TIME RELAY PCM-04 INSTRUCTION MANUAL Zakad Mechaniki i Elektroniki ZAMEL sp.j. J.W. Dzida, K. odziska ul. Zielona 27, 43-200 Pszczyna, Poland Tel. +48 (32) 210 46 65, Fax +48 (32) 210 80 04 www.zamelcet.com, e-mail: marketing zamel.pl DESCRIPTION TECHNICAL PARAME- TERS PCM-04 The multifunctional time relay PCM-04 has a time function in automa- Input (supply) terminals: L, N tion and control systems. It is equipped Input rated voltage: 230 V~ with 10 independent operating modes Input voltage tolerance: from -15 to +10 % released by power supply voltage or Supply voltage control indicator: LED green external impulse command (coming from L or N line). It has a wide time Nominal frequency: 50 / 60 Hz adjustment range and constant switch Rated power consumption: 25 mA on/off function. The mode change is po- External release terminals: IN, IN, IN (released from L or N) ssible without waiting for the current cyc- Release current: 510 A le to be finished. Operating modes number: 10 Time adjustment range t: from 0,1s to 10days (step+smooth) Time measure accuracy: 0,2 % FEATURES Power/relay supply indicator and time measure: LED red Output relay parameters: 1NO/NC-16 A/250 V AC1 4000 VA 10 operating modes (external release Number of terminal clamps: 8 or from power supply voltage), 2 Section of connecting cables: from 0,2 to 2,50 mm supply voltage control signal - LED o Ambient temperature range: from -20 to +60 C green, Operating position: free power/relay supply indicator and time Mounting: TH 35 rail (PN-EN 60715) measure - LED red, Protection degree: IP20 (PN-EN 60529) time measure accuracy, Protection class: II wide time adjustment range, Overvoltage category: II constant switch on, switch off func- Pollution degree: 2 tion, Rated impulse withstand voltage: 2 kV (PN-EN 61000-4-5) voltage relay output - 1 change over contact (NO/NC) contact max 16 A Dimensions (height / width / depth): monomodular (17,5 mm) 90x17,5x66 mm capacity, Weight: 0,08 kg monomodular casing, Reference standards: PN-EN 60730-1 PN-EN 60730-2-7 PN-EN 61000-4-2,3,4,5,6,11 TH 35 DIN rail installation. APPEARANCE The device is designed for one-phase installation and must be installed in accor- Input supply terminal (L) Input supply terminal (N) dance with standards valid in a particular country. The device should be connected External release terminals CAUTION according to the details inc- (IN, IN, IN) luded in this operating manual. Installation, connection and control should be carried out by a qualified electrician staff, who act in accordance with the service manual and Supply voltage control Power/relay supply indicator the device functions. Disassembling of the indicator (time measure signal) device is equal with a loss of guarantee and can cause electric shock. Before in- Operating mode choice stallation make sure the connection cables are not under voltage. The cruciform head screwdriver 3,5 mm should be used to instal Smooth time adjustment the device. Improper transport, storage, and use of the device influence its wrong functioning. It is not advisable to instal the device in the following cases: if any device Time adjustment choice part is missing or the device is damaged or deformed. In case of improper functioning of the device contact the producer. The symbol stands for selective collection of electrical and electronic devices. Output (load) relay Placing used devices with other terminals (11, 12, 14) waste is not allowed VER. 001 02.10.2009MOUNTING FUNCTIONING 1. Disconnect the power supply from the mains by the phase fuse, the circuit-breaker or the Power supply voltage release: switch-disconnector that are joined to the E F SWITCH ON DELAY - after the supply voltage U has been applied the G D proper circuit, C H U time measure t starts. After the time is over the relay switches on (pos. A B I 11-14). The next switch on interval appears after power supply voltage 2. Check if there is no voltage on connection t t J A reset. cables by means of a special measure equ- E F ipment, SWITCH OFF DELAY - after the supply voltage U has been applied, the D G H U C output relay R switches on immediately (pos.11-14), and the preset time 3. Install PCM-04 device in the switchboard on B I t t t is measured. After the preset time t has been measured, the output B TH 35 DIN rail, A J relay R returns to the initial state (pos.11-12). 4. Connect the cables with the terminals accor- FLASHER STARTING WITH OFF - (Starting from the switch off position). ding to installing diagram, E F After the supply voltage U has been applied, the preset time t measurement D G 5. Switch on the power supply from the mains, H U starts. After the time t is over, the relay switches on (pos.11-14) and the pre- C C B I set time t is measured once more. After the preset time t is over, the output 6. Choose the required operating mode by t t t t t t A J relay R returns to the initial state (pos.11-12), and the next operating cycle of MODE knob, the relay starts. The relay operates until the supply voltage is removed. 7. Adjust the time using the TIME and RANGE FLASHER STARTING WITH ON - (Starting from the switch off position). After knobs, where t=TIMExRANGE. the supply voltage U has been applied, the relay is switched on immediately E F G D (pos.11-14) and the preset time t measurement starts. After the time t is U C H over, the relay switches off (pos.11-12) and the preset time t is measured D B I t t t t t t once more. After the preset time t is over, the output relay R returns to the A J DIMENSIONS initial state, and the next operating cycle of the relay starts. The relay operates until the supply voltage is removed. DELAY IMPULSE GENERATION 0,5 s - after the supply voltage U has E F D G U been applied the time measure t starts. After the time is over the relay swit- H C E ches on (pos. 11-14) for 0,5s, next the relay is switched off (pos.11-12). The B I t 0.5s t 0.5s A J next switch on interval appears after power supply voltage reset.T. External signal release: GROWING MODULATED VOLTAGE VALUE after the impulse release E F D G has been applied to the powered system (growing value) it switches on S C H the relay (pos. 11-14), and starts to measure the preset time. After the F B I t t time t is over the relay switches off (pos.11-12). Impulse time duration is A J not important here (pos.11-12). CONNECTING FALLING MODULATED VOLTAGE VALUE - powered system switches E F D G on the relay after impulse release fades (pos. 11-14) and time measu- S H C G rement starts. The relay is switched off after time t is finished. The follo- B I t t wing time release fades during time measurement does not cause time A J measure from the beginning (no retriggerable). SWTCH ON/OFF DELAY - after the impulse release has been applied to the powered system (growing value) let the relay be switched off (pos.11- E F 12), the same, starts the preset time t measurement. After the time is D G S C over the relay is switched on (pos. 11-14). After the impulse release fade H H B I is detected (falling modulated voltage), the system starts preset time me- t t t t t A J asurement again after it is finished the relay is switched off (pos.11-12). In case impulse duration is longer than the preset time t the relay is switched on for the t time only. BISTABLE RELAY WITH TIME LIMIT - after the impulse release has been E F applied to the powered system (growing value) it switches on the relay D G S C H (pos. 11-14), and starts to measure the preset time. The relay is switched I B t t off during the next impulse release (growing modulated voltage) or after I A J t time t is over if there was no such impulse occurence. Impulse time dura- tion is not important for system operating. GROWING MODULATED VOLTAGE VALUE WITH SWTCH OFF DELAY (RETRIGGERABLE) - after the impulse release has been applied to the E F D G S powered system (growing value) it switches on the relay (pos. 11-14). After C H J B I the impulse release fade is detected (falling modulated voltage), the system t t t t A t starts preset time measurement again and when it is finished the relay is J switched off (pos.11-12). In case impulse duration is longer than the preset time t the relay is switched on for the t time only. Diodes function Time adjustment example t U description Relay turned off 10min 1h 10h 5 6 t = TIMExRANGE, 1min 4 7 time not counted down 11 12 14 10s 1d 8 3 ON 1s 2 9 Relay turned on t = 8 x 1 d = 8 d 1 10 0,1s OFF time not counted down The release Relay turned off t = TIMExRANGE, ATTENTION impulse can 1h 10min 5 6 10h 4 time counted down 7 1min by a signal from L or N line. The operating 1d 10s 3 8 t = 3 x 1 h = 3 h 9 1s ON mode change (in any moment) causes an 2 Relay turned on 1 10 0,1s OFF immediate zeroing of the measured time and time counted down starting the new chosen operating mode. Time adjustment choices are made without delay. GUARANTEE CARD There is 24 months guarantee on the product 1. ZMIE ZAMEL SP. J. assures 24 months guarantee for the product. 2. The manufacturers guarantee does not cover any of the following actions: a) mechanical damage during transport, loading / unloading or under other circumstances, b) damage caused by incorrect product mounting or misuse, c) damage caused by unauthorised modifications made by the PURCHASER or any third parties to the product or any other devices needed for the product functioning, d) damage caused by Act of God or any other incidents independent of the manufacturer. 3. The PURCHASER shall lay any claims in writing to the dealer or ZMIE ZAMEL SP. J. 4. ZMIE ZAMEL SP. J. is liable for processing any claim according to current Polish legislation. 5. ZMIE ZAMEL SP. J. shall process the claim at its own discretion: product repair, replacement or money return. 6. The manufacturers guarantee is valid in the Republic of Poland. 7. The PURCHASERs statutory rights in any applicable legislation whether against the retailer arising from the purchase contract or otherwise are not affected by this warranty. Salesman stamp and signature, date of sale VER. 001 02.10.2009 E E E E E E E E E E E E D D D D D D D D D D M M I I T T O O O O O O O O O O E E G G M M M M M M M M M M N N A A R R