POWER SUPPLY INDICATOR LKM - 01 INSTRUCTION MANUAL Zakad Mechaniki i Elektroniki ZAMEL sp.j. J.W. Dzida, K. odziska ul. Zielona 27, 43-200 Pszczyna, Poland Tel. +48 (32) 210 46 65, Fax +48 (32) 210 80 04 www.zamel.pl, e-mail: marketing zamel.pl DESCRIPTION TECHNICAL PARAMETERS The device is used to signal the LKM - 01 presence of voltage in a three-phase supply system. It is realized by means Input (supply) terminals : L1, L2, L3, N of three LEDs (L1, L2, L3). There are Input rated voltage: 230/400 V~ four colours of the LED diode available Input voltage tolerance: from -15 to +10 % (red, green, yellow and mixed). LKM-01 Rated frequency: 50 / 60 Hz power supply indicator can be used in Rated power consumption (type 10, 20, 30, 40): 1,5 / 6 / 0,9 / 2,8 mA the TN-C supply system (together with Power supply indicator: 3x LED point zero). Number of terminal clamps: 4 2 Section of connecting cables: from 0,2 to 2,5 mm o Ambient temperature range: from -20 to +45 C FEATURES Operating position: free Mounting: TH35 rail (PN-EN 60715) Optical voltage presence signal- Protection degree: IP20 (PN-EN 60529) ling, Protection class: II LED diodes with increased light Overvoltage category: II emission, Pollution degree: 2 long durability of lighting elements, Rated impulse withstand voltage: 1 kV (PN-EN 61000-4-5) easy adaptation for special use, Dimensions (height / width / depth): monomodular (17,5 mm) 90x17,5x66 mm Weight: 47 g monomodular casing, Reference standards : PN-EN 60947-5-1, PN-EN 60947-1 TH-35 DIN rail installation. PN-EN 61000-4-2,3,4,5,6,11 APPEARANCE The device is designed for three-phase installa- tion and must be instal- led in accordance with standards valid in a par- Input (supply) terminals (L1) Input (supply) terminals (N) CAUTION ticular country. The de- vice should be connec- ted according to the details included in this operating manual. Installation, Input (supply) terminals (L2) Input (supply) terminals (L3) connection and control should be car- ried out by a qualified electrician staff, who act in accordance with the servi- ce manual and the device functions. Voltage indicator Disassembling of the device is equal with a loss of guarantee and can cause electric shock. Before installation make sure the connection cables are not un- der voltage. The cruciform head screw- driver 3,5 mm should be used to instal the device. Improper transport, stora- ge, and use of the device influence its wrong functioning. It is not advisable to instal the device in the following cases: if any device part is missing or the de- vice is damaged or deformed. In case of improper functioning of the device contact the producer. ver. 0.4.2 2006.06.20 14:00MOUNTING FUNCTIONING CONNECTING The appropriate LED diode is on 1. Disconnect the power supply from if there is power supply on a particular the mains by the phase fuse, the phase wire. The LED diode is off if there circuit-breaker or the switch-discon- is no power supply. For proper device functioning it is necessary to connect nector that are joined to the proper neutral wire. circuit, 2. Check if there is no voltage on connection cables by means of a INNER DIAGRAM special measure equipment, 3. Install LKM-01 device in the L1 L2 L3 N switchboard on TH-35 DIN rail, 4. Connect the cables with the ter- minals according to installing dia- gram, 5. Switch on the power supply from the mains. DIMENSIONS EXAMPLE OF INSTALLATION PRODUCT FAMILY LKM-01 power supply indicator belongs to LKM voltage indicators family. Typical use: LKM-01 power supply indicator signals the voltage presence or it absence on every phase of a three -phase supply system: L1, L3 diodes in ON position signal voltage presence, L2 diode in OFF position signals voltage absence on L2 phase (fuse is switched off). GUARANTEE CARD There is 24 months guarantee on the product 1. ZAMEL provides a two-year warranty for its products. 2. The ZAMEL warranty does not cover: a) mechanical defects resulting from transport, loading / unloading or other circumstances, b) defects resulting from incorrect installation or operation of ZAMEL products, c) defects resulting from any changes made by CUSTOMERS or third parties, to products sold or equipment necessary for the correct operation of products sold, d) defects resulting from force majeure or other aleatory events for which ZAMEL is not liable. 3. All complaints in relation to the warranty must be provided by the CUSTOMER in writing to the retailer after discovering a defect. 4. ZAMEL will review complaints in accordance with existing regulations. 5. The way a complaint is settled, e.g. replacement of the product, repair or refund, is left to the discretion of ZAMEL. Salesman stamp and signature, date of sale ver. 0.4.2 2006.06.20 14:00