PowerAlert Console Launcher
Highlights
To address Java Runtime Environment (JRE) issues with respect to the SNMPWEBCARD web interface, Tripp
Monitored 30A 208/240V PDU in
Lite recommends using the PowerAlert Console Launcher. This application enables local access of the
0U 70in / 178cm vertical
SNMPWEBCARD interface using a self-contained, compatible JRE version. The Console Launcher can be
rack-mount format
downloaded for free from the Technical Support page or from the Management Solutions / Utilities page.
Reports voltage, frequency and
load level via Ethernet interface
5/5.8kW Single-Phase Monitored PDU, 208/240V
Visual current meter, Toolless
Outlets (36 C13 & 6 C19), L6-30P, 10ft Cord, 0U
button-mount installation
Vertical, TAA
NEMA L6-30P input plug with
10ft / 3m line cord
MODEL NUMBER: PDUMNV30HV2
42 outlets (36 C13, 6 C19) with
included cord retention brackets
Temperature, humidity and
contact-closure monitoring
options
Federal Trade Agreements Act /
TAA Compliant for GSA
Schedule purchases
Package Includes
Rackmount PDU
Plug retention plates
Rack mounting brackets
Owner's manual
Description
Tripp Lite single phase Monitored PDU / Power Distribution Unit offers real-time remote monitoring of voltage, frequency and load levels via built-in network
connection. PowerAlert interface supports custom notification of user-specified remote conditions via email, PowerAlert Console Launcher, SNMP, Telnet or
SSH interface. PDU lighted digital display enables visual monitoring of PDU output current to prevent circuit overloads as additional equipment is added.
Offers reliable rackmount multi-outlet power distribution from any protected UPS, generator or mains input power source. High quality design includes rugged
all-metal housing and secure rack-mount installation with included mounting accessories.
Features
30A single phase 208/240V Monitored Power Distribution Unit / PDU (agency derated to 24A continuous)
Attached 10ft / 3m NEMA L6-30P input cable included
0U 70 in / 178cm vertical rackmount format
42 outlets (36 C13, 6 C19) in two separately breakered 20A output load banks
Toolless installation supported in button-mount compatible equipment racks
Bolt-down brackets support installation in other racks and additional surfaces
Lighted display with select button reports output power consumption in amps in 3 segments (bank 1, bank 2 and total)
Digital display also supports IP-address self-identification and 180 degree display rotation
Built-in SNMP/ethernet interface reports voltage, frequency and PDU loading via network interface or PowerAlert Console Launcher with options for user
specified alarm and notification thresholds
Supports in-rack environmental reporting with optional ENVIROSENSE temperature / humidity sensor and rack access notification with up to 4 optional
SRSWITCH door sensors
1 / 4
DHCP/Manual configuration support
10/100 Mbps auto-sensing allows optimal communication with 10/100 Base-T networks
Real-time clock backup maintains the time of day and date even if the PDU is unpowered
Tiered access privileges allow an administrator and a guest to login simultaneously for monitoring
Alert notifications via email or SNMP traps offer immediate event notification
Firmware upgrade ability supports future product enhancements.
Supports HTTP, HTTPS, PowerAlert Network Management System, SMTP, SNMPv1, SNMPv2, SNMPv3, Telnet, SSH, FTP, DHCP, BOOTP, NTP
protocols
Fully compatible with FREE PowerAlert Network Management System / NMS Software
Included cord retention brackets keep vital network equipment plugged in and continuously powered
Federal Trade Agreements Act / TAA Compliant for GSA Schedule purchases
Specifications
OVERVIEW
PDU Type Monitored
OUTPUT
5.8kW (240V), 5kW (208V), 4.8kW (200V) total capacity / 30A max (Agency de-rated to 24A), 20A max per
Output Capacity Details
breakered outlet bank; 16A max per C19 outlet; 12A max per C13 outlet
Frequency Compatibility 50 / 60 Hz
Output Receptacles (36) C13; (6) C19
Output Nominal Voltage 200; 208; 240
Overload Protection Two 20A breakers protect 21 outlets each
Customized Load Management
n/a
Receptacles
INPUT
PDU Input Voltage 200; 208; 240
Recommended Electrical Service 30A 208/240V
Maximum Input Amps 30
Maximum Input Amps Details Agency de-rated to 24A continuous
PDU Plug Type NEMA L6-30P
Input Cord Length (ft.) 10
Input Cord Length (m) 3.05
Input Phase Single-Phase
USER INTERFACE, ALERTS & CONTROLS
Digital meter reports PDU output current in amps, Scroll IP-address information; Display can be rotated 180 degrees
Front Panel LCD Display
for installation with the input cable at the top
2 / 4