480W Single Output Industrial DIN RAIL NDR-480 series Bauar t gep r u f t S i c h e r h e i t e g e l m a ge o d o s b e w a c g w w w .t u v.c o m ID 2000000000 File Name:NDR-480-SPEC 2015-10-29480W Single Output Industrial DIN RAIL NDR-480 series SPECIFICATION MODEL NDR-480-24 NDR-480-48 DC VOLTAGE 24V 48V RATED CURRENT 20A 10A CURRENT RANGE 0 ~ 20A 0 ~ 10A RATED POWER 480W 480W RIPPLE & NOISE (max.) Note.2 150mVp-p 150mVp-p OUTPUT VOLTAGE ADJ. RANGE 24 ~ 28V 48 ~ 55V VOLTAGE TOLERANCE Note.3 1.0% 1.0% LINE REGULATION 0.5% 0.5% LOAD REGULATION 1.0% 1.0% SETUP, RISE TIME 1500ms, 100ms/230VAC 3000ms, 100ms/115VAC at full load HOLD UP TIME (Typ.) 16ms/230VAC 16ms/115VAC at full load VOLTAGE RANGE Note.4 90 ~ 264VAC 127 ~ 370VDC FREQUENCY RANGE 47 ~ 63Hz POWER FACTOR (Typ.) PF>0.98/115VAC, PF>0.94/230VAC at full load INPUT EFFICIENCY (Typ.) 92.5% 92.5% 4.8A/115VAC 2.4A/230VAC AC CURRENT (Typ.) INRUSH CURRENT (Typ.) 20A/115VAC 35A/230VAC LEAKAGE CURRENT <2mA / 240VAC 105 ~ 130% rated output power OVERLOAD Protection type : Constant current limiting, unit will shut down after 3 sec., re-power on to recover 29 ~ 33V 56 ~ 65V PROTECTION OVER VOLTAGE Protection type : Shut down o/p voltage, re-power on to recover Shut down o/p voltage, recovers automatically after temperature goes down OVER TEMPERATURE -20 ~ +70 (Refer toDerating Curv) WORKING TEMP. 20 ~ 95% RH non-condensing WORKING HUMIDITY ENVIRONMENT STORAGE TEMP., HUMIDITY -40 ~ +85, 10 ~ 95% RH TEMP. COEFFICIENT 0.03%/ (0 ~ 50) Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes Mounting: Compliance to IEC60068-2-6 VIBRATION Ul508, TUV EN60950-1 approved (meet EN60204-1) SAFETY STANDARDS WITHSTAND VOLTAGE I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC SAFETY & ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25/ 70% RH EMC (Note 4) EMC EMISSION Compliance to EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3 EMC IMMUNITY Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A MTBF 146.8K hrs min. MIL-HDBK-217F (25) OTHERS DIMENSION 85.5*125.2*128.5mm (W*H*D) 1.5Kg 8pcs/13Kg/0.9CUFT PACKING NOTE For guidance on how to perform these EMC tests, please refer to EMI testing of component power supplies. (as available on