NV-Power NVM-175 Isolation 2 x MOPPs (3rd edition 60601) type tested to 4.5kVac (equivalent to 6.3kVdc), production Input to Output Reinforced 4.5kVac tested to 4.3kVdc 1 x MOOP (3rd edition 60601) Input to Earth Basic 1.5kVac, 2.3kVdc 1 x MOPP (3rd edition 60601) Output to Earth 1.5kVac Environment 0C to 50C operational, -40C to 85C storage (max 12 months). Temperature Full load, with 2m/s air blown from input to output (approximately 10CFM) 50C to 70C derate each output by 2.5% per C Derating with 2m/s air blown from input to output Low Temp Startup -20C Humidity 5 - 95% RH non condensing 3 x 30g shocks in each plane, total 18 shocks 30g shock = 11ms (+/-0.5msec), half sine Shock Conforms to EN60068-2-27, EN60068-2-47, IEC68-2-27, IEC68-2-47, JIS C0041-1987. Conforms to MIL-STD-810E/F, Method 516.5, Pro I, IV, VI Single axis 10 - 500 Hz at 2g (sweep and endurance at resonance) in all 3 planes Vibration Conforms to EN60068-2-6, IEC68-2-6 Conforms to MIL-STD-810E, Method 514.4, Pro I, Cat 1,9 5000 metres operational Altitude (3000 metres for medical approval, 4000m for 60601-1 3rd edition) Pollution Degree 2, Material group IIIb Global Interface Signals Logic level to en- Standby PSU good signal able main output Power good = logic low signal to indicate when ac supply is good and S 12V / 0.2A Power good High output 1 is within regulation S1 12V / 0.2A Power good Low Channel 1 good = logic low signal to indicate when output 1 is within S2 12V / 0.2A Channel 1 good High regulation S3 12V / 0.2A Channel 1 good Low S5 5V / 0.5A Power good Low Approvals / Accreditations IEC/EN 62368-1, UL62368-1 / CSA 22.2 No 62368-1 File E135494 IEC/EN 60950-1, UL60950-1 / CSA 22.2 No 60950-1 File E135494 IEC/EN 60601-1, UL/CSA 60601-1, ANSI/AAMI ES60601-1 File E349607 CAN/CSA-C22.2 No 60601-1-08 Low Voltage Directive (LVD), electromagnetic compatibility CE Mark (EN62368-1) (EMC) and Restriction of Hazardous Substances (RoHS) CB certificate and Report available on request Please check with technical sales for status of approvals Designed and manufactured under the control of ISO9001 and ISO13485 (including risk management). Immunity EN61000-6-2:2005, EN60601-1-2:2007 Criteria Air discharge 8kV, Contact discharge 6kV. Not applicable to open Electrostatic Discharge EN61000-4-2 Level 3 A frame units Electromagnetic Field EN61000-4-3 Level 3 12V/m A ac input tested to 4.4kV Fast / Burst Transient EN61000-4-4 Level 4 A dc output tested to 2.2kV Surge Immunity EN61000-4-5 Level 3 Common mode - 2.2kV, Differential - 1.1kV A 12V Conducted RF Immunity EN61000-4-6 Level 3 A Power Frequency Magnetic Field EN61000-4-8 Level 4 30A/m A Criteria B for 5 sec interruption and dips to 40% for 5 cycles below Voltage Dips, Variations, Interruptions EN61000-4-11 Class 3 A 154Vac nominal input Emissions EN61000-6-3:2007, EN60601-1-2:2007 (as per CISPR.11/22) Class B, FCC47 part 15 subpart B Radiated Electric Field EN55011, EN55032 see application note for details. Conducted Emissions EN55011, EN55032 (as per CISPR.11/22) Class B, FCC47 part 15 subpart B Conducted Harmonics EN61000-3-2 Class A Flicker EN61000-3-3 Compliant - d only max NVM175 Datasheet 60966 - v14.0 NV-Power NVM-175 2