KLAW. ZAS. A/C A/C RTM-30 TEMPERATURE REGULATOR MANUAL INSTRUCTION MOUNTING CONNECTION 1. Disconnect power supply by the pha- Zakad Mechaniki i Elektroniki se fuse, the circuit-breaker or the L switch- disconnector combined to the ZAMEL sp.j. N proper circuit. J.W. Dzida, K. odziska 2. Check if there is no voltage on con- nection cables by means of a special measure equipment. ul. Zielona 27, 43-200 Pszczyna, Poland 3. Install the RTM-30 on the TH-35 DIN Tel. +48 (32) 210 46 65, Fax +48 (32) 210 80 04 rail in the switchboard. www.zamelcet.pl, e-mail: marketing zamel.pl 4. Connect the cables with the termi- nals in accordance with the installing diagram. 5. Switch on the power supply from the DESCRIPTION TEChNICAL DATA mains. The temperature regulator operation is RTM-30 based on heating/regulation curve which we Power supply terminals: A1, A2 Heating obtain by means of choosing points inclu- INNER DIAGRAM Input rated voltage: 85 265 V AC ding both the expected temperature and the reference temperature, by choosing a ready Nominal frequency: 50 / 60 Hz Cooling made curve or by changing options for room Rated power consumption: < 1,5 W regulation. The regulator preserves the tem- perature with the heating source suitable for LCD Temperature sensor terminals: T1 (t reference), T2 (t expected) the reference point (e.g outer or inner tem- Temperature sensor type: KTY 81-210 perature), chosen during configuration pha- o se. Regulation algorithm causes the heating Temperature regulation adjustment range: 5 95 C C costs lower and the same gives full comfort of o Hysteresis: +/- 0,5 C room and weather regulation. The regulator Relay output (supply) terminals: 11, 12, 14, 21, 22, 24 uses two sensors for proper operation. There RTC is also a possibility of extending its existing Receiver switch on indicator: LCD connection cable up to 50 m with a cable sec- LCD display backlight: amber 2 tion of 0,22,5 mm . The reference tempera- Output relay parameters: 2NO/NC 16A / 250V AC1 4000VA ture sensor can be replaced with a standard resistor, which causes one sensor operation DIMENSIONS APPLICATION Number of terminal clamps: 12 as in the standard temperature regulation. 2 Section of connecting cables: 0,2 2,50 mm The regulator is a perfect solution in eve- o Outer temperature sensor ry situation we want to be sure there was a Regulator ambient temperature range: -20 60 C full factor ciculation e.g.: cooling systems or RTM-30 regulator o Sensor ambient temperature range: -20 90 C heating systems, but also in situations where Room temperature sensor Operating mode: suitable temperature difference is necessary freely Floor heating for preserving best conditions with maximum Mounting: rail TH35 (acc to PN-EN 60715) Air-conditioner low costs e.g.: hot water circulation. Repla- Protection degree: IP20 (PN-EN 60529) cing one temperature sensor with a standard resistor has the effect of constant regulation Protection level: II around one point in accordance with the ad- Overvoltage category: II justed curve, close to the chosen points. L N Pollution degree: 2 Replacing one temperature sensor with a potentiometer with similar functions has the Dimensions: double-modular (35 mm) 90x35x66 mm effect of changing a universal regulator into a Weight: 0,160 kg standard temperature regulator with differen- ce regulation possibility by means of curve Reference standards: PN-EN 60730-1 PN-EN 60730-2-7 FAMILy PRODUCT and hysterisis. It allows to control, e.g., the PN-EN 61000-4-2,3,4,5,6,11 heating source in such a way its temperature RTM-30 temperature regulator belongs is higher than the adjusted one including dif- to RTM family product. ference corresponding e.g. the ambient tem- perature loss through windows, etc. APPEARANCE RTM - xx Device type: CEChy 01 - basic Power supply Temperature sensor clamps 02 - LCD display terminals (A1, A2) (T1, T2) Temperature level regulation in the range 03 - weather with LCD of 5 95 C, display two external temperature sensors, LCD display and keypad, Device symbol output receivers temperature regulation in accordance with the reference temperatu- LCD display re, output receivers temperature regulation in WARRANTy CARD accordance with temperature differences, heating sources economical regulation There is 24 months guarantee on the product gives enormous savings during heating 1. ZMIE ZAMEL SP. J. assures 24 months guarantee for the product. 2. The manufacturers guarantee does not cover any of the following actions: period, Control push buttons a) mechanical damage during transport, loading / unloading or under other circumstances, simultaneous regulation possibilities of b) damage caused by incorrect product mounting or misuse, cooling and heating sources, c) damage caused by unauthorised modifications made by the PURCHASER or any third parties to the product or any other devices needed for the product functioning, temperature regulation possibility by d) damage caused by Act of God or any other incidents independent of the manufacturer. means of blending valves, 3. The PURCHASER shall lay any claims in writing to the dealer or ZMIE ZAMEL SP. J. replacing possibility of a reference tempe- 4. ZMIE ZAMEL SP. J. is liable for processing any claim according to current Polish legislation. rature regulator with a standard resistor, 5. ZMIE ZAMEL SP. J. shall process the claim at its own discretion: product repair, replacement or money return. The symbol stands for selective 6. The manufacturers guarantee is valid in the Republic of Poland. double-modular casing with a shield, collection of electrical and Relay output (supply) terminals 7. The PURCHASERs statutory rights in any applicable legislation whether against the retailer arising from the purchase contract or electronical devices. It is TH-35 DIN rail installation, otherwise are not affected by this warranty. (12, 11, 14, 24, 21, 22) forbidden to place the used Salesman stamp and signature, date of sale two output relays of max 16A capacity. devices with other waste. VER. 002 20.05.2010DESCRIPTION SUMMER/WINTER TIME ADJUSTMENT Displayed elements and messages description Use cursor to change from main window to current time and date window or use cursor to choose calculated and expected temperature window . After 15 sec there is an automatic return. Window Window - days of the week - adjusted temperature - automatic mode - reference temperature (T1) - manual mode - winter time Different windows: - choosing one out of two modes by means of which the summer/winter time switching follows: - the switching follows automat- - current date ically the last Sunday of March at 2:00 AM from winter time to summer time, and last Sunday of October at 3:00 AM from summer time to winter time, - day, - year - the user chooses between winter/summer time press OK to enter - automatic, - user - current time MODE ADJUSTMENT - use cursor to choose the required mode or and press OK to confirm after choosing mode, the clock automatically Window adjusts to summer or winter time in reference to the adjusted date choosing mode allows to enter the next window - on/off - automatic mode, - manual mode Use cursors o choose summer/winter time where stands for winter time and stands for summer time, if there was a cursor change the system changes - reference temperature current time by adding or distracting 1 hour, press OK to confirm - anti frozen temperature Confirming the choice the system enters summer/winter time change window. or - T1 or T2 sensor error - comfort temperature There is an escape possibility from every submenu window one level higher in every moment of programming by pressing or without saving the adjusments. - economical temperature - calculated temperature - expected temperature (T2) REGULATOR FUNCTION ADJUSTMENT Push buttons description main window - automatic mode entry Arrow up blinks: opening - enter signal to open the valve. - regulator function adjustment. Choose to different windows - one level higher entry without saving the inserted data control devices on the basis of on/off (heater, air conditoner, main window - manual mode entry Arrow up is on: switch on the heater or open the central heating boiler, temperature control by means of two-way valve), and different windows - one level higher entry without saving the inserted data circulation valve. choose to control temperature by means of three-way main window - main menu entry Arrow down blinks: closing - enter signal to close the valve. or four-way blending valve, press OK to review and to edit different windows - submenu entry or adjusted data saving Arrow down is on: switch on the cooling device or open the ice water Use cursors to choose functions or , press toggle between menu windows or increase/decrease options of the ad- valve. OK to confirm choose function to return to justed value. menu next choose to adjust function parameters: - regulator intensification (dynamics) press OK to enter use cursors to adjust the value in the range of 1 to 10 MAIN MENU press OK to confirm. - full valve opening time press OK to enter use cursors Choose OK to enter menu use cursor to choose to adjust the value in the range of 15 to 1200 seconds options. press OK to confirm. - time between following measurements (so called inte- Function Description grator time) press OK to enter use cursors to adjust PROGRAMMES ASSIGNING the value in the range of 5 to 600 seconds it means TEMPERATURE ADJUSTMENT time equals 1/5 press OK to confirm. PROGRAMME ADJUSTMENT CURRENT TIME ADJUSTMENT CURRENT DATE ADJUSTMENT SUMMER/WINTER TIME ADJUSTMENT REGULATOR FUNCTION ADJUSTMENT There is an escape possibility from every submenu window one level higher in every moment of programming by pressing or without saving the adjusments. SENSOR ADAPTATION ADJUSTMENT HEATING CURVE VALUE ADJUSTMENT OPERATING MODE ChANGE (AUTOMATIC, MANUAL) DATE ADJUSTMENT MANUAL MODE CHANGE - if the system is in the main window and in automatic mode pressing the button causes the system switches into manual mode, with a possibility of direct device switch on/switch off or valve control. Regulator in function: Jf the regulator is in manual mode pressing (holding) cursor causes the heating relay switches on (the relay short circuits contacts 11-14) - symbols and light , when the cursor is released the relay is switched off and and symbols fade . Another pressing (holding) cur- sor lights both and , and switches on the relay - the - current date adjustment press OK to enter relay is switched on only when pressing the cursor . YEAR - use cursor to choose the required year, press OK to confirm, adjustment range from 2000 to 2099 If the regulator is in manual mode pressing (holding) MONTH - use cursor to choose the required month, press OK to confirm cursor causes the cooling relay is switched on (the relay DAY - use cursor to choose the required day of the month, press OK to conrfi m the system is equipped with protection against wrong insertion of days for a short circuits contacts 11-12) - symbols light , when the particular month ( it includes leap years), and it automatically counts the day of the week on the basis of the adjusted date cursor is released the relay is switched off and and Confirming the command allows to enter date adjustment window and current summer/winter time adjustment window if the option is activated. symbols fade . Another pressing (holding) cursor lights There is an escape possibility from every submenu window one level higher in every moment of programming by pressing or without saving the adjusments. and , and switches on the relay - the relay is switched on only when pressing the cursor . TIME ADJUSTMENT Regulator in function: If the regulator is in manual mode pressing (holding) cursor causes the opening valve relay switches on (the relay short circuits contacts 11-14) - arrow lights when the cursor is released the relay is switched off and ights, it symbolizes the previous meter status . Another pressing (holding) cursor lights the arrow and switches on the relay - when the cursor is released, the arrow fades and the relay switches off - the relay is switched on only when pressing the cursor . If the regulator is in manual mode pressing cursor causes the closing valve relay switch- es on (the relay short circuits contacts 21-24) - arrow lights when the cursor is released the relay is switched off it symbolizes the previous meter status . Another pressing - current time adjustment press OK to enter (holding) cursor lights the arrow and switches on the relay - when the cursor is released, HOUR - use cursor use cursor to choose the required hour, you can adjust in format 1-24 or 1-12 (AM) and 1-12 (PM), press OK to confirm the arrow fades and the relay switches off - the relay is switched on only when pressing MINUTES - use cursor to choose the required minutes value, press OK to confirm the cursor . Confirming the minutes value causes seconds reset and time adjustment window entry. There is an escape possibility from every submenu window one level higher in every moment of programming by pressing or without saving the adjusments. If the system is in one of the two mentioned manual modes , press the cursor to return to automatic mode .