INTERNET-DATASHEET of Art.-No. 9000-41042-0100600 MICO Electronic auxiliary circuit, 2 channels IN: 24VDC OUT: 24V/1-2-4-6ADC MICO 2.6 2 channels Current adjustment 1, 2, 4, 6 A Image - Fire protection (EN 60950-1) - Operating voltage protection (EN 61131-2) Vicarious picture Technical Data Operating voltage 24 V DC (18...30 V DC) Current adjustment 1 A, 2 A, 4 A, 6 A, by countersinked rotary switch, sealed Inrush capacity max. 20 mF (per channel) Group alarm output potential free alarm output 30 V AC/DC, 100 mA Remote start (ON) 10...30 V DC Impulse length min. 20 ms General data Connection Spring clamp terminals Input terminals 1 16 mm Output terminals per output 1 4 mm Alarm terminals 2.5 mm Bridging concept one side, with spring clamp terminals or bridge set (max. 40 A) Mounting method DIN-rail mountable TH35 (EN 60715) Temperature range 0...+55 C (storage temperature -40...+80 C) Commercial data Net weight 90 Weight unit Gram Basic unit pc. Customs tariff number 85363010 Unit (piece) 1 Minimum order quantity (piece) 1 All data on this data sheet was compiled carefully. Liability regarding correctness, completeness, and actuality is limited to gross negligence. Created: 05/14 Murrelektronik GmbH Falkenstrae 3, D-71570 Oppenweiler Fon +49 7191 47-0, Fax +49 7191 47-130 info murrelektronik.com www.murrelektronik.comINTERNET-DATASHEET of Art.-No. 9000-41042-0100600 Circuit diagram Dimension drawing All data on this data sheet was compiled carefully. Liability regarding correctness, completeness, and actuality is limited to gross negligence. Created: 05/14 Murrelektronik GmbH Falkenstrae 3, D-71570 Oppenweiler Fon +49 7191 47-0, Fax +49 7191 47-130 info murrelektronik.com www.murrelektronik.com