Edco SLCP Series
TwoP airSL CLoopProtector(M odular)
The Edco SLCP Series are four-wire modules designed to protect signaling line
circuits (SLC). The device has 0 ohms of resistance and offers line to ground
protection.
General Technical Specifications
OperatingVoltage 5,12, 18, 24,32,36, 48,52VDC
ClampingVoltage 8,15,20,30,36,43, 50, 60VDC
OperatingCurrent 1A
PeakSur geCurrent 250A(8x20s)
FrequencyRange 0to20MHz EDCO PCB1B-WKEY BASE SOLD SEPARATELY
InsertionL oss <0.1 dBat20MHz
SPDTechnology SiliconA valancheDiode(S AD)
Features
ConnectionType Terminalblockw/c ompressionlugs
Terminalsa cceptu pto10A WG
CompatiblewithSLCc ircuits
OperatingTemperature -40Ct o+85C
Line-to-groundprotection
Dimensions(in/ mm) 2.0Hx1.0Wx2.5 L
[50.8x25.4x63.5mm]
State-of-the-artsi licontechnology
(SLCP+P CB1B-WKEYB ase)
Over-currentprotection
Weight(o z/ k g) 1oz[0.03 k g]
Certifications UL497B
ULlis ted497B
Warranty 5years
RequiresE dcoPCB1B-WKEYbase
PC642PTU(P assThr uUnit)
availablefortr oubleshooting
Ordering Information
5y earw arranty
How to Specify the Appropriate Model
OPERATING CLAMPING
MODEL
VOLTAGE VOLTAGE
SLCP-08 5VDC 8VDC
SLCP-15 12VDC 15VDC
SLCP-20 18 VDC 20VDC
SLCP-30 24VDC 30VDC
SLCP-36 32VDC 36VDC
SLCP-43 36VDC 43VDC
SLCP-50 48VDC 50VDC
SLCP-60 52VDC 60VDCInstallation Instructions
DANGER!
V
Only qualified personnel should install or
Terminal Assignments
service this system. Electrical safety pre-
cautions must be followed when installing
PCB1B-WKEY
or servicing this equipment. To prevent risk
of electrical shock, turn off and lock out all
Odd Terminals Even Terminals
power sources to the unit before making
10
electricalc onnectionsor servicing.
9
8
2.4"
Unprotected Pair 2
{
7
Seulement le personnel qualifi doit installer
Protected Pair 2
} [60.96]
6
ou maintenir ce systme. Des prcautions
Field Side
5
de scurit en lectricit doivent tre suivis
Electronics Side
2.125"
4
Unprotected Pair 1 {
3 lors de linstallation ou de la maintenance
[53.98]
Protected Pair 1
}
2
de cet equipement. Pour eviter tout risque
1
de choc lectrique, dbranchez et verouiller
Keying Pin toutes les sources dalimentation de cet
equipementa vantde .
1.0
[25.40]
GroundTerminal1or 10 toBui ldingA pprovedGround
(preferablyACPowers afetygr ound).
NOTE: DONOTdaisychaingrounds.NOTintendedf orshieldt ermination.
Installgroundinaccordancewith allapplicablecodes.
Emerson Network Power Contact information www.EmersonNetworkPower.com/Surge
SurgePr otection
100EmersonParkway
Binghamton,NY13905
T:(607)721-8840
T:(800)288-6169
F:(607)722-8713
E:SurgeTech@Emerson.com
EmersonNetworkP ower,the Eme rsonN etworkPowerlog oan dEdcoaretrademarks
IO-501165/14Rev.3PrintedinUSA andservicemarksofEmersonElectricCo.2014Eme rsonElec tricC o.
While every precaution has been taken to ensure accuracy and completeness herein, Emerson Network Power Surge Protection assumes no responsibility, and disclaims all liability, for damages
resultingfromuseo fthis in formationor foranyerrorsoromissions.S pecificationsaresubjecttochangewith outnotice.