DENSEI-LAMBDA DLP240-24-1 SPECIFICATIONS CA736-01-01B This specifications sheet also apply to option model /E,/EJ MODE ITEMS DLP240-24-1 1 Nominal Output Voltage V 24 2 Maximum Output Current A 10 3 Maximum Output Power W 240 4 Efficiency (100/230VAC) (Typ) ( * 1 ) % 82/86 5 Input Voltage Range ( * 2 ) 85 ~ 265VAC (47-63Hz) or 120 ~ 370VDC 6 Input Current (100/230VAC) (Typ) ( * 1 ) A 3.0/1.3 o 7 Inrush Current (100/230VAC) (Typ) ( * 3 ) 20A at 100VAC, 45A at 230VAC, Ta=25 C, Cold Start 8 PFHC Built to meet IEC61000-3-2 9 Power Factor (Typ) ( * 1 ) 0.99 / 0.95 10 Output Voltage Range V 21.6~28 Maximum Ripple & Noise 0 Ta60C mV 240 11 ( * 4 ) -10Ta<0C mV 360 12 Maximum Line Regulation ( * 4, 5 ) mV 120 13 Maximum Load Regulation ( * 4, 6 ) mV 192 14 Temperature Coefficient Less than 0.05%/C 15 Over Current Protection ( * 7 ) A 10.5~ 16 Over Voltage Protection ( * 8 ) V 30.0~35.0 17 Hold-Up Time (100/230VAC) ( * 1 ) 20ms /30ms 18 Leakage current ( * 9 ) Less than 0.75mA 19 Parallel Operation - 20 Series Operation Possible ( * 10 ) 85VAC~170VAC :- 10 ~ + 60 C , Convection: -10 ~ +50C ( 100% ) 60C ( 60% ) 21 Operating Temperature 170VAC~265VAC :- 10 ~ + 70 C , Convection: -10 ~ +50C ( 100% ) 70C ( 60% ) 22 Operating Humidity 30 ~ 90 %RH (No dewdrop) 23 Storage Temperature - 30 ~ +85C 24 Storage Humidity 10 ~ 95%RH (No dewdrop) 25 Cooling Convection cooling Input - Output : 3.0kVAC, Input - FG : 2.0kVAC (20mA) for 1min 26 Withstand Voltage Output - FG : 500VAC (100mA) for 1min. 27 Isolation Resistance More than 100M at Ta=25C and 70%RH, Output - FG : 500VDC At no operating and with DIN RAIL 28 Vibration 2 10~55Hz(Sweep for 1min) 9.8m/s Constant, X, Y, Z each 1hour 2 29 Shock (In package) Less than 196m/s Approved by UL60950, CSA60950, EN60950, UL508, CSA C22.2 No14, 30 Safety EN60529 IP20, EN50178 CATEGORY III(Primary), Built to meet DENAN 31 EMI Built to meet VCCI-B, FCC-ClassB, EN55011/EN55022-B 32 Immunity Built to meet IEC61000-6-2 (IEC61000-4-2,-3,-4,-5,-6,-8,-11) 33 Weight (Typ) g 1000 34 Size ( W.H.D.) mm 120x97x110 (Refer to Outline Drawing) * Read instruction manual carefully , before using the power supply unit = NOTES= * 1 : At 100/230VAC and maximum output power, Ta = 25C. Output terminal * 2 : For cases where conformance to various safety specs ( UL, CSA, EN ) are required, to be described as Rail 100 - 240VAC, 50 / 60Hz on name plate. * 3 : Not applicable for the in-rush current to Noise Filter for less than 0.2ms * 4 : Please refer to Fig A for measurement of line & load regulation and output ripple voltage Fig.B (Measure with JEITA RC-9131 probe) L * 5 : 85 - 265VAC, constant load. Input terminal * 6 : No load - Full load(Maximum power), constant input voltage +V * 7 : Constant current limit with automatic recovery A Avoid to operate at overload or dead short for more than 30seconds Output C2 + C1 * 8 : OVP circuit will shutdown output, manual reset. (Re power on) Fig. A terminal * 9 : Measured by each measuring method of UL, CSA, EN and -V DENAN (at 60Hz). L : 150mm *10: At standard mounting method, Fig B. C1 : Elec. Cap 100uF C2 : Film Cap 0.1uF Measurement point - Load(%) is percent of maximum output load ( Item2 and 3 ), do Measurement point for Bandwidth of scope : 100MHz for Vripple Vo Line/Load Regulation. not exceed derating in both Maximum Output Current and Power. -For standard mounting, refer to derating curve (CA736-01-02 )DENSEI-LAMBDA DLP240-24-1 OUTPUT DERATING CA736-01-02 (This specifications sheet also apply to option model /E,/EJ) DLP240-24-1 *COOLING: CONVECTION COOLING MOUNTING: STANDARD MOUNTING LOADING CONDITION(%) 85VAC~170VAC 170VAC~265VAC Ta(C) -10~50 100 100 55 80 100 60 86.7 60 --- 60 70 OUTPUT DERATING CURVE 100 80 60 85~170VAC 170~265VAC 40 20 0 -10 0 10203040 506070 Ta (C) Output connector Rail Input connector STANDARD MOUNTING LOAD (%)