POWER LCM1500 Data Sheet 1500 Watt Bulk Front End Total Power: 1500 W of Outputs: Single Outputs: 12 to 48 V Optional 5.0 V standby Specia l ef aut re S 1500 W output power Low Cost 2.5 x 5.2 x 10.0 12 Watts Per Cubic Inch Electrical Specicfi ations Industrial/Medical safety Input -40 C to 70 C with derating Input range: 90 - 264 Vac (Operating) Optional 5 V 2 A 115/230 Vac (Nominal) Housekeeping TERMINAL BLOCK High Efcfi iency: 89% typical Frequency: 47 - 440 Hz, Nominal 50/60 Variable speed Smart Fans Input fusing: Internal 20 A fuses, both lines fused DSP controlled Inrush current: 25 A peak, either hot or cold start Conformal coat option Power factor: 0.99 typical, meets EN61000-3-2 10% adjustment range Margin programming Harmonics: Meets IEC 1000-3-2 requirements OR-ing FET Input current: 18 A RMS max input current, at 100 Vac Hold up time: 20 ms minimum for Main O/P, at full rated load compil acn e Efficiency: > 91% typical at full load / 230 Vac nominal EMI Class A Leakage current: < 0.3 mA at 264 Vac EN61000 Immunity ON/OFF power switch: N/A RoHS 2 Power line transient: MOV directly after the fuse Isolation: PRI-Chassis 2500 Vdc Basic Saef t Y PRI-SEC 4000 VAC Reinforced 2xMOPP ULcUL Recognized ITE SEC-Chassis 500 Vdc (UL60950-1) ULcUL Recognized Medical LCM1500Q Ef ciency Without the 5 Vsb (ANSI/AAMI ES60601-1) 92.00 TUV-SuD ITE + Medical 90.00 (EN60950-1 and EN60601-1) 88.00 CE LVD (EN60950-1 + ROHS) 86.00 BSMI 100 Vac 84.00 230 Vac CB Report 82.00 - through Demko for IEC60950-1 - through TUV-SuD for 80.00 IEC60601-1 78.00 76.00 25 50 75 100 Loading % Ef ciency %LCM1500 Data Sheet Electrical Specicfi ations Output Output rating: See table 1 90 - 264 Vac Set point: 0.5% 90 - 264 Vac Total regulation range: Main output 2% Combined line/load/transient when measured at output 5 Vsb 1% terminal Rated load: 1500 W maximum Derate linear to 50% from 50 C to 70 C Minimum load: Main output 0.0 A No loss of regulation 5 Vsb 0.0 A Output noise (PARD): 1% max p-p Main output 50 mV max p-p 5 Vsb output Measured with a 0.1 F Ceramic and 10 F Tantalum Capacitor on any output, 20 MHz Output voltage overshoot: No overshoot/undershoot outside the regulation band during on or off cycle Transient response: < 300 Sec 50% load step 1 A/s Step load valid between 10% to 100% of output rating Recovery time to within 1% of set point at onset of transient Max units in parallel: Up to 10 Short circuit protection: Protected, no damage to occur Bounce mode Remote sense: Compensation up to 500 mV Output isolation: Standard per safety requirements Forced load sharing: To within 10% of all shared outputs Analog sharing control Overload protection (OCP): 105% to 125% Main output 120% to 170% 5 Vsb output Overvoltage protection (OVP): 125% to 145% 12 V output 110% to 125% 5 Vsb output Overtemp protection: 10 - 15 C above safe operating area Both PFC and output converter monitored Environmental Specicfi ations Operating temperature: -40 C to +70 C, linear derating to 50% from 50 C to 70 C Storage temperature: -40 C to +85 C Humidity: 20 to 90%, non-condensing. Operating. Conformal coat option available Fan noise: < 45 dBA, 80% load at 30 Altitude: Operating - 16,405 feet (3000m) Storage - 30,000 feet Shock: MIL-STD-810F 516.5, Procedure I, VI. Storage Vibration: MIL-STD-810F 514.5, Cat. 4, 10. Storage