Reverse Power Relays
Function:
32
WILMAR Protective Relays 700 Series w/ Adjustable Time Delay
ANSI/IEEE C37.90-1978
UL file No. E58048
CSA file No. LR61158
Several types of Reverse Power Relays are available
TERMINAL STRIPS
#6 - 32 SCREWS including relays sensitive to reverse reactive power
(KVAR). WILMAR is the leading brand of reverse power
relays. Our rugged sealed construction provides con-
tinuous and reliable operation unaffected by shock,
vibration or other severe environments. Reverse Power
Relays are used for the protection of generator sets
operating in parallel.
Model 710TD
Designed for 120, 220 or 266 volt
line to neutral connection
PART NUMBER SELECTION
Model 720TD (X) thru 724TD (X)
13
/64" DIA.
4 MTG. HOLES
Note: Dimensions in inches. Multiply values by 25.4 for dimensions in mm.
PRODUCT SPECIFICATIONS
Part Number 700TD Series
For operation on three phase,
Line Voltage ...................................... Model 710TD = 120 V, 220 V or 266 V, line to neutral three wire
Model 730TD = 120 V, 230 V, 380 V, 460 V, L-L, 3
Phase or 120 V, Single Phase, L-N
All models for three phase, three wire sensing are
available, see part number selection
PART NUMBER SELECTION
Line Frequency ................................. 50-500 Hz.
Sample Part No. 720TDX
Type:
Current Requirements ..................... 0 to 5 amp max direct or from CT with 5 amp
710TD = 120V, 220V, 266V line to neutral
secondary
720TD = 120V, L-L, 3 Phase
721TD = 230V, L-L, 3 Phase
Trip Adjustment ............................... Screwdriver adjustable 4% to 20% (of the 5 amp rating)
722TD = 380V, L-L, 3 Phase
723TD = 460V, L-L, 3 Phase
Time Delay Adjustment.................... 0.5 to 20 seconds, screwdriver adjustable
724TD = 575V, L-L, 3 Phase
725TD = 416V, L-L, 3 Phase
Output Contacts ............................... One set N.O., one set N.C.
730TD = 120 V, 230 V, 380 V, 460 V, L-L, 3 Phase or
Contact Ratings ................................ 5 amp resistive at 120 AC or 28 Vdc
120 V, Single Phase, L-N
Mounting:
Power Consumption ........................ Voltage circuit: 2 VA max.
X = Flange
Current circuit: 4 VA max.
Blank - Stud
Notes: Options:
1. Remove screw for access to the pick-up and time delay adjustments.
7 = Reverse Inductive, 60 Hz
2. Clockwise rotation of the pick-up adjustment will raise the reverse trip point.
3. Clockwise rotation of the time adjustment will increase the time delay.
Consult factory for additional models.
4. Polarity of the voltage and the current connections must be observed for true power sensing.
5. Interchanging connections on terminals 5 and 6, will cause the output contacts to pick-up on forward power and dropout on no power or reverse power.
29
Tyco Electronics / www.tycoelectronics.com / Factory Direct Technical Support: 800-253-4560, ext. 2023 (U.S., Canada, Mexico) or 805-220-2020, ext. 2023 (International)
7
3 /8
5
4 /8