Product data sheet METSEPM1200 Characteristics PM1200 power meter with energy and demand - with communication Main Range of product PowerLogic PM1000 Device short name PM1200 Product or component type Power meter Complementary Power quality analysis Up to the 9th harmonic Type of measurement Active and reactive power Active and reactive energy Voltage Current Frequency Power factor Us rated supply voltage 44...277 V DC 44...277 V AC (50/60 Hz) Network frequency 50/60 Hz Power consumption in VA < 3 VA at 240 V AC Display type LED Display resolution 3 lines with 4 digits Sampling rate 20 samples/cycle Measurement current 50 mA...6 A Analogue input type Current 0...5 A (impedance <= 0.1 Ohm) Current 0...1 A (impedance <= 0.1 Ohm) Measurement voltage 80...480 V AC 50/60 Hz phase to phase 0 V...999 kV AC 50/60 Hz with external VT Measurement accuracy 1 % power 1 % current 1 % voltage 1 % energy 0.1 % frequency 1 % power factor 1 % apparent power Accuracy class Class 2 (reactive energy according to IEC 62053-23) Mar 09, 2017 1 Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applicationsClass 1 (active energy according to IEC 62053-21) Communication port protocol Modbus: 19.2 kbauds, Communication port support RS485 Environment Electromagnetic compatibility Electrostatic discharge immunity test, conforming to IEC 61000-4-2 Susceptibility to electromagnetic fields, conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test, conforming to IEC 61000-4-4 1.2/50 s shock waves immunity test, conforming to IEC 61000-4-5 Conducted RF disturbances, conforming to IEC 61000-4-6 Immunity to impulse waves, conforming to IEC 61000-4-12 Immunity to microbreaks and voltage drops, conforming to IEC 61000-4-11 Conducted and radiated emissions class class A, conforming to CISPR 11 Mounting mode Flush-mounted Mounting support Panel Type of installation Indoor installation Overvoltage category III IP degree of protection IP51 (front face) conforming to IEC 60529 IP40 (back) conforming to IEC 60529 Relative humidity 5...95 % Ambient air temperature for operation -10...60 C Ambient air temperature for storage -25...70 C Operating altitude 0...2000 m Standards IEC 62053-21 IEC 62052-11 Width 96 mm Depth 80 mm (embedded) Height 96 mm Product weight 0.4 kg Offer Sustainability Sustainable offer status Green Premium product RoHS (date code: YYWW) Compliant - since 1320 - Schneider Electric declaration of conformity Schneider Electric declaration of conformity REACh Reference not containing SVHC above the threshold Reference not containing SVHC above the threshold Product environmental profile Available Product environmental Product end of life instructions Available End of life manual Contractual warranty Warranty period 18 months 2