n STAIRCASE LIGHTING TIMERy ASP-02 INSTRUCTION MANUAL Zakad Mechaniki i Elektroniki ZAMEL sp.j. J.W. Dzida, K. odziska ul. Zielona 27, 43-200 Pszczyna, Poland Tel. +48 (32) 210 46 65, Fax +48 (32) 210 80 04 www.zamelcet.com, e-mail: marketing zamel.pl DESCRIPTION TECHNICAL DATA ASP-02 The ASP-02 staircase timer is desi- gned for corridor and staircase lighting Power supply cables: L(black), N(blue) control. After the circuit triggering the Input rated voltage: 230 V~ timer keeps the light ON for the preset Input voltage tolerance: from -15 to +10 % time and then switches it OFF. It has an Nominal frequency: 50 / 60 Hz adjustable ON-time setting of 10 seconds Rated power consumption: 10,5 mA to 14 minutes. ON-time may be adjusted Release cable: IN (red) by means of a potentiometer. The timer is Output cable: (P) brown fitted with a counter-interlock circuit. The Time adjustment range: from 10 s to 14 min ASP-02 staircase timer may by applied Time accuracy adjustment: 10 % as a time relay for delayed switch-OFF. Time repeatability adjustment: 5 % It is possible to mount the device under a Time adjustment: continuous (rotational potentiometer) push button, in a deep junction box of 60 Load supply indicator: red LED mm diameter. Control: relay 5 A / 250 V AC1 1250VA Number of switch cables: 4 2 FEATURES Section of connecting cables: 1 mm Connecting cable length: 10 cm Staircase lighting control, o Ambient temperature range: from -20 to +45 C Continuous ON-time adjustment of 10 Operating position: free seconds to 14 minutes, Mounting: for 60 mm junction box Relay state indicator red LED, Protection degree: IP20 Device triggering by means of the L or Protective class: II N wire, Overvoltage category: II Applicable together with the single Pollution degree: 2 pole push buttons, illuminated, Dimensions: 50 x 50 x 15 mm Easy applicable together with any exi- Weight: 28 g sting electrical system, Counter-interlock function, Reference standards: PN-EN 60669-1 PN-EN 60669-2-1 PN-EN 61000-4-2,3,4,5,6,11 Relay voltage output, maximum load 5 A. APPERANCE The device should be connected to a sin- glephase system ac- cordingly to current standards. The device CAUTION Load supply indicator connection swill be de- scribed in this manual. Time adjustment Only qualified electricians are allowed Release cable (IN) to connect, assembly and adjust the ti- Power supply cable (N) mer. It is necessary to read this manual Output cable (P) before the timer mounting. Do not di- Power supply cable (L) sassembly the timer casing or you will lose any warranty rights and expose yourself to the electric shock hazard. Before mounting operation make sure of disconnecting the connection wires from the electric network. Use a cross- head screwdriver of 3.5 mm diameter to mount the device. The timer should be carried, stored and used in an ap- propriate way. Do not mount the timer in case of any device parts lack, dama- ge or deformation. In case of malfunc- tion please notify the manufacturer. VER. 002 12.12.2008 k w e c d o u a l r l e b b b re d u e l n b k r w c o a r l b b MOUNTING CONNECTING 1. Disconnect the electric network by means of an appropriate cut-off, cur- rent limiting circuit-breaker or separa- tor. L/N 2. Check if there is no any voltage be- tween power leads by means of an appropriate gauge. 3. Place the ASP-02 timer in a junction box and connect leads accordingly to electrical diagram. 4. Connect power supply circuit. 5. Adjust the light ON-time required by means of the potentiometer. FUNCTIONING The timer is ready to work just right EXAMPLE OF INSTALLATION after its appropriate connecting. The light will be ON for the preset ON-time after the timer is triggered by means of a single pole push button. When the preset time is over, the light will be OFF automatical- ly until the timer is triggered once again. The staircase timer may be connected either to three-conductor or four-con- ductor wiring. Check carefully if trigger and load circuits have been connected correctly. The timer may be damaged if connected inappropriately. In case of the counter-interlock circuit lack the light is continuously ON when the trigger push button is blocked. INNER DIAGRAM L N IN t DIMENSIONS TIME COURSE PRODUCT FAMILY The ASP-02 is a member of the ASx staircase timer family. Version 24 V AC/DC for ASM-02 available Device version: 01 three - or four-conductor wiring 02 anti-lock system 10 dimmer function RELAY CAPACITY Type of casing: M monomodular N surface mounting 375 W 180 W H hermetical P for junction box mounting 90 W 150 W Device symbol VER. 002 12.12.2008 n k e c w d u a o e l l r b b r b