HFE1600 Series Specifications Model HFE1600-12 HFE1600-24 HFE1600-32 HFE1600-48 Input Input Voltage range (2) Vac 85 - 265 Input Frequency Hz 47 - 63 Input Current (Max) 115/230Vac A 14.2 / 8.1 Inrush Current A <35 Leakage Current mA Less than 0.75/1.5mA at 100/230Vac, 60Hz Power Factor Correction - EN61000-3-2, PF >0.98 at full load Harmonic Compliance - Meets IEC61000-3-2 Hold up time ms >10ms, 100/230Vac input, 80% loading Efficiency (4) % 87 / 90 88 / 90 88 / 90 89 / 92 Conducted & Radiated EMI - EN55022 & FCC part 15 Conducted class B, Radiated class A Line Dip - Complies with SEMI F47 (200Vac line only) Immunity - See immunity section Safety Certifications and Markings - IEC/UL/CSA/EN62368-1, 60950-1, CE Mark and UKCA Mark Immunity Test Standard Test Level Criteria Notes ESD EN61000-4-2 2,3 B - Radiated Susceptibility EN61000-4-3 2 A - Electrical Fast Transient Burst EN61000-4-4 2 B - Surge EN61000-4-5 3,4 B - Conducted Susceptibility EN61000-4-6 2 A - Magnetic Fields EN61000-4-8 4 A - >95% for 0.5 cycles B - Voltage Dips and EN61000-4-11 30% for 25/30 cycles C - Input Interruptions >95% for 250/300 cycles C - Specifications Model HFE1600-12 HFE1600-24 HFE1600-32 HFE1600-48 Output Line Regulation mV 30 60 80 120 Load Regulation mV 60 120 160 240 External Load Capacitance uF/A 1000 Ripple & Noise (1) mV 240 240 320 480 Temperature Coefficient %/C <0.02 Minimum Load - No minimum load required Overcurrent Protection % 105-120 Overvoltage Protection (1) % 110% (Tracking). Cycle AC to reset or utilize Remote On/Off Overtemperature Protection (1) - Shutdown with automatic reset. Warning signal provided. Remote Sense Compensation V/wire 0.25 0.5 0.75 1.0 Remote On/Off - Unit ON: 0-0.6V or short, OFF: 2-15V or open circuit Remote Adjust - By either external 0-5V signal or 1k ohm potentiometer AC Fail Signal - Open Collector, ON when AC is within 85-270Vac DC Good Signal - Open Collector, ON when output is above 85 to 95% of setpoint (tracking) Auxiliary Output - 11.2 - 12.5V, 0.5A, 240mV ripple and noise 2 Communication - Optional isolated PMBus (I C) interface ( /S suffix) or plug-in LAN module. See model selectors Indicators - DC OK - Green- >90% 5% of set output voltage AC OK - Green - 85 to 270Vac Green / Red LED Parallel Operation (1) - Yes, single wire current share, up to 90% accuracy (load dependant), up to 10 units 2 HFE1600 Series