PBM - 03 BISTABLE RELAY INSTRUCTION MANUAL Zakad Mechaniki i Elektroniki ZAMEL sp.j. J.W. Dzida, K. odziska ul. Zielona 27, 43-200 Pszczyna, Poland Tel. +48 (32) 210 46 65, Fax +48 (32) 210 80 04 www.zamelcet.com, e-mail: marketing zamel.pl DESCRIPTION TECHNICAL DATA The PBM-03 bistable relay is designed for PBM - 03 lighting and other device control by means Power terminals: L,N of single pole push buttons connected in Rated voltage: 230 V parallel. Successive pressing of any button Rated voltage tolerance: -15 +10 % causes switching ON / OFF the load alter- Rated frequency: 50 / 60 Hz natively. Either L or N line may be a source Rated current: 24 mA of a control impulse. After the impulse has t time adjustment range: 0,1 s 10 dni arrived the load is ON. Then, after t preset Time measure accuracy: 0,2 % time has been over the load is OFF. It is Time setting: 2 x potentiometer (rotary + servo) possible to create lighting control intelligent Supply voltage indicator: green LED systems by means of using the PBM-03 Trigger terminals / wires: IN, IN, IN modules.. Trigger circuit control current: 510 A Relay state indicator: red LED FEATURES Relay contacts parameters: 1NO-16 A / 250 V AC1 4000 VA Connection wires quantity: 8 Bistable lighting control, 2 Connection wire section: 0,2 2,50 mm Time limit function, o Operating temperature: -20 +45 C Power supply indicator - red LED, Operating position: optional Relay state indicator - red LED, Device triggering by means either of Casing fastening: TH 35 rail (according to PN-EN 60715) the L or N wire, Casing IP: IP20 (PN-EN 60529) Operation with many single pole push Protection class: II buttons, illuminated, Overvoltage category: II Time limit function, Pollution level: 2 Two-conductor control system, Dimensions: single-module (17,5 mm) 90x17,5x66 mm Relay voltage output, maximum 16 A Weight: 75 g load, Standard conformity: PN-EN 60669-1, PN-EN 60669-2-1, Single-module casing. PN-EN 61000-4-2,3,4,5,6,11 APPERANCE The timer should be connected to a single- phase system accordin- Power terminal (L) Power terminal (N) gly to current standards. The device connections Trigger terminals CAUTION will be described in this (IN, IN, IN) manual. Only qualified electricians are allowed to assembly, connect and ad- just the timer. It is necessary to read this Supply voltage indicator Relay state indicator manual before the timer mounting. Do (time measure signalling) not disassembly the timer casing or you will lose any warranty rights and expo- se yourself to the electric shock hazard. Continuous time Before mounting operation make sure adjustment of disconnecting the connection wires from the electric network. The timer should be carried, stored and used in Time range an appropriate way. Do not mount the selection timer in case of any device parts lack, damage or deformation. In case of mal- function please notify the manufacturer. Relay output terminals (11, 12, 14)ASSEMBLY, OPERATION CONNECTIONS TIME DIAGRAMS 1. Disconnect the electric network by means of an appropriate cut-off, S current-limiting circuit-breaker or t t separator. t 2. Check if there is no any voltage between power leads by means of an appropriate gauge. UNIT DIAGRAM 3. Mount the PBM-03 device on TH 35 rail. 4. Connect the system leads according L N to the electrical diagram. 5. Connect power supply circuit. IN 14 IN The device is ready to work just right IN T after its appropriate connecting. The 11 light will be ON for the preset ON-time after the relay is triggered by means of a single pole push button. When the preset time is over, the light will be OFF automatically until the device is triggered LOAD once again. The light will be OFF when the device is triggered again during the preset time counting. CASING DIMENSIONS APPLICATION PRODUCT FAMILY The PBM-03 bistable relay is a member of the PBX product family. 24 V AC/DC supply version available for PMB-01, PMB-02, PMB-03 Device version: 01 basic 02 extended: SET, RESET functions and state storage 03 with time limit function Casing type: The bistable relay controls the staircase lighting and operates in three-conductor M single-module P for junction box wiring configuration. It is possible to connect the single pole push buttons (e.g. illumi - nated) in parallel. Device type WARRANTY The product warranty is for a period of 24 months 1. ZMIE ZAMEL SP. J. assures 24 months guarantee for the product. 2. The manufacturers guarantee does not cover any of the following actions: a) mechanical damage during transport, loading / unloading or under other circumstances, b) damage caused by incorrect product mounting or misuse, c) damage caused by unauthorised modifications made by the PURCHASER or any third parties to the product or any other devices needed for the product functioning, d) damage caused by Act of God or any other incidents independent of the manufacturer. 3. The PURCHASER shall lay any claims in writing to the dealer or ZMIE ZAMEL SP. J. 4. ZMIE ZAMEL SP. J. is liable for processing any claim according to current Polish legislation. 5. ZMIE ZAMEL SP. J. shall process the claim at its own discretion: product repair, replacement or money return. 6. The manufacturers guarantee is valid in the Republic of Poland. 7. The PURCHASERs statutory rights in any applicable legislation whether against the retailer arising from the purchase contract or otherwise are not affected by this warranty. Dealer signature & stamp, purchase date