ARTESYN INTELLIGENT MP SERIES Up to 1500 Watts Advanced Energy s Artesyn iMP1 series is an AC input DATA SHEET to DC output configurable power system consisting of a microprocessor-controlled PFC front end providing seven Total Power: slots that accept intelligent DC-DC converter modules with Up to 1500 W single, dual or triple outputs ranging from 2 V to 60 V. Single output modules come in four power ranges that can be Input Voltage: mixed and matched and connected in parallel or series to 85 - 264 Vac 120 - 300 Vdc obtain thousands of output combinations customized to any application. of Outputs: Optional extended hold-up module Up to 21 SPECIAL FEATURES (SEMI F47 compliance) Full medical EN60601 approval Increased power density to 50% over 2 standard MP Intelligent I C control External switching frequency sync Voltage adjustment on all outputs 2 input (manual or I C) Optional conformal coating Configurable input and output OK signals and indicators Industrial temp range (-40 C to 70 C) Configurable inhibit/enable No preload required Configurable output UP/DOWN sequencing Industrial shock/vibration (> 50Gs) Configurable current limit SAFETY (foldback or constant current) High power density (8.8 W/cu-in) UL UL60950/UL2601** Intelligent fan (speed control/fault CSA CSA22.2 No. 234 Level 5 status) TUV EN60950/EN60601-1** Downloadable GUI from website BABT Compliance to Customer provided air option EN60950/ uP controlled PFC input with active EN60601 BS7002 inrush protection CB Certificate and report 2 I C monitor of voltage, current, and CE Mark to LVD temp Programmable voltage, current limit, 2 2020 Advanced Energy Industries, Inc. inhibit/enable through I CIMP ELECTRICAL SPECIFICATIONS Input Input ra nge 85 - 264 Vac 120 - 300 Vdc (limited to 300 Vdc in medical applications) Frequency 47 - 63 Hz (iMP1 47 - 440 Hz) Inrush current 40 A peak maximum (soft start) Efficiency Up to 85% full case load Power Factor 0.99 typ. meets EN61000-3-2 (n/a 440 Hz) Turn-on time AC on 2.0 sec typ., inhibit/enable 150 ms typical Programmable delay 50 ms internal turn-on delay (Dual Output only) EMI filter CISPR 22/EN55022 Level B** Leakage current 300 A max. 240 Vac 47 - 63 Hz Radiated EMI CISPR 22/EN55022 Level B** Holdover storage 20 ms minimum (independent of input Vac) additional 34 ms holdover storage with optional HUP module (SEMI F47 compatible). For iMP4 15 ms (low-line), 10 ms (high-line) AC OK > 5 ms early warning min. before outputs lose regulation Full cycle ride thru (50 Hz) (n/a on iMP4 > 750 W 90 Vac) Harmonic distortion Meets EN61000-3-2 Isolation Meets EN60950 and EN60601 Input to output: 4000 Vac input to ground: 1500 Vac output to ground: 400 Vdc Meets 1 MOPP Primary to ground, 2 MOPP Primary to Secondary Global inhibit / enable TTL, Logic 1 and Logic 0 configurable Input fuse (internal) iMP4: 16 A iMP8: 20 A iMP1: 25 A (both lines fused) Warranty 2 years 2 advancedenergy.com