built-in incoming fuse internal Protection in the mains power input (IEC 898) Recommended miniature circuit breaker: from 16 A, characteristic B or from 10 A, characteristic C 6EP1332-1SH43 subject to modifications Page 1/4 10/22/2012 Copyright Siemens AG 2012Output Output Controlled, isolated DC voltage Rated voltage Vout DC 24V Total tolerance, static 3% Static mains compensation, approx. 0.1% Static load balancing, approx. 1.5% Residual ripple peak-peak, max. 200mV Residual ripple peak-peak, typ. 10mV Spikes peak-peak, max. (bandwidth: 20 MHz) 300mV Spikes peak-peak, typ. (bandwidth: 20 MHz) 50mV Adjustment range 22.2 26.4V Product feature / output voltage adjustable Yes Output voltage setting via potentiometer Status display Green LED for output voltage OK On/off behavior No overshoot of Vout (soft start) Startup delay, max. 0.5s Voltage rise, typ. 10ms Rated current value Iout rated 2.5A Current range 0 2.5A Note 2.5 A up to +55 C, 1.7 A up to +70 C delivered active power / typ. 60W Parallel switching for enhanced performance Yes Numbers of parallel switchable units for enhanced performance 2 Efficiency Efficiency at Vout rated, Iout rated, approx. 88% Power loss at Vout rated, Iout rated, approx. 8W Closed-loop control Dynamic mains compensation (Vin rated 15 %), max. 0.2% Dynamic load smoothing (Iout: 10/90/10 %), Uout typ. 2% Load step setting time 10 to 90%, typ. 1ms Load step setting time 90 to 10%, typ. 1ms Protection and monitoring Output overvoltage protection Yes, according to EN 60950 Current limitation, typ. 3.3A Characteristic feature of the output / short-circuit protected Yes Short-circuit protection Constant current characteristic Enduring short circuit current / Effective level / maximum 4.8A Overload/short-circuit indicator - Safety 6EP1332-1SH43 subject to modifications Page 2/4 10/22/2012 Copyright Siemens AG 2012