SIL 2 Switch/Proximity Detector Repeater Relay Output DIN-Rail D1032 Models D1032D, D1032Q Characteristics: Technical Data: Supply: 24 Vdc nom (20 to 30 Vdc) reverse polarity protected, General Description: ripple within voltage limits 5 Vpp. The Switch/Proximity Detector Repeater type D1032 is a DIN Rail unit with two or four Current consumption 24 V: 75 mA for 4 channels D1032Q, independent and isolated channels. The unit can be configured for contact or proximity 60 mA for 2 channels D1032D with input closed and relays energized. detector, NO or NC and for NE or ND relay output. Each channel enables a Safe Area Power dissipation: 1.8 W for 4 channels D1032Q, 1.4 W for 2 channels D1032D load to be controlled by a switch, or a proximity detector, located in Hazardous Area. with 24 V supply voltage, input closed and relays energized. D1032Q quad channel type has four independent input channels and actuates the Max. power consumption: at 30 V supply voltage, short circuit input and corresponding output relay. Two actuation modes can be independently DIP switch relays energized, 2.4 W for 4 channels D1032Q, 2.0 W for 2 channels D1032D. configured on each input channel: NO input/NE relay or NO input/ND relay. Isolation (Test Voltage): I.S. In/Out 1.5 KV I.S. In/Supply 1.5 KV I.S. In/I.S. In 500 V Contact or proximity sensor and its connection line short or open circuit fault detection is Out/Supply 1.5 KV Out 1-3/Out 2-4 1.5 KV. also DIP switch configurable: fault detection can be enabled (in case of fault it Input switching current levels: ON 2.1 mA, OFF 1.2 mA, switch current 1.65 mA 0.2 mA hysteresis. de-energizes the corresponding output relay and turns the fault LED on) or disabled Fault current levels: open fault 0.2 mA, short fault 6.8 mA (in case of fault the corresponding output relay repeats the input line open or closed (when enabled both faults de-energize channel relay with quad channel unit D1032Q or status as configured). actuate fault relay with dual channel unit D1032D). D1032D dual channel type has two input channels and four output relays Input equivalent source: 8 V 1 K typical (8 V no load, 8 mA short circuit). the unit has two DIP switch configurable operating modes: Output: voltage free SPST relay contact. Mode A) input channel actuates in parallel the two output relays. Contact material: AgNi90/10. Relay actuation mode can be independently configured for each output in two modes: Contact rating: 2 A 250 Vac 500 VA, 2 A 250 Vdc 80 W (resistive load). NO input/NE relay or NO input/ND relay. DC Load breaking capacity: Mode B) input channel actuates output relay A configurable in two modes as in V (V) mode A above. Output relay B operates as a fault output (in case of input fault, relay B actuates and the fault LED turns on while relay A repeats the input line 300 as configured). Actuation can be DIP switch configured in two modes: 200 No input fault/energized relay (it de-energizes in case of fault) or Resistive No input fault/de-energized relay (it energizes in case of fault). Load Function: 2 or 4 channels I.S. switch repeater for contact or EN60947-5-6 proximity. 100 Provides 3 port isolation (input/output/supply). Line-fault detection, common to all input signals, available when using Power Bus enclosure. Signalling LEDs: Power supply indication (green), output status (yellow), line fault (red). 50 Field Configurability: NO/NC input for contact/proximitor, NE/ND relay operation and 40 fault detection enable/disable. 30 EMC: Fully compliant with CE marking applicable requirements. Functional Safety Management Certification: 20 FSM G.M. International is certified by TUV to conform to IEC61508:2010 SIL 3 part 1 clauses 5-6 for safety related systems up to and included SIL3. I (A) 10 0.1 0.2 0.3 0.5 1 2 5 6 5 Mechanical / Electrical life: 15 * 10 / 1 * 10 operation, typical. Operate / Release time: 5 / 2 ms typical. Front Panel and Features: Bounce time NO / NC contact: 1 / 5 ms. Response time: 20 ms. 1 2 3 4 SIL 2 according to IEC 61508:2010 Ed.2 Frequency response: 10 Hz maximum. for Tproof = 3 /10 years ( 10% / >10 % of total SIF). Compatibility: CE mark compliant, conforms to Directive: PFDavg (1 year) 2.55 E-04, SFF 71.24 %. 2014/34/EU ATEX, 2014/30/EU EMC, 2014/35/EU LVD, 2011/65/EU RoHS. 5 6 7 8 SIL 3 Systematic capability. Environmental conditions: Operating: temperature limits -20 to + 60 C, relative humidity max 95%. Input from Zone 0 (Zone 20), Division 1, Storage: temperature limits -45 to + 80 C. installation in Zone 2, Division 2. Safety Description: NO/NC contact/proximity Detector Input. Four voltage free SPST Relay contact Output Signals. ATEX: II (1)G Ex ia Ga IIC, II (1)D Ex ia Da IIIC, I (M1) Ex ia Ma I, II 3G Ex nAC IIC T4 Gc Relay Output for fault detection on IECEx / INMETRO: Ex ia Ga IIC, Ex ia Da IIIC, Ex ia Ma I, Ex nAC IIC T4 Gc UL: AIS / I, II, III / 1 / ABCDEFG, AEx ia IIC dual channel version. C-UL: AIS / I, II, III / 1 / ABCDEFG, Ex ia IIC Line fault detection with common signalling FM: NI / I / 2 / ABCD / T4, NI / I / 2 / IIC / T4, AIS / I, II, III / 1 / ABCDEFG, AEx ia IIC available when using Power Bus enclosure. FMC: NI / I / 2 / ABCD / T4, NI / I / 2 / IIC / T4, AIS / I, II, III / 1 / ABCDEFG, Ex ia IIC EAC-EX: 2Ex nA nC ia Ga IIC T4 X, Ex ia Da IIIC X, Ex ia Ma I X. Three port isolation, Input/Output/Supply. PWR ON UKR TR n. 898: 2ExnAnCiaIICT4 X, ExiaI X EMC Compatibility to EN61000-6-2, EN61000-6-4, associated apparatus and non-sparking electrical equipment. 1 2 EN61326-1. Uo/Voc = 9.6 V, Io/Isc = 10 mA, Po/Po = 24 mW at terminals13-14, 15-16, 9-10, 11-12. Um = 250 Vrms, -20 C Ta 60 C. In-field programmability by DIP Switch. 3 4 Approvals: ATEX, IECEx, UL & C-UL, FM & FM-C, INMETRO, STATUS/ DMT 01 ATEX E 042 X conforms to EN60079-0, EN60079-11, EN60079-26. EAC-EX, UKR TR n. 898, TV Certifications. IECEx BVS 07.0027X conforms to IEC60079-0, IEC60079-11, IEC60079-26. FAULT IMQ 09 ATEX 013 X conforms to EN60079-0, EN60079-15. TV Functional Safety Certification. IECEx IMQ 13.0011X conforms to IEC60079-0, IEC60079-15. D1032 INMETRO DNV 13.0108 X conforms to ABNT NBR IEC60079-0, ABNT NBR IEC60079-11, Type Approval Certificate DNV and KR for ABNT NBR IEC60079-15, ABNT NBR IEC60079-26. maritime applications. UL & C-UL E222308 conforms to UL913, UL 60079-0, UL60079-11 for UL and High Reliability, SMD components. CSA-C22.2 No.157-92, CSA-E60079-0, CSA-E60079-11 for C-UL. 9 10 11 12 FM & FM-C No. 3024643, 3029921C, conforms to Class 3600, 3610, 3611, 3810 and High Density, four channels per unit. C22.2 No.142, C22.2 No.157, C22.2 No.213, E60079-0, E60079-11, E60079-15. Simplified installation using standard C-IT.MH04.B.00306 conforms to GOST R IEC 60079-0,GOST R IEC 60079-11, 13 14 15 16 DIN Rail and plug-in terminal blocks. GOST R IEC 60079-15. C 16.0034 X conforms to 7113, 22782.5-78, I 60079-15. 250 Vrms (Um) max. voltage allowed to the TV Certificate No. C-IS-236198-03, SIL 2 conforms to IEC61508:2010 Ed.2. instruments associated with the barrier. TV Certificate No. C-IS-236198-09, SIL 3 Functional Safety Certificate conforms to IEC61508:2010 Ed.2, for Management of Functional Safety. DNV No.A-13778 and KR No.MIL20769-EL001 Certificates for maritime applications. Ordering Information: Mounting: T35 DIN Rail according to EN50022. Weight: about 185 g D1032Q, 165 g D1032D. Model: D1032 Connection: by polarized plug-in disconnect screw terminal blocks to accomodate 2 terminations up to 2.5 mm . 2 channels D Location: Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and 4 channels Q Class I, Zone 2, Group IIC, IIB, IIA T4 installation. Protection class: IP 20. Power Bus enclosure /B Dimensions: Width 22.5 mm, Depth 99 mm, Height 114.5 mm. Power Bus and DIN-Rail accessories: DIN rail anchor MCHP065 DIN rail stopper MOR016 Terminal block male MOR017 Terminal block female MOR022 G.M. International DTS0148-13 Page 1/2 www.gmintsrl.com Parameters Table: Image: Safety Description Maximum External Parameters Group Co/Ca Lo/La Lo/Ro Cenelec (F) (mH) (H/) Terminals 13-14, 15-16 9-10, 11-12 Uo/Voc = 9.6 V IIC 3.5 379 1530 Io/Isc = 10 mA IIB 25 1500 6150 Po/Po = 24 mW IIA 209 3000 12310 I 99 4900 20200 IIIC 25 1500 6150 NOTE for USA and Canada: IIC equal to Gas Groups A, B, C, D, E, F and G IIB equal to Gas Groups C, D, E, F and G IIA equal to Gas Groups D, E, F and G Function Diagram: HAZARDOUS AREA ZONE 0 (ZONE 20) GROUP IIC, SAFE AREA, ZONE 2 GROUP IIC T4, HAZARDOUS LOCATIONS CLASS I, DIVISION 1, GROUPS A, B, C, D, NON HAZARDOUS LOCATIONS, CLASS I, DIVISION 2, CLASS II, DIVISION 1, GROUPS E, F, G, CLASS III, DIVISION 1, GROUPS A, B, C, D T-Code T4, CLASS I, ZONE 2, GROUP IIC T4 CLASS I, ZONE 0, GROUP IIC MODEL D1032Q 3 + = Supply 24 Vdc 4 - voltage free = Proximity Contact 13 1 + = Out 1 In 1 14 2 Common Channels 1-3 = - + 15 5 = Out 2 In 2 16 6 Common Channels 2-4 = - 9 7 + = Out 3 In 3 10 2 Common Channels 1-3 = - 11 8 + = Out 4 In 4 12 6 Common Channels 2-4 = - MODEL D1032D 3 + = Supply 24 Vdc 4 - voltage free = Proximity Contact 13 1 + = Out 1-A In 1 14 2 Common Channel 1 = - 15 5 + = Out 2-A In 2 16 6 Common Channel 2 = - 7 Out 1-B 2 Common Channel 1 8 Out 2-B 6 Common Channel 2 Relay contact shown in de-energized position G.M. International DTS0148-13 Page 2/2