Commercial/Medical International + Linears
Medical
Commercial
FEATURES
World-wide ac input ranges and safety standards Medical leakage current does not exceed 10 A
Industry standard packages
MTBF 200,000+ hours per Mil Handbk 217D (most units)
Commercial UL/CSA TUV/IEC approved68 models to All electrolytic caps rated at 105C
UL1950; CSA C22.2 No. 950 L3; TUV certified to EN60950 Transformer insulation meets Class F (155C)
Burn-in with cycling; 3-year warranty Exceed FCC and CISPR22, Class B conducted emissions
Capacitors have highest CV & ripple current ratings
marked to LVD
Medical Approved to UL2601-1, IEC60601-1 and
CSA601.1
SPECIFICATIONS:
Ac Input
Remote Sensing
100, 120 and 240 Vac: +10%, -13%; 215 Vac: +12%, -11
Provided on all models; open sense lead protection built-in
%; 47 to 63Hz. Tolerance for 230 Vac operation is +15%,
(except HA series).
-10%. Derate output current 10% for 50 Hz operation.
Stability
Dc Output
0.05% for 24 hours after warmup.
See voltage rating chart. Adjustment range 5% minimum
except HA series.
Temperature Rating
0 to 50C full rated, derated linearly to 40% at 70C.
Line Regulation
0.05% for a 10% change.
Temperature Coefficient
0.01%/C maximum.
Load Regulation
0.05% for a 50% load change.
Efficiency
5 V units: 45%; 12 and 15 V units: 55%; 20 and 24 V units: 60%.
Output Ripple
3 mV +0.05% of output voltage, peak to peak maximum.
Logic Inhibit and Current-Share
All 3-terminal regulator outputs: 3 mV +0.2% peak to
F & G models.
peak maximum.
Medical Stock and Vibration
Transient Response
Per Mil-Std-810D, Method 514.3, Category 1, Procedure 1.
<50 microseconds for 50% load change.
Per Mil-Std-810D, Method 516.3, Procedure III.
Short Circuit Protection
Storage
Automatic current limit/foldback.
-40 to +85 C.
Overvoltage Protection
Built-in on all 5 V models, set at 6.2 V 0.4 V. Other models
use optional overvoltage protection.
Condor D.C. Power Supplies, Inc., 2311 Statham Parkway, Oxnard, CA 93033
800-235-5929 805-486-4565 FAX 805-487-8911 www.condorpower.com
116Commercial/Medical International + Linears
Commercial Medical
Voltage Current Case
Model (Single) Model
HA2-1.5-A+ 2AV 1B.5
HB2-3-A+ 2AV 3B
HC2-6-A+ 2AV 6C
HN2-9-A+ 2AV 9N
HD2-12-A+ 2AV 1D2
HE2-18-A+* 2AV 1E8
ML5-OV-A 5AV 1L.0
HA5-1.5-OV-A+ 5AV 1B.5
HB5-3-OV-A+ MB5-3-OV-A 5AV 3B
HC5-6-OV-A+ MC5-6-OV-A 5AV 6C
HN5-9-OV-A+ 5AV 9N
HD5-12-OV-A+ MD5-12-OV-A 5AV 1D2
HE5-18-OV-A+* 5AV 1E8
F5-25-OV-A+* 5AV 2F5
G5-35-OV-A+* 5AV 3G5
CP197-A+* 5AV 5G0
ML12-0.5-A 1A2 V 0L.5
HA15-0.9-A+ (12 V) 1A2 V 0B.9
HB12-1.7-A+ MB12-1.7-A 1A2 V 1B.7
HC12-3.4-A+ MC12-3.4-A 1A2 V 3C.4
HN12-5.1-A+ 1A2 V 5N.1
HD12-6.8-A+ MD12-6.8-A 1A2 V 6D.8
HE12-10-2-A+* 1A2 V 1E0.2
F15-15-A+* (12V) 1A2 V 1F6
ML15-0.4-A 1A5 V .L4
HA15-0.9-A+ 1A5 V 0B.9
HB15-1.5-A+ MB15-1.5-A 1A5 V 1B.5
HC15-3-A+ MC15-3-A 1A5 V 3C
HN15-4.5-A+ 1A5 V 4N.5
HD15-6-A+ MD15-6-A 1A5 V 6D
HE15-9-A+* 1A5 V 9E
F15-15-A+* 1A5 V 1F5
ML24-0.28-A 2A4 V .L28
HA24-0.5-A+ 2A4 V 0B.5
HB24-1.2-A+ MB24-1.2-A 2A4 V 1B.2
HC24-2.4-A+ MC24-2.4-A 2A4 V 2C.4
HN24-3.6-A+ 2A4 V 3N.6
HD24-4.8-A+ MD-24-4.8-A 2A4 V 4D.8
HE24-7.2-A+* 2A4 V 7E.2
F24-12-A+* 2A4 V 1F2
HA24-0.5-A+ (28V) 2A8 V 0B.5
HB28-1-A+ MB28-1-A 2A8 V 1B
HC28-2-A+ MC28-2-A 2A8 V 2C
HN28-3-A+ 2A8 V 3N
HD28-4-A+ MD28-4-A 2A8 V 4D
HE28-6-A+* 2A8 V 6E
F24-12-A+* (28V) 2A8 V 1F0
HB48-0.5-A+ 4A8 V 0B.5
HC48-1-A+ 4A8 V 1C
HD48-3-A+** 4A8 V 3D
HE48-4-A+* 4A8 V 4E
F48-6-A+* 4A8 V 6F
Condor D.C. Power Supplies, Inc., 2311 Statham Parkway, Oxnard, CA 93033
800-235-5929 805-486-4565 FAX 805-487-8911 www.condorpower.com
117