TDK-Lambda RDS100-24 SPECIFICATIONS B029-01-01D MODEL RDS100-24-5 RDS100-24-12 RDS100-24-15 RDS100-24-24 ITEMS 1 Nominal Output Voltage V 5 121524 2 Maximum Output Current A 20 8.3 6.6 4.2 3 Maximum Output Power W 100 99.6 99 100.8 4 Efficiency (Typ) (*1)%78 79 80 5 Input Voltage Range - 18 - 32VDC 5.4 6 Input Current (Typ) (*1) A 7 Inrush Current (Typ) (*1) - 4.7A at Cold Start 8 Output Voltage Range (*8) V 4.0 - 6.0 9.6 - 14.4 12.0 - 18.0 19.2 - 28.8 9 Maximum Ripple (*2) mV 50 80 80 100 10 Maximum Ripple & Noise (*2) mV 100 170 200 290 11 Maximum Line Regulation (*3) mV 40 96 120 192 12 Maximum Load Regulation (*4) mV 50 100 100 200 13 Temperature Coefficient - Less than 0.02 %/ 14 Over Current Protection (*5) A 22 - 24 9.3 - 9.9 7.4 - 7.9 4.7 - 5.1 15 Over Voltage Protection (*6) V 6.2 - 7.5 15.0 - 18.0 18.5 - 22.5 29.5 - 36.0 16 Remote ON/OFF control - Possible 17 Parallel Operation - - 18 Series Operation - Possible 19 Operating Temperature (*7) - -20 - +60C (-20 - +50C:100%, +60C:70%) 20 Operating Humidity - 20 - 95%RH (No Condensing) 21 Storage Temperature - -25 - +75C 22 Storage Humidity - 20 - 95%RH (No Condensing) 23 Cooling - Convection Cooling 24 Withstand Voltage - I/P - O/P, I/P - FG : 2kVAC (10mA) for 1min., O/P - CNT(RC) : 100VAC (100mA) for 1min. 25 Isolation Resistance - O/P - FG : 500VDC 100Mohm, O/P - CNT(RC) : 100VDC 10Mohm 2 26 Vibration - 10 - 55Hz : 19.6m/s , X,Y,Z 1hour each. Designed to meet JIS E 3014-2-B 2 27 Shock - 294m/s (time : 63ms) Designed to meet JIS E 3015-2-B 28 Safety -Approved by UL60950-1 & CSA60950-1, Designed to meet EN60950-1 29 Conducted Emission - Designed to meet EN55011/EN55022-A, FCC-ClassA, VCCI-A 30 Radiated Emission - Designed to meet EN55011/EN55022-A, FCC-ClassA, VCCI-A 31 Immunity - Designed to meet IEC61000-4-2(Level 2,3), -4(Level 3), -8(Level 4) 32 Weight (Typ) g 850 33 Size (W x H x D) mm 60 x 95 x 220 ( Refer to Outline Drawing ) *Read instruction manual carefully, before using the power supply unit. =NOTES= *1. At 24VDC, Ta=25C, nominal output voltage and maximum output power. *2. Measure with JEITA RC-9131A probe, Bandwidth of scope :100MHz. *3. 18 - 32VDC, constant load. *4. No load-Full load, constant input voltage. *5. OCP TYPE : Constant current limit with automatic recovery. *6. OVP circuit will shut the output down, manual reset (Re power on). Ratings *7. - Derating at standard mounting. Refer to output derating curve(B029-01-02 ). - Load (%) is percent of maximum output power or maximum output current, whichever is greater. *8. At 24VDC Input.(Refer to instruction manual.) TDK-Lambda RDS100-24 OUTPUT DERATING B029-01-02A *COOLING : CONVECTION COOLING LOAD (%) Ta (C) MOUNTING A MOUNTING B -20 - +40 100 100 50 100 70 60 70 - OUTPUT DERATING CURVE 120 100 80 MOUNTING A 60 MOUNTING B 40 20 0 -20 -10 0 10 20 30 40 50 60 70 Ta (C) A B C D E (STANDARD MOUNTING) LOAD (%)