HFE2500 Series 2500W 1U Front End Power Supplies Features 1U rackmount containing up to 4 units Internal ORing MOSFET & Current Share High Ef ciency Up to 9,500W in 1U rack TM 2 PMBus (I C) and LAN options Key Market Segments & Applications (HFE2500-48 model) Speci cations Model Input Voltage Range (2) VAC 85 - 265VAC, 47 - 63Hz. See model selector for power derating Input Current (Max) 100/230VAC A 15 / 12A Inrush Current A <50A Power Factor Correction - Meets EN61000-3-2, PF > 0.98 at full load Temperature Coef cient %/C <0.02%/C Overcurrent Protection % 105 - 115% Overvoltage Protection (1) % 110% (Tracking). Cycle AC to reset or utilize Remote On/Off Overtemperature Protection (1) - Shutdown with automatic reset. Warning signal provided Hold-up time ms >10ms, 115/230VAC Input, 80% loading Leakage Current mA < 0.75 / 1.5mA, 100 / 230VAC, 60Hz Remote Sense Compensation - HFE2500-12: 0.25V / Wire, HFE2500-24: 0.5V / Wire, HFE2500-48: 1V / Wire Indicators - AC OK: Green LED, DC OK / Fail: Green / Red LED Remote On/Off - Unit ON: 0 - 0.6V or short, OFF: 2 - 15V or open circuit Parallel Operation (1) - Yes, single wire current share, 95% accuracy, up to 8 units AC Fail Signal - Open Collector, ON when AC is within 85 - 270VAC DC Good Signal - Open Collector, ON when output is above 85 to 95% of setpoint (tracking) Remote Adjust (1) - By either external 0 - 5V signal or 1k potentiometer 2 I C Interface (1) - Isolated from output, Add suf x /S, PMBus compatible Auxiliary Output - 11.2 - 12.5V, 0.5A, 240mV ripple and noise Operating Temperature C -10 to +70C, derate 2%/C from 50 to 60C, 2.5%/C from 60 to 70C Storage Temperature C -30 to +85C Humidity (Non condensing) %RH Operating: 10 - 90%RH, Storage: 10 - 95%RH Cooling - Two variable speed internal fans, air ow exits across input/output connector (3) Withstand Voltage - I/P to O/P 3kVAC, I/P to GND 2kVAC, O/P to GND: HFE2500-12, -24V 500VAC, HFE2500-48 1.5kVAC Isolation Resistance M >100M at 25C & 70%RH, Output to Ground 500VDC Vibration (Basic transportation) - Meets IEC60068-2-64 Shock (Basic transportation) - Meets IEC60068-2-27 Safety Agency Certi cations - UL60950-1, EN60950-1, CE Mark Line Dip - Complies with SEMI F47 (200VAC line only) Conducted and Radiated EMI - EN55032 & FCC part 15 Conducted class B, Radiated class A Immunity - IEC61000-4-2 (lv 2,3), -3 (lv 2), -4 (lv 2), -5 (lv 3,4), -6 (lv 2), -8 (lv 4), -11 Size (W x H x D) in Power Supply: 4.21 x 1.61 x 12.8, Rack: 17.5 x 1.72 x 15.8 Weight g Power Supply: 2100g, Rack: 5000g Warranty yrs Three Years (1) See installation manual for detailed speci cations & test methods (2) Derate linearly 1.3%/V from 100VAC to 85VAC input (3) Reverse air - contact factory 1-800-526-2324 www.us.tdk-lambda.com/lp/ 68 Disclaimer: us.tdk-lambda.com/lp/legal.htmHFE2500 Series Model Selector Output Adjust Max Current Max Power Max Current Max Power (1) (2) (2) Model Voltage Range (Vin>180VAC) (Vin>180VAC) (100<Vin<132VAC) (100<Vin<132VAC) HFE2500-12 12V 9.6 - 13.2V 200A 2400W 125A 1500W HFE2500-12/S 12V 9.6 - 13.2V 200A 2400W 125A 1500W HFE2500-24 24V 19.2 - 29V 104A 2496W 62.5A 1500W HFE2500-24/S 24V 19.2 - 29V 104A 2496W 62.5A 1500W HFE2500-48 48V 38.4 - 58V 52A 2496W 31.25A 1500W HFE2500-48/S 48V 38.4 - 58V 52A 2496W 31.25A 1500W Load Line Ripple & Ef ciency PMBus/ (1) (4) 2 Model Reg Reg Noise (%) I C HFE2500-12 60mV 30mV 240mV 90 / 92% - HFE2500-12/S 60mV 30mV 240mV 90 / 92% Yes HFE2500-24 120mV 60mV 240mV 90 / 92% - HFE2500-24/S 120mV 60mV 240mV 90 / 92% Yes HFE2500-48 240mV 120mV 480mV 91 / 93% - HFE2500-48/S 240mV 120mV 480mV 91 / 93% Yes (4) At 75% load, 100 / 230VAC input Accessories Model Description Maximum Rack Current HFE2500-S1U Four slot 19 rack, IEC320-C20 input connector 320A each side (640A total) HFE2500-S1U-TB Four slot 19 rack, Terminal Block input connector 320A each side (640A total) HFE2500/BP One slot blanking panel, two provided with each rack - HFE2500-LAN Plug in LAN module. Takes up one rack slot. For use with /S models only. - Outline HFE2500S1U 273.6 88.5 OUTPUT 214.5 BUS BAR- M5 HOLES FOR OUTPUT 82.5 61.0 MOUNTING BRACKETS. BUS BAR+ 17.0 TYPx2 4 PLACES SEE NOTE 3. OUTPUT BUS BAR- OUTPUT BUS BAR+ 22.0 TYP x2 SEE NOTE 5. MODULE MODULE MODULE MODULE 125.8 13.0 TYP x2 PMBUS ADRESS SEE NOTE 2. SEE NOTE 4. 13.0 TYPx2 MODULE MODULE MODULE MODULE AIR FLOW MODEL KEY DIRECTION FOR DIFFERENT OUTPUT VOLTAGE MODELS. CONNECTOR DESCRIPTION: IPLT1-120-01-L-D-RA(SAMTEC) SIGNALS & CONTROL CONNECTOR PINS ASSIGNMENT MATING CONNECTOR: IPD1-20-D (SAMTEC) 40 2 1 39 HOLES FOR BLANK PANEL MOUNTING. USE FLAT HEAD SCREW M3x6 8 PLACES MARKED NOTES AA A A 1. MOUNTING HOLES FOR RACK 19 . USE M6x12 SCREWS TO FIX THE UNIT TO A RACK. 2. USE NUT,FLAT WASHER AND SPRING WASHER FOR LOAD WIRES 445.0 1.0 FIXING. USE LUG STUD M6 FOR LOAD WIRES.RECOMMENDED TORQUE: 42-56 Kgf.cm SEE NOTE 1. 3. TO FIX THE MOUNTING BRACKET TO THE CHASSIS USE M5x10 SEMS 483.0 1.0 SCREWS .RECOMMENDED TIGHTENING TORQUE 27~31Kgf.cm. SCREWS MUST NOT PENETRATE THE CHASSIS MORE THAN 6.0 mm. 4. REFER TO INSTRUCTION MANUAL FOR SETTING DETAILS. 5. MODEL NAME, VOLTAGE AND CURRENT RATING AND SAFETY APPROVALS SYMBOLS WILL BE SHOWN HERE ACCORDING TO THE SPECIFICATION. 6. THE HFE-S1U RACK IS SHOWN WITH 4 HFE2500 466.2 1.0 UNITS INSTALLED. For Additional Information, please visit us.tdk-lambda.com/lp/products/hfe-series.htm 1-800-526-2324 www.us.tdk-lambda.com/lp/ 69 Revision B3: Mar 2017 333.0 TYP x2 15.0 TYP x2 +0.4 43.6 0.0 24.5 11.0 409.0 1.0 2.0 10.0 10.7 24.6 TYP 14.0 1.2 426.5 1.0 6.0 14.0 TYPx2 31.7 16.0 TYPx2