SIL 2 Repeater Power Supply Hart compatible DIN-Rail D1014 Models D1014S, D1014D Characteristics: Technical Data: Supply: General Description: 12-24 Vdc nom (10 to 30 Vdc) reverse polarity protected, The single and dual channel DIN Rail Repeater Power Supply, D1014S and D1014D ripple within voltage limits 5 Vpp. is a high integrity analog input interface suitable for applications requiring SIL 2 level Current consumption 24 V: 110 mA for 2 channels D1014D, (according to IEC61508:2010) in safety related system for high risk industries. 55 mA for 1 channel D1014S with 20 mA output typical. Provides a fully floating dc supply for energizing conventional 2 wires 4-20 mA Current consumption 12 V: 220 mA for 2 channels D1014D, transmitters located in Hazardous Area, and repeats the current in floating circuit 110 mA for 1 channel D1014S with 20 mA output typical. to drive a Safe Area load. Power dissipation: 1.8 W for 2 channels D1014D, 0.9 W for 1 channel D1014S The circuit allows bi-directional communication signals, for Hart transmitters. with 24 V supply voltage and 20 mA output typical. Function: Max. power consumption: at 30 V supply voltage and short circuit condition, 1 or 2 totally independent and isolated channels I.S. analog input for 2 wires loop 3.4 W for 2 channels D1014D, 1.7 W for 1 channel D1014S. powered Hart transmitters, provides 3 port isolation (input/output/supply) and Isolation (Test Voltage): current (source or sink) or voltage output signal. I.S. In/Out 1.5 KV I.S. In/Supply 1.5 KV I.S. In/I.S. In 500 V Signalling LED: Out/Supply 500 V Out/Out 500 V. Power supply indication (green). Input: Field Configurability: 4 to 20 mA (2 wire Tx current limited at 25 mA). mA (source or sink) or V output signal. Transmitter line voltage: Hart Communication Frequency Band: 15.0 V at 20 mA with max. 20 mVrms ripple on 0.5 to 2.5 KHz frequency band. 0.5 to 2.5 KHz within 3 dB. Output: EMC: 4 to 20 mA, on max. 600 load in source mode Fully compliant with CE marking applicable requirements. V min. 5 V at 0 load V max. 30 V in sink mode, current limited at 25 mA or 1 to 5 V on internal 250 shunt (or 2 to 10 V on internal 500 shunt on request). Response time: 20 ms (10 to 90 % step change). Functional Safety Management Certification: FSM Output ripple: 20 mVrms on 250 communication load on 0.5 to 2.5 KHz band. G.M. International is certified by TUV to conform to IEC61508:2010 SIL 3 Frequency response: 0.5 to 2.5 KHz bidirectional within 3 dB (Hart protocol). part 1 clauses 5-6 for safety related systems up to and included SIL3. Performance: Ref. Conditions 24 V supply, 250 load, 23 1 C ambient temperature. Calibration accuracy: 0.1 % of full scale. Linearity error: 0.1 % of full scale. Supply voltage influence: 0.05 % of full scale for a min to max supply change. Load influence: 0.05 % of full scale for a 0 to 100 % load resistance change. Temperature influence: 0.01 % on zero and span for a 1 C change. Compatibility: CE mark compliant, conforms to Directive: 2014/34/EU ATEX, 2014/30/EU EMC, 2014/35/EU LVD, 2011/65/EU RoHS. Environmental conditions: Front Panel and Features: Operating: temperature limits -20 to + 60 C, relative humidity max 95 %. Storage: temperature limits 45 to + 80 C. Safety Description: 1 2 3 4 SIL 2 according to IEC 61508:2010 Ed. 2 for Tproof = 9 / 10 years (10% / >10 % of total SIF). PFDavg (1 year) 1.05 E-04, SFF 87.01%. ATEX: II (1)G Ex ia Ga IIC, II (1)D Ex ia Da IIIC, I (M1) Ex ia Ma I II 3G Ex nA IIC T4 Gc 5 6 7 8 SIL 3 Systematic capability. IECEx / INMETRO: Ex ia Ga IIC, Ex ia Da IIIC, Ex ia Ma I Ex nA IIC T4 Gc UL: AIS / I, II, III / 1 / ABCDEFG, AEx ia IIC 2 fully independent channels. C-UL: AIS / I, II, III / 1 / ABCDEFG, Ex ia IIC Input from Zone 0 (Zone 20), Division 1, FM: NI / I / 2 / ABCD / T4, NI / I / 2 / IIC / T4, AIS / I, II, III / 1 / ABCDEFG, AEx ia IIC installation in Zone 2, Division 2. FM-C: NI / I / 2 / ABCD / T4, NI / I / 2 / IIC / T4, AIS / I, II, III / 1 / ABCDEFG, Ex ia IIC 4-20 mA Input, Output Signal. EAC-EX: 2Ex nA ia Ga IIC T4 Gc X, Ex ia Da IIIC X, Ex ia Ma I X UKR TR n. 898: 2ExnAiaIICT4 X, ExiaI X Hart compatible. associated apparatus and non-sparking electrical equipment. Input and Output short circuit proof. Uo/Voc = 25.2 V, Io/Isc = 93 mA, Po/Po = 585 mW at terminals 14-15, 10-11. Um = 250 Vrms, -20 C Ta 60 C. High Accuracy. Approvals: Three port isolation, Input/Output/Supply. DMT 01 ATEX E 042 X conforms to EN60079-0, EN60079-11, EN60079-26. 1 2 EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1 IECEx BVS 07.0027X conforms to IEC60079-0, IEC60079-11, IEC60079-26. PWR ON IMQ 09 ATEX 013 X conforms to EN60079-0, EN60079-15. In-field programmability by DIP Switch. IECEx IMQ 13.0011X conforms to IEC60079-0, IEC60079-15. ATEX, IECEx, UL & C-UL, FM & FM-C, INMETRO, EAC-EX, INMETRO DNV 13.0108 X conforms to ABNT NBR IEC60079-0, ABNT NBR IEC60079- UKR TR n. 898, TV Certifications. 11, ABNT NBR IEC60079-15, ABNT NBR IEC60079-26, ABNT NBR IEC 61241-11. TV Functional Safety Certification. UL & C-UL E222308 conforms to UL913, UL 60079-0, UL60079-11, UL60079-15 Type Approval Certificate DNV and KR for ANSI/ISA 12.12.01 for UL and CSA-C22.2 No.157-92, CSA-E60079-0, CSA-E60079-11, D1014 maritime applications. CSA-C22.2 No. 213 and CSA-E60079-15 for C-UL. FM & FM-C No. 3024643, 3029921C, conforms to Class 3600, 3610, 3611, 3810, High Reliability, SMD components. ANSI/ISA 12.12.02, ANSI/ISA 60079-0, ANSI/ISA 60079-11, C22.2 No.142, 9 10 11 12 High Density, two channels per unit. C22.2 No.157, C22.2 No.213, E60079-0, E60079-11, E60079-15, GOST R 12.2.007.0-75, R 51330.0-99, R 51330.10-99 Simplified installation using standard GOST 12.2.007.0,22782.0,22782.5 DIN Rail and plug-in terminal blocks. 13 14 15 16 TV Certificate No. C-IS-236198-03, SIL 2 conforms to IEC61508:2010 Ed.2. 250 Vrms (Um) max. voltage allowed to the TV Certificate No. C-IS-236198-09, SIL 3 Functional Safety Certificate conforms to instruments associated with the barrier. IEC61508:2010 Ed.2, for Management of Functional Safety. DNV No.A-13625 and KR No.MIL20769-EL001 Certificates for maritime applications . Mounting: Ordering Information: T35 DIN Rail according to EN50022. Weight: about 170 g D1014D, 115 g D1014S. Model: D1014 Connection: by polarized plug-in disconnect screw terminal blocks to accomodate 2 terminations up to 2.5 mm . 1 channel S Location: Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, 2 channels D Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation. Power Bus enclosure /B Protection class: IP 20. Dimensions: Width 22.5 mm, Depth 99 mm, Height 114.5 mm. Power Bus and DIN-Rail accessories: DIN rail anchor MCHP065 DIN rail stopper MOR016 Terminal block male MOR017 Terminal block female MOR022 G.M. International DTS0181-15 Page 1/2 www.gmintsrl.com Parameters Table: Image: Safety Description Maximum External Parameters Group Co/Ca Lo/La Lo/Ro Cenelec (F) (mH) (H/) Terminals 14-15, 10-11 Uo/Voc = 25.2 V IIC 0.105 4.1 60.7 Io/Isc = 93 mA IIB 0.819 16.4 242.9 Po/Po = 585 mW IIA 2.899 32.8 485.8 I 4.15 54 797.1 IIIC 0.819 16.4 242.9 NOTE for USA and Canada: IIC equal to Gas Groups A, B, C, D, E, F and G IIB equal to Gas Groups C, D, E, F and G IIA equal to Gas Groups D, E, F and G Function Diagram: HAZARDOUS AREA ZONE 0 (ZONE 20) GROUP IIC, SAFE AREA, ZONE 2 GROUP IIC T4, HAZARDOUS LOCATIONS CLASS I, DIVISION 1, GROUPS A, B, C, D, NON HAZARDOUS LOCATIONS, CLASS I, DIVISION 2, CLASS II, DIVISION 1, GROUPS E, F, G, CLASS III, DIVISION 1, GROUPS A, B, C, D T-Code T4, CLASS I, ZONE 2, GROUP IIC T4 CLASS I, ZONE 0, GROUP IIC MODEL D1014D 3 + = = Ch.1 Supply 12-24 Vdc Out 1 4 - = HHT HHT 2 Wire Tx Source I Source V Sink I 14 1 + + + + RL = + mA RL mA In 1 15 2 V I = - - - - 7 + = = Ch.2 Supply 12-24 Vdc Out 2 8 - = HHT HHT 2 Wire Tx Source I Source V Sink I 10 5 + + + + RL = + mA RL mA In 2 11 6 V I = - - - - MODEL D1014S 3 + = = Ch.1 Supply 12-24 Vdc Out 1 4 - = HHT HHT 2 Wire Tx Source I Source V Sink I + 14 1 + + + RL = + mA RL mA In 1 15 2 V I = - - - - G.M. International DTS0181-15 Page 2/2