process yellow 116 1375 1797 375 3405 313 2985 240 Embedded Power for Business-Critical Continuity 242 2607 Rev.06.14.11 47 UFE / UFR Series 1 of 6 652 UFE / UFR Series Up to 6000 Watts Total Power: Up to 6000 W Input Voltage: 85 - 264 Vac of Outputs: Single + Aux Output: 24 V & 48 V Electrical Specifications Special Features Rack mounted chassis (1U, 19) Output 3 hot pluggable rectifiers per 1U Output Power: Main output See Table 1 chassis, up to 4 kW redundant or Auxiliary output 11 V 15%, 2.875 W 6 kW available power Lin e regulation: Low line to high line 0.15% max. (180 - 264 Vac input) Load regulation (active share mode): Full load to min. load 0.15% max. Up to 2.6 kW redundant or Turn-on delay: (See Note 4) 5.0 s max. 3.9 kW available per shelf at 90 - 132 Vac input Ambient temp. coefficient: At full load, min. Vin 0.005%/C Stackable to 6U high to provide Voltage adjustability: 48 Vout 42-57 Vdc up to 36 kW available power Adjustable PMBus command 24 Vout 21-28.5 Vdc (See Note 6) Class B conducted EMI EN5502 2 Output setpoint accuracy: 0.5% (See Note 1) Automatic fan speed control with Default output voltage: 48 Vout (active default) 48 V 0.5% 41 A setting 25 C 24 Vout (active default) 27 V 0.5% 48 A fault reporting Auxiliary standby output, 11 V at Voltage droop: 24 Vout 40.3 mV/A 3.0% from approximately 2.8 W (operation set PMBus command) 10 A up to power limit High density up to 22 W/in3 48 Vout 80.6 mV/A 3.0% from High efficiency up to 91% 10 A up to power limit Floating as well as isolated main Total error band: -40 C to +70 C, FL range 1.0% max. output voltage allows positive or Overshoot/undershoot: Main output turn-on/off 0%/0% negative polarity operation Ripple and noise (20 MHz): Main output, -5 C and above 500 mV pk-pk, 150 mV rms EU directive 2002/95/EC Auxiliary output 400 mV pk-pk, 150 mV rms compliant for RoHS Dynamic regulation (except droop mode): Peak dev., 25% load step Recovery 2.5% max. 2 year warranty time 1 ms max. PMBus compliant Current sharing (See Note 3): (I1-I2) / ILIMIT x 100 15% max. Safety All specifications are typical at nominal input, full load at 25 C ambient unless otherwise stated. VDE EN/IEC60950-1 UL/cUL60950-1process yellow 116 1375 1797 375 3405 313 2985 240 242 Embedded Power for Business-Critical Continuity 2607 Rev.06.14.11 47 Input UFE / UFR Series Input volt age range: 88 - 264 Vac 2 of 6 652 (See note 2) 176 - 264 Vac Input frequenc y range: 47 - 63 Hz Input cur rent : 15 A max . Ground leakage cur rent : AC to safet y ground 2 mA max . Notes Input f use (inter nal) B oth lines f used 30 A 1 Final EMI performance is system/shelf Power factor: 50 to 100% load 0.98 dependent. U nder volt age lockout : High line range 176 Vac max . 2 Auto ranging sets power limit based on input (power up) W ide line range 88 Vac. max voltage at turn on. 3 The difference in output current among any U nder volt age lockout : High line range 162 Vac min. two rectifiers operating in parallel does not (power down) LED war ning 176 V max . exceed a value equal to 15% of the rated current limit. This specification applies for W ide line range 76 Vac min. operation with any output current from no LED war ning 88 V max . load to 110 % of maximum. 4 Maximum 15 minute warm up time at light General Specifications loads below -15 C. See Application Note 212 for cold start timing data. Electrical insulation: Input/output 3000 Vac / 4242 Vdc 5 For operation above 1,524 m (5,000 ft), Input/chassis 1500 Vac / 2121 Vdc maximum operation temperature is derated Switching frequency: F ixed 450 kHz by 2 C per 305 m (1,000 ft). Approvals and standards: VDE EN/IEC60950-1 6 Output voltage can be modified on the fly between UL/CUL60950-1 21-28.5 V (24 V model) or 42-57 V (48 V Weight: 5.5 lbs model) PMBus command. 7 PM BUs communication. Pin names in Hold-up time: 48 Vout at rated output power 20 ms min. parenthesis refer to the PMBus version names. 24 Vout at rated output power 20 ms min. UFE2000-96S48PJ and UFE130096S24P J use MTBF ( 25 C): Telcordia SR-332 Issue 1 279,069 hours PMBus. Acoustical noise: Over all conditions 71 dB max . 25 C ambient at rated output power 58 dB t y p. EMC Conducted emissions: EN55022, FCC part 15 Class B (when installed in system) Immunity: Harmonic current: EN61000-3-2 Compliant ESD air/contact: EN61000-4-2 Level 3 Surge: EN61000-4-5 Fast transients: EN61000-4-4 Level 3 Flicker: EN61000-3-3 Compliant Magnetic field: EN61000-4-8 Compliant Radiated immunity: EN61000-4-3 Level 3 EN61000-4-6 Level 3 Conducted immunity: O rder ing Infor mation Output Voltage Power Limit Rated Output Output Line Range at Turn Operating Current Limit Vout +15% / -0% Vout Model Numbers (7) Order Number Power Current (Min) On (Auto Ranging) Line Range (Vout) < Vout (min) Min Max (min) 24 Vout Models 1300 W 21 v 28.5 V 0 A 1300 W 90-264 Vac 65 A 65 A UFE1300-96S24C1J UFE1300-5 48 Vout Models 1300 W 42 V 57 V 0 A 1300 W 90-264 Vac 33 A 33 A UFE2000-96S48PJ UFE2000-9 2000 W 42 V 57 V 0 A 2000 W 180-264 Vac 52 A 52 A 1300 W 42 V 57 V 0 A 1300 W 90-264 Vac 33 A 33 A UFE2000-96S48PDJ UFE2000-9-D 2000 W 42 V 57 V 0 A 2000 W 180-264 Vac 52 A 52 A 1300 W 42 V 57 V 0 A 1300 W 90-264 Vac 33 A 33 A UFE2000-96S48PHDJ UFE2000-9-HD 2000 W 42 V 57 V 0 A 2000 W 180-264 Vac 52 A 52 A Rack O rder ing Infor mation Rack Model Number Hot Plug Interface Number of Power Modules per Pack UFR6000-00J Yes 3 UFR6000-01J Yes 2 + 1 (Split Rack) UFR6000PJ Blank Panel 3