TL Series 1000 to 2500W Front End Power Supplies Features u 2U high u Up to 12,500W in 19 rack u Hotswap capable u >90% ef ciency u Full power at 65C ambient u Full array of signals Speci cations Model 24V Nominal (Factory Set) 48V Nominal (Factory Set) Output Voltage Range (1) VDC 21 - 28V 42 - 56V Total Regulation % 1 Current limit % 105 to 120% Short Circuit Current % 150% maximum Output Noise mV 480mV maximum, peak to peak (10Hz to 20MHz) Output Rise Time - 100 - 400ms Dynamic Response - 3% in 10ms for a 10 - 100% load change Overvoltage Protection (3) VDC 27 to 30V 54 to 60V Load sharing - 10% Redundancy - Internal or-ing protection I2C programming (1) - Set Output Volt., Monitors AC Present, Converter OK, Thermal pro le, Fan fail Signals (opto isolated) (2) - Converter OK, AC Present, and Over-temperature alarms. Active Low on Fail Remote On/Off - Shuts down output(s) by applying 5V Auxiliary Output - 12V 0.1A bias voltage AC Input - TL1000: 90~264VAC, 95VAC start up TL1500-2500: 180~264VAC, 185VAC start up Power Factor - 0.99 Typical meets EN61000-3-2 Inrush Current A <40A Leakage Current mA <3.2mA Ef ciency (typical) % 92% Immunity - EN61000-4-2, -3, -4, -5, -6, -8 EMC (conducted and radiated) - EN55022, level B, FCC Class B Operating Temperature - -40C to +65C, short duration at 75C, no derating (TL250048: -40C to 65C) Storage Temperature - -40 to +85C Humidity - 5 - 95% RH non condensing Altitude - -200 to 8000 feet, derate max. ambient 2C/1000 feet Shock - IEC68-2-27, MIL STD 810E, 20G Vibration - IEC68-2-64 (random) 20 - 200Hz, 30 minutes Safety Agency - UL60950, CSA 22.2 No. 60950-00, EN60950, CE Mark Size (L x W x H) - 11.12 x 3.41 x 3.45 (stand alone), 14 x 18.9 (incl. ears) x 3.45 (TLR5 rack) Weight lbs Stand alone unit: 5.6lbs, Rack: 9.5lbs Warranty yrs Two Years (1) Contact Factory for application (2) All three signals share a common return - Logic GND (3) Factory Programmable Not Recommended For New Designs 1-800-526-2324 www.us.tdk-lambda.com/lp/ 11 Disclaimer: us.tdk-lambda.com/lp/legal.htmTL Series TL Rack Outline Drawing TL Module Outline Drawing Other Industrial Products Models Output Output Maximum FPS 1U 1kW to 3kW Front end Model Voltage Current Power PX, CC-E, PAQ, PAH, PAF DC-DC Converters HWS, LZSA 15W to 1800W Single output TL100024 24V 40A 1000W TL150024 24V 55A 1500W TL100048 48V 20A 1000W For Additional Information, please visit TL150048 48V 30A 1500W us.tdk-lambda.com/lp/products/tl-series.htm TL250048 48V 50A 2500W TLR5 19 Rack, holds up to 5 TL Modules TLRBP Blanking Panel for One Module Slot TLRC01 Signal Cable TLCK232 RS232 Communications Kit Not Recomended For New Designs 1-800-526-2324 www.us.tdk-lambda.com/lp/ 12 Revision B9: May 2012