Power Supplies
3
SDP Low Power DIN Rail Series
The compact, lightweight DIN Rail power supplies come
in output voltages from 5 to 48 Vdc and power ratings of
up to 100 Watts. These extra small, efficient units are
designed specifically for the industrial environment. Each
unit is rated from -10C to 70C, with no derating necessary
until above 60C.
Many extra industrial features are standard for the
TM
SDP PowerBoost overload circuitry can start up
industrial loads (i.e. motors, relays, solenoids and DC-DC
converters), that can cause ordinary power supplies to
E137632
foldback or shutdown. Each unit contains a DC indicator E61379
E234790
and front panel adjustment potentiometer. With the SolaHD
Three year limited warranty
SDP series, you can count on a high grade design.
NEC Class 2 power supply acc. to NFPA 70 article
725-41 (a)(2) except Model SDP 4-24-100RT
Applications
Industrial Control
Certifications and Compliances
Process Control
Listed, Industrial Control Equipment, E61379
Machine Control
- UL 508, CSA C22.2 No. 107.1
Building Automation
Recognized Component, ITE, E137632
UL 60950
E137632
Instrumentation
- UL 60950-1/CSA C22.2 No. 60950-1, 2nd Edition
CUL/CSA-C22.2
No. 234-M90
Recognized Component, Haz. Loc., E234790
UL 60950
E137632
Features
- ISA 12.12.01, CSA C22.2 No. 213
CUL/CSA-C22.2
No. 234-M90
Ultra slim 15W footprint
- Class I, Division 2, Groups A, B, C, D
No tools required for mounting
- IEC/EN60950-1, 2nd Edition
Adjustable output
TM
RoHS Compliant
PowerBoost industrial overload design
Overvoltage, short circuit protection
Related Products
Continuous short circuit protection
SDN Series
Low output noise
SCP Series
Screw terminal connections
Selection Table
Catalog Number DC Output Voltage Output Current Ripple / Noise Size (H x W x D) - in. (mm)
5 - 6 V 5 A
SDP 5-5-100T
10 - 12 V 3 - 2.5 A
SDP 2-12-100T
2.95 in x 1.77 in x 3.58 in
(75.0 mm x 45.0 mm x 91.0 mm)
12 - 15 V 4.2 - 3.4 A
SDP 3-15-100T
48 - 56 V 1 A
SDP 1-48-100T
2.95 in x 0.9 in x 3.8 in
0.6 A <50 mVpp
SDP 06-24-100T
(75.0 mm x 22.8 mm x 96.7 mm)
1.3 A
SDP 1-24-100T
2.95 in x 1.77 in x 3.58 in
(75.0 mm x 45.0 mm x 91.0 mm)
24-28 Vdc 2.1 A
SDP 2-24-100T
3.8 A
SDP 4-24-100LT
2.95 in x 2.85 in x 3.8 in
(75.0 mm x 72.5 mm x 96.7 mm)
4.2 A
SDP 4-24-100RT *
* NEC Class 1
Contact Technical Services at (800) 377-4384 with any questions.
134
Visit our website at www.solahd.com. Power Supplies
3
SDP Series Specifications (24 V models)
Catalog Number
Description
SDP 06-24-100T SDP 1-24-100T SDP 2-24-100T SDP 4-24-100LT SDP 4-24-100RT
Input
1
85-264 Vac, 90-375 Vdc 85-132 / 176-264 Vac, 210-375 Vdc
Input Voltage
47-63 Hz
Input Frequency
0.4 A / 0.25 A 0.7 A / 0.4 A 1.1 A / 0.7 A 1.8 A / 1.0 A 2.2 A / 1.2 A
Input Current
Not required. Unit provides internal fuse (T3A, not accessible)
External Fusing
> 25 ms
Hold-Up Time
> 80% typ. > 83% typ. > 86% typ. > 88% typ.
Efficiency
< 3.75 W typ. < 6.1 W typ. < 8.1 W typ. < 12 W typ.
Losses
Output
24 V (22.5 - 28.5 Vdc Adj.) 24 V (24 - 25.7 Vdc Adj.) 24 V (22.5 - 28.5 Vdc Adj.)
Output Voltage
Voltage Regulation Static 0.5% V , dynamic + 2% V overall\
out out
2
< 50 mVpp
Ripple/Noise
> 26 Vdc, but < 27.2 > 30 Vdc, but < 33 Vdc,
> 30 Vdc, but < 33 Vdc, auto recovery
Overvoltage Protection (OVP)
Vdc, auto recovery auto recovery
Output Noise
Radiated EMI values below EN61000-6-2
Suppression
Rated Continuous 0.63 A @ 24 Vdc / 1.3 A @ 24 Vdc / 2.1 A @ 24 Vdc / 4.2 A @ 24.5 Vdc /
3.8 A @ 24.5 Vdc
0.54 A @ 28 Vdc 1.1 A @ 28 Vdc 1.8 A @ 28 Vdc 3.6 A @ 28 Vdc
Loading
Continuous operation at overload/short-circuit: up to 1.5 x Nominal Current Continuous
Overload Behavior
Unit is continuously protected against short-circuit, overload and open-circuit.
Protection
35 V
Power Back Immunity
Installation
Green LED on, when V OK.
Status Indicators
out
Molded plastic housing using UL 94 approved flameproof material rating 94V-2.
Case & Mounting
Simple snap-on to DIN TS35/7.5 or TS35/15 rail system.
Dimensions
2.95 x 0.90 x 3.80 2.95 x 1.77 x 3.58 2.95 x 2.85 x 3.80
H x W x D - inches (mm)
(75.0 x 22.8 x 96.7) (75.0 x 45.0 x 91.0) (75.0 x 72.5 x 96.7)
Weight - lbs (kg) 0.4 lbs (.18 kg) 0.5 lbs (.23 kg) 0.7 lbs (.32 kg)
Standard: Vertical; Optional: Horizontal or on top (Contact Technical Services).
Mounting Orientation
Ventilation/Cooling
Normal convection, no fan required; Above/below: 25 mm recommended.
Free space for cooling
Connection
2
Input: screw terminals, connector size range: 20-12AWG (1.5 - 6 mm ) for solid or stranded conductors.
Connector size range
General
Electromagnetic
EN61000-6-3 (Includes EN61000-6-4) Class B (EN 55022) incl. Annex A
Emissions (EMC)
Electromagnetic
EN61000-6-2 (Includes EN61000-6-1) (EN55024) Criterion A: no derogation of performance
Immunity (EMI)
Storage: -25C to +85C Operation: -10 to +60C full power with linear derating to half power from 60C to 70C.
Temperature
(Convection cooling, no forced air required).
> 500,000 hours according to Telcordia/Bellcore Document SR-332, Issue 1
MTBF
Up to 90% RH, noncondensing; IEC 68-2-2, 68-2-3
Humidity
SELV (acc. EN60950)
Safe Low Voltage
IP20 (IEC529), Protection Class 1 (IEC536)
Protection Class/Voltage
3 year limited warranty
Warranty
Notes:
1. Not UL listed for DC input.
2. Ripple/noise is stated as typical values when measured with a 20 MHz, bandwidth scope and 50 Ohm resistor.
Contact Technical Services at (800) 377-4384 with any questions.
135
Visit our website at www.solahd.com.