TIME RELAY PCM-01/U INSTRUCTION MANUAL Zakad Mechaniki i Elektroniki ZAMEL sp.j. J.W. Dzida, K. odziska ul. Zielona 27, 43-200 Pszczyna, Poland Tel. +48 (32) 210 46 65, Fax +48 (32) 210 80 04 www.zamelcet.com, e-mail: marketing zamel.pl DESCRIPTION TECHNICAL PARAMETERS PCM-01/U The one mode time relay PCM-01/U has a delayed switch on function (rever- Input (supply) terminals: A1, A2 sive) in automation and control systems. Input rated voltage: 12 240 V AC/DC The relay is released by power supply Input voltage tolerance: -5%, +10 % voltage. It has a wide time adjustment Supply voltage control indicator: LED green range from 0,1 s to 10 days. Additio- Nominal frequency: 50 / 60 Hz nal ON/OFF functions enable constant Rated power consumption: 15 mA switch on, switch off of the output (load). The system has the indicators of power Operating mode number: 1 (switch on delay) supply voltage, relay mode, and time me- Time adjustment range t: from 0,1 s to 10 days asure with the help of red LED diode. Time measure accuracy: 0,2 % Time adjustment: 2x potentiometer (rotary + step) Power/relay supply indicator and time measure: LED red Output relay parameters: 1NO/NC - 16 A / 250 V AC1 4000 VA FEATURES Number of terminal clamps: 5 2 Section of connecting cables: from 0,2 to 2,50 mm o Ambient temperature range: from -20 to +60 C Operating mode: switch on delay (in- Operating position: free put voltage release), supply voltage control indicator - LED Mounting: TH 35 rail (PN-EN 60715) green, Protection degree: IP20 (PN-EN 60529) power/relay supply indicator and time Protection class: II measure - LED red, Overvoltage category: II time measure accuracy, Pollution degree: 2 wide time adjustment range, constant switch on, switch off func- Rated impulse withstand voltage: 2 kV (PN-EN 61000-4-5) tion, Dimensions (height / width / depth): monomodular (17,5 mm) 90x17,5x66 mm relay output - 1 change-over contact Weight: 0,09 kg (NO/NC) contact max 16 A capacity, Reference standards: PN-EN 60730-1 TH 35 DIN rail installation. PN-EN 60730-2-7 PN-EN 61000-4-2,3,4,5,6,11 The device is designed for APPEARANCE one-phase installation and must be installed in accor- Input supply terminal (A1) Input supply terminal (A2) dance with standards valid in a particular country. The device should be connec- CAUTION ted according to the details included in this operating manual. Installa- tion, connection and control should be car- ried out by a qualified electrician staff, who act in accordance with the service manual Supply voltage control indicator Power/relay supply indicator and the device functions. Disassembling of the device is equal with a loss of guarantee and can cause electric shock. Before in- stallation make sure the connection cables are not under voltage. The cruciform head screwdriver 3,5 mm should be used to in- Smooth time adjustment stal the device. Improper transport, storage, and use of the device influence its wrong functioning. It is not advisable to instal the device in the following cases: if any device Time adjustment choice part is missing or the device is damaged or deformed. In case of improper functioning of the device contact the producer. The symbol stands for selective collection of electrical and electronic devices. Placing used Output (load) relay terminals devices with other waste is not allowed (11, 12, 14) VER. 001 08.06.2009MOUNTING FUNCTIONING 1. Disconnect the power supply from the ma- ins by the phase fuse, the circuit breaker or SWITCH ON DELAY - after the supply voltage U has been applied the U time measure t starts. After the time is over the relay switches on (pos. the switch disconnector that are joined to the t t 11-14). proper circuit, 2. Check if there is no voltage on connec- tion cables by means of a special measu- Diodes function re equipment, Time adjustment example t U description 3. Install PCM-01/U device in the switchboard 10min 1h 10h on TH 35 DIN rail, 5 6 1min relay switched on (closed 4 t = TIMExRANGE, 7 10s 1d 8 3 4. Connect the cables with the terminals accor- contacts 11-14), counting ON 1s 2 9 time off ding to installing diagram, t = 8 x 1 d = 8 d 1 10 0,1s OFF 5. Switch on the power supply from the mains, 1h 10min 6. Adjust the time using the TIME and RANGE 5 6 10h relay switched off (closed t = TIMExRANGE, 4 7 1min 1d 3 8 10s knobs, where t=TIMExRANGE. contacts 11-12) counting 1s ON 2 9 time on t = 3 x 1 h = 3 h 1 10 0,1s OFF Switching on the power supply voltage cau- ses the green LED luminosity. The cycle wil be automatically initiated with the adjusted t time. CONNECTING EXAMPLE OF INSTALLATION L L(+) N 12 240 V AC/DC N(-) START/STOP Warning system before the motor starts up. PCM-01/U time relay works in the system where after pushing the START/STOP button a warning acoustic signal is heard to inform the motor is just to start up. This relay cooperates with PCM-04 in bistable relay mode with limited time (MODE=I), it enables to switch on/off the engine by means of one button as well as to set max possible working time. PRODUCT FAMILY PCM-01/U time relay belongs to PCx time relay product family. DIMENSIONS INNER DIAGRAM Voltage type: 24V - 24 V AC/DC U - 12240 V AC/DC: available for PCM-01, PCM-02, PCM-03, PCM-06 U - 24250 V AC 30300 V DC: available for PCM-07 Device type: 01 - 1 operating mode switch on delay 02 - 1 operating mode switch off delay 03 - 1 operating mode cyclic change over 04 - 8 (PCP-04) or 10 (PCM-04) operating modes 06 - 2 operating modes - switch on/ switch off delay 07 - 25 operating modes, digital, two ranges of time operation 10 - 10 operating modes, two ranges of time RELAY CAPACITY operation Casing type: M - modular version (TH 35 DIN rail) P - flush junction box 60 version Device symbol GUARANTEE CARD There is 24 months guarantee on the product 1. ZMIE ZAMEL SP. J. assures 24 months guarantee for the product. 2. The manufacturers guarantee does not cover any of the following actions: a) mechanical damage during transport, loading / unloading or under other circumstances, b) damage caused by incorrect product mounting or misuse, c) damage caused by unauthorised modifications made by the PURCHASER or any third parties to the product or any other devices needed for the product functioning, d) damage caused by Act of God or any other incidents independent of the manufacturer. 3. The PURCHASER shall lay any claims in writing to the dealer or ZMIE ZAMEL SP. J. 4. ZMIE ZAMEL SP. J. is liable for processing any claim according to current Polish legislation. 5. ZMIE ZAMEL SP. J. shall process the claim at its own discretion: product repair, replacement or money return. 6. The manufacturers guarantee is valid in the Republic of Poland. 7. The PURCHASERs statutory rights in any applicable legislation whether against the retailer arising from the purchase contract or otherwise are not affected by this warranty. Salesman stamp and signature, date of sale VER. 001 08.06.2009 E E M M I I T T E E G G N N A A R R