Highlights
SmartPro 120V 3kVA 2.25kW Line-Interactive
3kVA / 3000VA / 2250W line
Sine Wave UPS, 2U, Extended Run, Network
interactive 2U rack/tower UPS,
Card Options, LCD, USB, DB9
Sine Wave
MODEL NUMBER: SMART3000RM2U
120V output, Corrects
brownouts and overvoltages
from 83V to 145V
0.75 Power Factor, Interactive
LCD interface
Extended runtime options up to
1600W
4 post compatible mounting
accessories
98% line-mode efficiency, 2
switched load banks
USB, RS232, EPO and slot for
Network Management Card
Description
options
Tripp Lite SmartPro Line Interactive UPS with enhanced LCD interface offers network-grade power
120V NEMA L5-30P input, 8
protection for critical server, network and telecommunications equipment. Line Interactive Uninterruptible
NEMA 5-15/20R & 1 L5-30R
Power Supply (UPS) with built-in Auto-Voltage Regulation (AVR) actively corrects brownouts and
outlets
overvoltages back to usable levels while maintaining a full battery charge in case of power failure. Tripp
Lite's unique configuration excels in exceptionally poor-power environments with two separate levels of
This product is ENERGY STAR
voltage boost to correct both slight undervoltages and severe brownout conditions. Interactive LCD
qualified for its ability to save
interface reports UPS operating mode, detailed UPS and site-power data, plus enables a variety of UPS
customers money while helping
setup and configuration options. Super-fast switchover from line to battery power occurs within
to protect the environment
milliseconds to maintain operation of connected equipment without interruption or reboot. 98% line-mode
efficiency offers reduced heat emissions and operating costs. Network management interfaces support
Package Includes
communications via USB, RS-232 and installed Network Management Card option. HID-compliant USB
SMART3000RM2U UPS
port enables integration with built-in power management and auto shutdown features of Windows and
System
Mac OS X. Network communications ports enable detailed monitoring of equipment load levels, self-test
USB, Serial & EPO cabling
data and utility power conditions. PowerAlert UPS monitoring software is available via free download.
4-post rackmount installation kit
Switched output load banks enable scheduled and real-time remote reboot and load shedding of select
Instruction manual
outlets. Emergency Power Off (EPO) interface. LCD display panel easily rotates for viewing in rackmount
or tower configurations. Audible alarm with push-button momentary alarm-cancel and silent-mode
configuration options. Programmable self-test. Field-replaceable, hot-swappable battery modules.
Features
Tripp Lite SMART3000RM2U line interactive 2U rack/tower UPS with 3000VA / 3kVA capacity (1600W
maximum load with external battery packs)
Line interactive UPS with Automatic Voltage Regulation (AVR) corrects brownouts and overvoltages
1 / 6from 83 to 145V
NEMA L5-30P input plug; 8 NEMA 5-15/20R and 1 L5-30R output receptacles, Two independently
switchable output load banks
Maintains uninterrupted operation of connected networking equipment during blackouts, surges,
brownouts and overvoltages
High 98% efficiency rating in line-power mode offers reduced power consumption and BTU emisssions
Internal batteries offer 10 minutes at 50% load (1125W) and 3.5 minutes at 100% load (2250W)
Extended runtime is available with optional BP48V24-2U (limit 1), BP48V60RT-3U (multi-pack
compatible) and BP48V27-2US (multi-pack compatible) external battery packs (max output de-rates to
1600 watts with external batteries)
External battery configurations require the use of Tripp Lite's External Battery Configuration Software
(see manual)
Intelligent battery management system extends battery life
Hot-swappable, user-replaceable internal batteries and external battery packs can be replaced with no
disruption to connected equipment
Front panel LCD monitoring screen with MODE and ENTER buttons reports operating mode with 5-bar
battery charge graphic, plus 7 selectable screens of detailed UPS and site power information
LCD interface also supports a number of advanced user setup and operating preferences
Ships with 4 post rackmount installation hardware; Optional 2POSTRMKITWM enables 2 post
rackmount/wallmount installation; Optional 2-9USTAND enables tower placement
Built-in USB, RS-232 and slot for Network Management Card options; Compatible with Tripp Lite UPS
management card options TLNETCARD, WEBCARDLX, SNMPWEBCARD and RELAYIOCARD
HID-compliant USB port enables integration with built-in power management and auto shutdown
features of Windows and Mac OS X
USB & Serial ports enable data-saving unattended shutdown when used with Tripp Lite's PowerAlert
software, available via FREE download from www.tripplite.com/poweralert
Built-in Emergency Power Off (EPO) interface with cable
Specifications
OUTPUT
Output Volt Amp Capacity (VA) 3000
Output kVA Capacity (kVA) 3
Output Watt Capacity (Watts) 2250
Output kW Capacity (kW) 2.25
Output Capacity Details Output is reduced to 1600 watts maximum when used with external battery packs
2 / 6